GE c60 Instruction Manual page 170

Breaker protection system
Hide thumbs Also See for c60:
Table of Contents

Advertisement

PRODUCT SETUP
section). The UR Setup software imports all of these settings into the current session, not just those in the IEC 61850
window. To avoid loss of any unsaved setting changes made in other panels during the current session, all other panels for
the C60 must be closed before the IEC 61850 panel can be opened; the software prompts for this when applicable. Panels
for other devices can be open concurrently to facilitate parameter coordination.
The Restore button restores all settings in the IEC 61850 window to their last saved values. The Default button causes all
settings in the IEC 61850 window to revert to factory default values. Both buttons affect the current panel being displayed.
Neither button affects settings in other than the IEC 61860 window.
Create CID and settings files
When the Save button in the online IEC 61850 window is clicked, UR Setup software prepares a configured IED description
(CID) file containing all the device's settings and sends the CID file to the connected C60. On receipt of a CID file, the C60
checks it for correctness, and if no error is found, reboots using the settings in the CID file. UR Setup displays a message
when the C60 is running the new settings, confirming successful transfer. This process can take a minute or so due to the
extensive amount of processing required by the software and the C60.
Certain settings not related to IEC 61850 are indicated in this manual as taking effect only when the device is restarted.
The reboot following CID file transfer described in the previous paragraph does not make these setting changes take
effect, as the C60 does not accept the setting change until after the CID file transfer reboot. For any change in the
indicated settings to take effect, after the automatic restart due to CID file transfer, you must perform a manual restart, for
example by executing the Maintenance > Reboot Relay Command in the software.
When the Save button in the offline IEC 61850 window is clicked, UR Setup software saves to local storage, for example the
hard drive, a .urs file containing all of the device's settings.
Server configuration
5
The Server Configuration panel contains IEC 61850 settings relevant to the server functions of the IED implementation.
The path is Settings > Product Setup > Communications > IEC 61850 > Server Configuration.
The following settings are available, where <iedName> is a syntactic variable representing the present value of the IED
NAME setting.
IED NAME
Range: 1 to 64 VisibleString characters
Default: TEMPLATE
The value entered sets the IED name used by IEC 61850 for the C60. An IED name unique within the network must be
entered for proper operation. Valid characters are upper and lowercase letters, digits, and the underscore (_) character.
The first character must be a letter.
Master functional ldName
Range: 0 to 64 VisibileString characters
Default:
The Master logical device contains the UR logical nodes modelling communications and setting group control. Valid
characters are upper and lowercase letters, digits, and the underscore (_) character. If the number of characters entered
is greater than zero, this setting sets the name used in communications for the Master logical device. If an ldName is
entered, a name unique within the network must be entered for proper operation. The standard recommends choosing
this name according to IEC 81346-1. If the number of characters entered is zero, the name used in communications for
the Master logical device is "<iedName>Master", where <iedName> is the value of setting IED NAME described earlier.
Throughout the remainder of this section, <LDName> is a syntactic variable representing the present name of
the master logical device. Depending on its context, <LDName> can be a product-related name or a function-
NOTE
related name. In SCL files, <LDName> is always the product-related name. In IEC 61850 messages, <LDName>
is the function-related name if one is set by the Master functional ldName setting, otherwise <LDName> is
again the product-related name. The product-related name of the Master logical device is
"<iedName>Master". The function related name of the Master logical device is the value of the Master
functional ldName setting.
5-44
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS