A –Crimp terminals in correct position
u
Wire Gauges and Tightening Torque
Use the tables in this section to select the appropriate wires and crimp terminals.
Gauges listed in the tables are for use in the United States.
Note:
1. Wire gauge recommendations based on drive continuous current ratings using 75 °C 600 Vac vinyl-sheathed wire assuming ambient
temperature within 40 °C and wiring distance less than 100 m.
2. Terminal +3 is not used. Do not connect devices or wiring to this terminal.
• Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater
than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to
calculate the amount of voltage drop:
Line drop voltage (V) =
Refer to UL Standards Compliance on page 83
Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed
closed-loop crimp terminals are specifically required when wiring the drive main circuit terminals on models 2A0031 to
2A0396 and 4A0034 to 4A0590. Use only the tools recommended by the terminal manufacturer for
Loop Crimp Terminal Size on page 84
The wire gauges listed in the following tables are Yaskawa recommendations. Refer to NEC table 310-16 for proper wire
gauge selection for terminals -M, +M, -1, +3, and ground.
n
Three-Phase 200 V Class
Model
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2A0011
-M, +M
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2A0017
-M, +M
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide
Figure i.19 Crimp Terminals
3
× wire resistance (Ω/km) × wire length (m) × current (A) × 10
for information on UL compliance.
for closed-loop crimp terminal recommendations.
Table i.5 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
Recomm. Gauge
Terminal
Wire Range
AWG, kcmil
AWG, kcmil
14
14
14 to 8
10
10
14 to 8
i.4 Electrical Installation
-3
crimping.Refer to Closed-
Screw
Tightening Torque
Size
N·m (lb. in.)
1.6 to 1.8
M4
(14 to 16)
2.7 to 3.0
M5
(24 to 27)
1.6 to 1.8
M4
(14 to 16)
2.7 to 3.0
M5
(24 to 27)
23