Step 7 - Terminate The Unused End Of The Engage Cable - enphase M215 Installation And Operation Manual

Microinverter
Hide thumbs Also See for M215:
Table of Contents

Advertisement

Step 7 – Terminate the Unused End of the Engage Cable
Terminate the far end of the Engage Cable as follows.
a. Remove 60mm (2.5 inches) of the cable sheath from the conductors.
b. Slide the hex nut onto the Engage
Cable.
c. Insert the Engage Cable all the way
into the wire organizer (up to the
stop).
d. Bend the individual wires back into
the recesses in the wire organizer so
that they angle
back toward the cable.
e. Cut the individual wires so that no excess extends
outside of the wire organizer. The portions that
angle back will need to extend enough to fit neatly
into the 0.5 cm (0.2 in) recesses in the wire
organizer and flush with the edge of the cap.
f.
Screw the hex nut onto the cap. Never unscrew
the hex nut as this can twist and damage the
cable.
g. Hold the cap with an Enphase disconnect tool, or
insert a #2 Phillips screwdriver.
h. Use a 24mm (7/8 inch) wrench to tighten the hex nut until the latching mechanism is screwed all
the way to the base.
i.
Use a tie wrap or cable clip to attach the cable to the PV racking, so that the Engage Cable and
terminator do not touch the roof.
j.
Ensure that all cabling is located underneath the PV module.
15
hex nut
Copyright  2012 Enphase Energy
M215 Installation and Operation
cap
wire organizer
141-00012 Rev 04