Pmu Aggregator; Transducer Inputs/Outputs; Records; Fault Reports - GE c60 Instruction Manual

Breaker protection system
Hide thumbs Also See for c60:
Table of Contents

Advertisement

RECORDS

These actual values display without the corresponding time stamp as they become available per the recording rate
setting. Also, the recording post-filtering setting is applied to these values.

6.3.9 PMU aggregator

ACTUAL VALUES  METERING  PHASOR MEASURMENT UNIT  PMU AGGREGATOR 1(2)
 PMU AGGREGATOR 1
Actual values for the IEC 61850-90-5 PDU size are provided. These values allow you to know the approximate Ethernet
frame size for the data streams from each aggregator. This can help to estimate network loading. The PDU size shown in
the displays does not include the Ethernet, UDP, or IP layers. PDU sizes approaching approximately 1500 bytes result in
fragmented data frames, causing increased network traffic.

6.3.10 Transducer inputs/outputs

ACTUAL VALUES  METERING  TRANSDUCER I/O DCMA INPUTS  DCMA INPUT xx
 DCMA INPUT xx
Actual values for each DCmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
ACTUAL VALUES  METERING  TRANSDUCER I/O RTD INPUTS  RTD INPUT xx
 RTD INPUT xx
Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value.
6
6.4 Records

6.4.1 Fault reports

ACTUAL VALUES  RECORDS  FAULT REPORTS  FAULT REPORT 1(15)
NO FAULTS TO REPORT
or
 FAULT REPORT 1
6-22
PMU AGGREGATOR 1
PDU SIZE: 0
DCMA INPUT xx
0.000 mA
RTD INPUT xx
-50 °C
FAULT 1
LINE ID: SRC 1
FAULT 1
DATE:
2000/08/11
FAULT 1
TIME:
00:00:00.000000
FAULT 1
TYPE:
ABG
FAULT 1
LOCATION
00.0 km
FAULT 1
RECLOSE
SHOT: 0
CHAPTER 6: ACTUAL VALUES
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: YYYY/MM/DD
Range: HH:MM:SS.ssssss
Range: not available if the source VTs are in the
"Delta" configuration
Range: not available if the source VTs are in the
"Delta" configuration
Range: where applicable
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL

Advertisement

Table of Contents
loading

Table of Contents