CONTROL ELEMENTS
In this example, the phase voltage VT input is programmed as "Delta" with a secondary setting of 120 volts and a ratio of
13800 V / 120 V = 115. The auxiliary VT connection is selected to be VAB since this vector is in phase with VA on the
5
transformer primary. The secondary setting is 69 volts and the auxiliary VT ratio is calculated as 13800 V / 69 V = 200. Note
that the metered values for the auxiliary VT now reflect the AB voltage of the secondary side of the transformer.
5.8.6 Digital elements
SETTINGS CONTROL ELEMENTS DIGITAL ELEMENTS DIGITAL ELEMENT 1(48)
DIGITAL ELEMENT 1
5-228
Figure 5-118: Synchrocheck applied across a transformer
DIGITAL ELEMENT 1
FUNCTION: Disabled
DIG ELEM 1 NAME:
Dig Element 1
DIG ELEM 1 INPUT:
Off
DIG ELEM 1 PICKUP
DELAY:
0.000 s
DIG ELEM 1 RESET
DELAY:
0.000 s
DIG ELEMENT 1
PICKUP LED: Enabled
DIG ELEM 1 BLOCK:
Off
DIGITAL ELEMENT 1
TARGET: Self-reset
DIGITAL ELEMENT 1
EVENTS: Disabled
Range: Disabled, Enabled
Range: 16 alphanumeric characters
Range: FlexLogic operand
Range: 0.000 to 999999.999 s in steps of 0.001
Range: 0.000 to 999999.999 s in steps of 0.001
Range: Disabled, Enabled
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS