No.
A1-02
Setting 0: V/f Control for Induction Motors
Use this mode for simple speed control and for multiple motor applications with low demands to dynamic response or speed
accuracy. The speed control range is 1:40.
Setting 5: Open Loop Vector Control for PM
Use this mode when running a PM motor in variable torque applications that benefit from energy efficiency. The drive can
control an SPM or IPM motor with a speed range of 1:20 in this control mode.
n
b1-01: Frequency Reference Selection for AUTO Mode
Selects the frequency reference source 1.
Note:
If a Run command is input to the drive, but the frequency reference entered is 0 or below the minimum frequency, the AUTO or HAND
indicator LED on the HOA keypad will light and the OFF indicator will flash.
No.
b1-01
Frequency Reference Selection for AUTO Mode
Setting 0: HOA Keypad
Using this setting, the frequency reference can be input by:
• switching between the multi-speed references from d1-01 to d1-04.
• entering the frequency reference on the operator keypad.
Setting 1: Terminals (Analog Input Terminals)
Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1 or A2.
Voltage Input
Voltage input can be used at any of the two analog input terminals. Make the settings as described in
used.
Table i.23 Analog Input Settings for Frequency Reference Using Voltage Signals
Terminal
Signal Level
0 to 10 V
with Zero Limit
A1
0 to 10 V
without Zero
Limit
0 to 10 V
with Zero Limit
A2
0 to 10 V
without Zero
Limit
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide
Parameter Name
Control Method Selection
Parameter Name
Parameter Settings
Signal Level
Function Selection
Selection
H3-01 = 0
(Frequency Reference Bias)
H3-01 = 1
H3-09 = 0
(Frequency Reference Bias)
H3-09 = 1
i.5 Start-Up Programming and Operation
Gain
H3-02 = 0
H3-03
H3-10 = 0
H3-11
Setting Range
0, 5
Setting Range
0 to 3
Table i.23
Notes
Bias
H3-04
Set Jumper S1 on the terminal
board to "V" for voltage input.
H3-12
Default
0
Default
1
for the input
49