NOTE: It is possible to recharge the batteries while performing insulation
measurements provided that the values measured are higher than 20MΩ.
In this case, the recharging time is higher than 6 hours and depends on
the frequency of the measurements.

3.5 Environmental Specifications

Operating Range:
14° to 104°F (-10° to 40°C) during recharging of batteries
14° to 131°F (-10° to 55°C) during measurement
10 to 80% RH
Storage: -40° to 158°F (-40° to 70°C); 10 to 90% RH
Altitude: <2000m

3.6 Mechanical Specifications

Case Dimensions (LxWxH):
10.63 x 9.84 x 7.09" (270 x 250 x 180mm)
Weight: 9.5 lbs (4.3kg) approx

3.7 Safety Specifications

Electrical safety according to EN 61010-1 (Ed. 2 for 2001),
EN 61557 (ed. 97)
Double insulation:
1000V CAT III
2500V CAT I
Pollution Degree 2
Electromagnetic Compatibility:
NF EN 61326-1 (Ed. 97) + A1, industrial environment category
Mechanical Protection:
IP 53 per NF EN 60529 (Ed. 92)
IK 04 per NF EN 50102 (Ed. 95)