GE c60 Instruction Manual page 271

Breaker protection system
Hide thumbs Also See for c60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
PMU 1 VA... IG CALIBRATION MAGNITUDE
sources, and they allow the user to calibrate each channel (four voltages and four currents) individually to offset errors
introduced by VTs, CTs. The setting values are effectively a multiplier of the measured magnitudes. Therefore, entering a
multiplier greater than 100% of the secondary signal increases the true signal, and a multiplier less than 100% value of the
secondary signal reduces the true signal.
— This setting allows correcting positive- and negative-sequence voltages for vector groups of
PMU 1 SEQ VOLT SHIFT ANGLE
power transformers located between the PMU voltage point and the reference node. This angle is effectively added to the
positive-sequence voltage angle and subtracted from the negative-sequence voltage angle. Note that:
When this setting is not "0°", the phase and sequence voltages do not agree. Unlike sequence voltages, the phase
voltages cannot be corrected in a general case and therefore are reported as measured.
When receiving synchrophasor data at multiple locations, with possibly different reference nodes, it can be more
beneficial to allow the central locations to perform the compensation of sequence voltages.
This setting applies to PMU data only. The C60 calculates symmetrical voltages independently for protection and
control purposes without applying this correction.
When connected to line-to-line voltages, the PMU calculates symmetrical voltages with the reference to the AG
voltage and not to the physically connected AB voltage (see the Metering Conventions section in Chapter 6).
— This setting allows correcting positive and negative-sequence currents for vector groups of
PMU 1 SEQ CURR SHIFT ANGLE
power transformers located between the PMU current point and the reference node. The setting has the same meaning for
currents as the
PMU 1 SEQ VOLT SHIFT ANGLE
except rare applications when the voltage and current measuring points are located at different windings of a power
transformer.
5.5.7.11 PMU triggering overview
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1(2)  PMU 1(2)
TRIGGERING
 PMU 1
 TRIGGERING
Each Phasor Measurement Unit (PMU) contains five triggering mechanisms to facilitate triggering of the associated PMU
recorder, or cross-triggering of other PMUs in the system. They are:
Overfrequency and underfrequency
Overvoltage and undervoltage
Overcurrent
Overpower
High rate of change of frequency
The pre-configured triggers can be augmented with a user-specified condition built freely using programmable logic of the
relay. The entire triggering logic is refreshed once every two power system cycles.
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
— These settings recognize applications with protection class voltage and current
setting has for voltages. Normally, the two correcting angles are set identically,
 PMU 1 USER
 TRIGGER
 PMU 1 FREQUENCY
 TRIGGER
 PMU 1 VOLTAGE
 TRIGGER
 PMU 1 CURRENT
 TRIGGER
 PMU 1 POWER
 TRIGGER
 PMU 1 df/dt
 TRIGGER
See page 5-146
See page 5-146
See page 5-147
See page 5-148
See page 5-149
See page 5-150
SYSTEM SETUP
5
5-145

Advertisement

Table of Contents
loading

Table of Contents