CHAPTER 6: ACTUAL VALUES
The latest 15 fault reports can be stored. The most recent fault location calculation (when applicable) is displayed in this
menu, along with the date and time stamp of the event which triggered the calculation. See the
menu for assigning the source and trigger for fault calculations. See the
SETUP  FAULT REPORTS
menu for manual clearing of the fault reports and to the
RECORDS
menu for automated clearing of the fault reports.

6.4.2 Event records

ACTUAL VALUES  RECORDS  EVENT RECORDS
 EVENT RECORDS
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological
order from most recent to oldest. When all 1024 event records have been filled, the oldest record is removed as a new
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated
with the event trigger. See the

6.4.3 Oscillography

ACTUAL VALUES  RECORDS  OSCILLOGRAPHY
 OSCILLOGRAPHY
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The cycles
per record value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillography
section of chapter 5 for details.
A trigger can be forced here at any time by setting "Yes" to the FORCE TRIGGER? command. See the
menu for information on clearing the oscillography records.
RECORDS

6.4.4 Data logger

ACTUAL VALUES  RECORDS  DATA LOGGER
 DATA LOGGER
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
EVENT: XXXX
RESET OP(PUSHBUTTON)
EVENT: 3
POWER ON
EVENT: 2
POWER OFF
EVENT: 1
EVENTS CLEARED
COMMANDS
 CLEAR RECORDS
FORCE TRIGGER?
No
NUMBER OF TRIGGERS:
0
AVAILABLE RECORDS:
0
CYCLES PER RECORD:
0.0
LAST CLEARED DATE:
2000/07/14 15:40:16
OLDEST SAMPLE TIME:
2000/01/14 13:45:51
NEWEST SAMPLE TIME:
2000/01/14 15:21:19
SETTINGS  PRODUCT SETUP  CLEAR RELAY RECORDS
Date and time stamps
EVENT 3
DATE: 2000/07/14
EVENT 3
TIME: 14:53:00.03405
menu for clearing event records.