CHAPTER 3: INSTALLATION

3.7.1 Configure serial communication

A computer with an RS232 port and a serial cable are required. To use the RS485 port at the back of the relay, a GE Digital
Energy F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for details.
1.
Connect the computer to the F485 and the F485 to the RS485 terminal on the back of the UR device, or connect
directly the computer to the RS232 port on the front of the relay.
2.
In the EnerVista Launchpad software on the computer, select the UR device to start the software.
3.
Click the Device Setup button to open the Device Setup window, and click the Add Site button to define a new site.
4.
Enter a site name in the Site Name field. Optionally add a short description of the site along with the display order of
devices defined for the site. This example uses "Location 1" as the site name. When done, click the OK button. The new
site appears in the upper-left list in the EnerVista UR Setup window.
5.
Click the Device Setup button, then select the new site to re-open the Device Setup window.
6.
Click the Add Device button to define the new device.
7.
Enter a name in the Device Name field and a description (optional) of the site.
8.
Select "Serial" from the Interface drop-down list. This displays a number of interface parameters that must be entered
for serial communications.
9.
Enter the COM port used by the computer, the baud rate, and parity settings from the front panel
SETUP  COMMUNICATIONS  SERIAL PORTS
 PRODUCT SETUP  COMMUNICATIONS  MODBUS PROTOCOL  MODBUS SLAVE ADDRESS
fields.
10. Click the Read Order Code button to connect to the C60 and upload the order code to the software. If a
communications error occurs, ensure that the EnerVista UR Setup serial communications values entered in the
previous step correspond to the relay setting values.
11. Click the OK button when the relay order code has been received. The new device is added to the Site List window (or
Online window) located in the top left corner of the main EnerVista UR Setup window.
The device has now been configured for RS232 communications. Proceed to the Connect to the C60 section to begin
communication.
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 3-53: Configuring serial communication
menu, and the relay slave address setting from the front panel
CONFIGURE THE C60 FOR SOFTWARE ACCESS
SETTINGS  PRODUCT
menu in their respective
3
SETTINGS
3-45