Step 8: Terminate the Unused End of the Engage Cable

WARNING: Risk of Electrical Shock. Do not install the terminator cap while power is
connected.
Terminate the far end of the Engage Cable as follows.
a. Remove 60mm (2.5 inches) of the
cable sheath from the conductors.
b. Slide the hex nut onto the Engage
Cable.
c. Insert the Engage Cable all the way
into the wire organiser (up to the
stop).
d. Bend the individual wires back into
the recesses in the wire organiser so
that they angle back toward the
cable.
e. Cut the individual wires so that no excess extends outside of
the wire organiser. The portions that angle back will need to
extend enough to fit neatly into the 0.5 cm (0.2 in) recesses
in the wire organiser and flush with the edge of the cap.
f.
Place cap over the wire organiser.
g. Hold the cap with an Enphase disconnect tool, or
insert a #2 Phillips screwdriver.
h. Use a 22 mm (7/8 inch) spanner to tighten the
hex nut until the latching mechanism is screwed
all the way to the base. Never unscrew the hex
nut as this can twist and damage the cable.
i.
Use a tie wrap to attach the cable to the
mounting rail, so that the Engage Cable and
terminator do not touch the roof.
j.
Ensure that all cabling is located underneath the
PV module.
21
 2016 Enphase Energy. All rights reserved.
M-Series Microinverter Installation and Operation
wire organiser
hex nut
cap
141-00024 Rev 02b