CONNeCTION OF The CONTROL
2.2.7.4 DEV ST - LED
DEV ST
off
on
on
on
flashing
Table 4:
2.2.7.5 OPT - LED
OPT
-
Table 5:
2.3 Connection of the control
Observe the following instructions to avoid malfunctions
•
•
•
•
•
•
The terminals of the control terminal block, enocder inputs and communication interface
are securely isolated in accordance with
LED colour
Description
-
Device off or booting
red
Error
yellow
no error, DC link not loaded
green
no error, ready for operation
green
no error, is used for identification of the unit (fb32)
LED function DEV-ST
LED colour
Description
-
reserved for options
LED function OPT
Use shielded / drilled cables.
Lay shield on one side of the inverter onto earth potential.
Install control cables and power cables separately (approx. 10...20 cm distance);
Lay crossings in a right angle.
Separate shield for analog and digital control lines.
Depending on the use of the relay output, an extra shielding is to be used, too.
In case of inductive load on the relay outputs a protective wiring must be provided
(e.g. free-wheeling diode)!
EN
61800-5-1.
19