CHAPTER 5: SETTINGS
Buffered Report1 RptID
Range: 0 to 129 VisibleString characters
Default: empty string
The entered value sets the RptID value in Buffered Report1 messages, and it can be used by the client to discriminate
Buffered Report1 messages from other messages. If the number of characters entered is zero, the value used for RptID
in messages is an ObjectReference to the report's control block, that is, "<LDName>/LLN0$BR$"BRCB01".
Buffered Report1 DatSet
Range: None, DataSet01, DataSet02, ...
Default: None
This setting selects the data set whose members' status is reported in Buffered Report1 messages using the UR Setup
software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as
described later.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0$" and the data
set name, is used in the datSet field of report messages, and it can be used by the client to discriminate Buffered Report1
messages from other messages.
Buffered Report1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
The entered value sets the confRev value in Buffered Report1 messages, and it can be used by clients to discriminate
report messages of the expected configuration revision from messages of a different revision. The standard requires
that confRef be incremented each time the members or the order of the members is changed, and each time the data
set name is changed. The standard states that the value of 0 is reserved.
Buffered Report1 OptFlds
Range: The check box for each individual bit can be enabled or not (see figure)
Default: All bits true
The OptFlds setting is bitstring that controls which of the optional fields are included in report messages. The figure
shows the available option bits.
Buffered Report1 BufTm
Range: 0 to 4294967295 in steps of 1
Default: 0
The entered value sets the time interval in milliseconds for the buffering of events for inclusion in a single report.
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-19: Options for buffered report messages
PRODUCT SETUP
5
5-59