Flexlogic; Flexlogic Operands - GE c60 Instruction Manual

Breaker protection system
Hide thumbs Also See for c60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
— The relay increments the Configuration revision every time the configuration is changed. This setting
MSVCB 1 CONFREV
allows the user to reset the configuration back to 1 or a value from 1 to 4294967295.
— A value from 0 through 7. The default value is 4.
MSVCB 1 PRIORITY
— The value represents the IPv4 Differentiated Services (formerly called TypeOfService) value. The default
MSVCB 1 IP CLASS
value is set for Expedited Forwarding (101110B (46 or 2EH). This value provides priority routing, when supported in the
routers.
— A range of values limited from 0 to 4095.
MSVCB 1 VID
— This setting allows the selection of a specific application ID for each sending device.
MSVCB 1 APPID
— This is the destination multicast IP address that is entered in Standard IPV4 address format. The valid
MSVCB 1 DEST. IP
range for IPv4 is from 224.0.0.0 to 239.255.255.255. The UR does not test the address entered.
— This setting selects the level of security and authentication used, as outlined in the following table, and
MSVCB 1 SECURITY
is in the form of an enumeration as per standard. The range is 0 to 2.
Shaded settings in the table are not supported in firmware 7.0.
NOTE
Table 5-20: Security
Enumeration
Authentication
0
No
1
Yes
2
Yes

5.6 FlexLogic

5.6.1 FlexLogic operands

For flexibility, the arrangement of internal digital logic combines fixed and user-programmed parameters. Logic upon
which individual features are designed is fixed, and all other logic, from contact input signals through elements or
combinations of elements to contact outputs, is variable. The user has complete control of all variable logic through
FlexLogic. In general, the system receives analog and digital inputs that it uses to produce analog and digital outputs. The
figure shows major subsystems of a generic UR-series relay involved in this process.
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
Encryption
No
No
Yes
FLEXLOGIC
5
5-155

Advertisement

Table of Contents
loading

Table of Contents