INPUTS/OUTPUTS
5.9.2 Virtual inputs
SETTINGS INPUTS/OUTPUTS VIRTUAL INPUTS VIRTUAL INPUT 1(64)
VIRTUAL INPUT 1
There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the
menu) and communications protocols. All virtual input operands are defaulted to "Off" (logic 0) unless the
COMMANDS
appropriate input signal is received.
If the
VIRTUAL INPUT x FUNCTION
input. If set to "Enabled," the input operates as shown on the logic diagram and generates output FlexLogic operands in
response to received input signals and the applied settings.
There are two types of operation: self-reset and latched. If
transits from off to on, the output operand is set to on for only one evaluation of the FlexLogic equations and then return to
off. If set to "Latched," the virtual input sets the state of the output operand to the same state as the most recent received
input.
The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic equations. If the
5
operand is to be used anywhere other than internally in a FlexLogic equation, it likely needs to be lengthened in time. A
FlexLogic timer with a delayed reset can perform this function.
5.9.3 Contact outputs
5.9.3.1 Digital outputs
SETTINGS INPUTS/OUTPUTS CONTACT OUTPUTS CONTACT OUTPUT H1
CONTACT OUTPUT H1
5-264
VIRTUAL INPUT 1
FUNCTION: Disabled
VIRTUAL INPUT 1 ID:
Virt Ip 1
VIRTUAL INPUT 1
TYPE: Latched
VIRTUAL INPUT 1
EVENTS: Disabled
is to "Disabled," the input is forced to off (logic 0) regardless of any attempt to alter the
VIRTUAL INPUT x type
Figure 5-138: Virtual inputs logic
CONTACT OUTPUT H1 ID
Cont Op 1
OUTPUT H1 OPERATE:
Off
OUTPUT H1 SEAL-IN:
Off
Range: Disabled, Enabled
Range: up to 12 alphanumeric characters
Range: Self-Reset, Latched
Range: Disabled, Enabled
is "Self-Reset," when the input signal
Range: up to 12 alphanumeric characters
Range: FlexLogic operand
Range: FlexLogic operand
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS