PRODUCT SETUP
RxGOOSE Boolean1 ID
Range: 0 to 12 characters
Default: RxG Bool1
This setting allows the user to assign descriptive text to the name of the RxGOOSE Boolean1 FlexLogic operand. The full
operand name is the value of this setting appended with " On". This descriptive text also appears in the SCL files
associated with the UR.
5
RxGOOSE Boolean1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the RxGOOSE containing the value that drives the RxGOOSE Boolean1 FlexLogic operand. If set to
None, the RxGOOSE Boolean1 FlexLogic operand assumes its default state.
RxGOOSE Boolean1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE Boolean1 FlexLogic operand. A setting of 1
selects the first member, 2 selects the second member, and so on. Entering a number greater than the number of
members in the message and entering the number of a member that is not a BOOLEAN results in the RxGOOSE
Boolean1 FlexLogic operand assuming its default state.
RxGOOSE Boolean1 DEFAULT STATE
Range: On, Off, Latest/On, Latest/Off
Default: On
This setting selects the logic state for the RxGOOSE Boolean1 FlexLogic operand if the UR has just completed startup and
the selected RxGOOSE has not yet received a message, or the selected RxGOOSE has lost its connectivity with the
publisher. The following choices are available:
"On" value defaults the input to logic 1
"Off" value defaults the input to logic 0
"Latest/On" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-up
but before the first communication, the input defaults to logic 1. When communication resumes, the input
becomes fully operational.
"Latest/Off" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-up
but before the first communication, the input defaults to logic 0. When communication resumes, the input
becomes fully operational.
5-54
Figure 5-15: RxGOOSE Boolean panel