Advertisement

FRONT PANEL INTERFACE
USER-PROGRAMMABLE LEDS
Default labels for LED panel 2
The default labels are intended to represent the following:
GROUP 1...6 — The illuminated GROUP is the active settings group
BREAKER 1(2) OPEN — The breaker is open
BREAKER 1(2) CLOSED — The breaker is closed
4
BREAKER 1(2) TROUBLE — A problem related to the breaker has been detected
SYNCHROCHECK NO1(2) IN-SYNCH — Voltages have satisfied the synchrocheck element
RECLOSE ENABLED — The recloser is operational
RECLOSE DISABLED — The recloser is not operational
RECLOSE IN PROGRESS — A reclose operation is in progress
RECLOSE LOCKED OUT — The recloser is not operational and requires a reset
Firmware revisions 2.9x and earlier support eight user setting groups; revisions 3.0x and higher support six
setting groups. For convenience of users using earlier firmware revisions, the relay panel shows eight setting
NOTE
groups. Even though the LEDs have default labels, they are fully user-programmable.
The relay is shipped with the default label for the LED panel 2. The LEDs, however, are not pre-programmed. To match the
pre-printed label, the LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. The
LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explained in
the next section.

4.2.8 Custom LED labeling

4.2.8.1 Enhanced faceplate
The following procedure requires these pre-requisites:
EnerVista UR Setup software is installed and operational
4-20
Figure 4-21: LED panels 2 and 3 (index template)
Figure 4-22: LED panel 2 (default labels)
USER-PROGRAMMABLE LEDS
842784A1.CDR
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: INTERFACES
842782A1.CDR