Set Date And Time; Relay Maintenance - GE c60 Instruction Manual

Breaker protection system
Hide thumbs Also See for c60:
Table of Contents

Advertisement

CHAPTER 7: COMMANDS AND TARGETS
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a
command setting to "Yes" and pressing the
"No."

7.1.3 Set date and time

COMMANDS  SET DATE AND TIME
 COMMANDS
 SET DATE AND TIME
The date and time can be entered on the faceplate keypad. The time setting is based on the 24-hour clock. The complete
date, as a minimum, must be entered to allow execution of this command. The new time and date take effect when the
key is pressed.
ENTER
When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time is over-
written.
The timescale of the entered time is local time, including daylight savings time where and when applicable.

7.1.4 Relay maintenance

COMMANDS  RELAY MAINTENANCE
 COMMANDS
 RELAY MAINTENANCE
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are
activated by changing a command setting to "Yes" and pressing the
reverts to "No." The service command is activated by entering a numerical code and pressing the
— Turns on all faceplate LEDs and display pixels for a short duration.
PERFORM LAMPTEST
— This command causes the relay to scan the backplane for the hardware modules and update the
UPDATE ORDER CODE
order code to match. If an update occurs, the following message displays.
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER
CODE NOT UPDATED message displays.
— Restarts the relay so that changes to configuration settings can take effect. In most cases, if changes are
REBOOT RELAY
made to the configuration settings these changes do not take effect unless the relay is rebooted.
With the CyberSentry option, the Administrator or Operator role can initiate the Reboot Relay command.
NOTE
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
key. After clearing data, the command setting automatically reverts to
ENTER
SET DATE AND TIME:
2000/01/14 13:47:03
PERFORM LAMPTEST?
No
UPDATE ORDER CODE?
No
REBOOT RELAY?
No
SERVICE COMMAND:
0
SAVE VOLATILE DATA?:
No
UPDATING...
PLEASE WAIT
Range: YYYY/MM/DD HH:MM:SS
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: 0, 101
Range: No, Yes
key. The command setting then automatically
ENTER
COMMANDS MENU
key.
ENTER
7-3