Settings Templates - GE c60 Instruction Manual

Breaker protection system
Hide thumbs Also See for c60:
Table of Contents

Advertisement

CHAPTER 4: INTERFACES
4.
Site list / online window area
5.
Settings list / offline window area
6.
Software windows, with common tool bar
7.
Settings file data view windows, with common tool bar
8.
Workspace area with data view tabs
9.
Status bar
10. Quick action hot links
2
1
3
10
4
5

4.1.6 Settings templates

Settings file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An
example is a substation that has 10 similar feeders protected by 10 UR-series F60 relays.
In these situations, typically 90% or greater of the settings are identical among devices. The templates feature allows
engineers to configure and test these common settings, then lock them so that they are not available to users. For
example, these locked down settings can be hidden from view for field engineers, allowing them to quickly identify and
concentrate on specific settings.
The remaining settings (typically 10% or less) can be specified as editable and be made available to field engineers
installing the devices. These are settings such as protection element pickup values and CT and VT ratios.
The settings template mode allows the user to define which settings are visible in the EnerVista software. Settings
templates can be applied to both settings files (settings file templates) and online devices (online settings templates). The
functionality is identical for both purposes.
Settings files conversion from previous firmware versions is supported.
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 4-1: EnerVista UR Setup software window
6
9
8
ENERVISTA SOFTWARE INTERFACE
7
4
842786A2.CDR