CHAPTER 5: SETTINGS

5.7.9 Sensitive directional power

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  POWER  SENSITIVE DIRECTIONAL POWER 
DIRECTIONAL POWER 1(2)
 DIRECTIONAL
 POWER 1
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-107: Open pole detector logic
DIR POWER 1
FUNCTION: Disabled
DIR POWER 1
SOURCE: SRC 1
DIR POWER 1
RCA: 0°
DIR POWER 1
CALIBRATION: 0.00°
DIR POWER 1 STG1
SMIN: 0.100 pu
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0 to 359° in steps of 1
Range: 0 to 0.95° in steps of 0.05
Range: –1.200 to 1.200 pu in steps of 0.001
5
5-211