YASKAWA Z1000 Quick Start Manual page 72

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

i.8 Parameter Table
No.
Name
Carrier Frequency
C6-02
Selection
Carrier Frequency
C6-03
Upper Limit
Carrier Frequency
C6-04
Lower Limit
Carrier Frequency
C6-05
Proportional Gain
d1-01 to
Frequency Reference 1
d1-04;
to 4; 16
d1-16
Jog Frequency
d1-17
Reference
Frequency Reference
d2-01
Upper Limit
Frequency Reference
d2-02
Lower Limit
Master Speed
d2-03
Reference Lower Limit
d3-01
Jump Frequency 1
d3-02
Jump Frequency 2
d3-03
Jump Frequency 3
d3-04
Jump Frequency Width
E1-01
Input Voltage Setting
72
Description
1: 2.0 kHz
2: 5.0 kHz
3: 8.0 kHz
4: 10.0 kHz
5: 12.5 kHz
7: Swing PWM1 (Audible sound 1)
8: Swing PWM2 (Audible sound 2)
9: Swing PWM3 (Audible sound 3)
A: Swing PWM4 (Audible sound 4)
B to E: No setting possible
F: User-defined (determined by C6-03
through C6-05)
Note:
Default setting value is
dependent on parameters
A1-02, Control Method
Selection and o2-04, Drive
Model Selection.
Determines the upper and lower limits for
the carrier frequency.
Carrier Frequency
C6-03
C6-04
Output Frequency
× (C6-05) × K
Output
Frequency
E1-04
Max Output
Frequency
Sets the frequency reference for the drive.
Setting units are determined by parameter
o1-03.
Sets the Jog frequency reference. Setting
units are determined by parameter o1-03.
Sets the frequency reference upper limit as
a percentage of the maximum output
frequency.
Sets the frequency reference lower limit as
a percentage of the maximum output
frequency.
Sets the lower limit for frequency
references from analog inputs as a
percentage of the maximum output
frequency.
Eliminates problems with resonant
vibration of the motor/machine by avoiding
continuous operation in predefined
frequency ranges. The drive accelerates and
decelerates the motor through the
prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥
d3-02 ≥ d3-03.
Sets the dead-band width around each
selected prohibited frequency reference
point.
This parameter must be set to the power
supply voltage.
WARNING! Electrical Shock Hazard.
Drive input voltage (not motor
voltage) must be set in E1-01 for the
protective features of the drive to
function properly. Failure to do so
may result in equipment damage
and/or death or personal injury.
No.
Name
E1-03
V/f Pattern Selection
Maximum Output
E1-04
Frequency
E1-05
Maximum Voltage
E1-06
Base Frequency
Middle Output
E1-07
Frequency
Middle Output
E1-08
Frequency Voltage
Minimum Output
E1-09
Frequency
Minimum Output
E1-10
Frequency Voltage
Middle Output
E1-11
Frequency 2
Middle Output
E1-12
Frequency Voltage 2
E1-13
Base Voltage
E2-01
Motor Rated Current
E2-11
Motor Rated Power
E5-02
Motor Rated Power
E5-03
Motor Rated Current
E5-04
Number of Motor Poles Sets the number of motor poles.
Motor Stator
E5-05
Resistance
Motor d-Axis
E5-06
Inductance
Motor q-Axis
E5-07
Inductance
Motor Induction
E5-09
Voltage Constant 1
Motor Induction
E5-24
Voltage Constant 2
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide
Description
0: 50 Hz, Constant torque 1
1: 60 Hz, Constant torque 2
2: 60 Hz, Constant torque 3 (50 Hz base)
3: 72 Hz, Constant torque 4 (60 Hz base)
4: 50 Hz, Variable torque 1
5: 50 Hz, Variable torque 2
6: 60 Hz, Variable torque 3
7: 60 Hz, Variable torque 4
8: 50 Hz, High starting torque 1
9: 50 Hz, High starting torque 2
A: 60 Hz, High starting torque 3
B: 60 Hz, High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f E1-04 through E1-13
settings define the V/f pattern
Note:
Parameter setting value is
not reset to the default
value when the drive is
initialized.
These parameters are only applicable when
E1-03 is set to F.
To set linear V/f characteristics, set the
same values for E1-07 and E1-09.
In this case, the setting for E1-08 will be
disregarded. Ensure that the four
frequencies are set according to these rules:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
Note:
E1-07, E1-08, and E1-10
to E1-13 are not available
in OLV/PM control mode.
Sets the motor nameplate full load current
in amps. Automatically set during
Auto-Tuning.
Sets the motor rated power in kilowatts (1
HP = 0.746 kW). Automatically set during
Auto-Tuning.
Sets the rated capacity of the motor.
Sets the motor rated current.
Set the resistance for each motor phase.
Sets the d-Axis inductance for the PM
motor.
Sets the q-Axis inductance for the PM
motor.
Sets the induced peak voltage per phase in
units of 0.1 mV/(rad/s) [electrical angle].
Set this parameter when using an IPM
motor with variable torque.
Set E5-24 to 0 when setting this parameter.
Sets the induced phase-to-phase rms
voltage in units of 0.1 mV/(r/min)
[mechanical angle].