3.1 Reference Conditions
Temperature
Relative Humidity
Supply Voltage
Frequency Range
Capacitance in parallel with the input
resistance
Electric Field
Magnetic Field
3.2 Voltage
Measurement Range
Frequency Range*
Resolution
Accuracy
Input Impedance
*Over 500Hz, the small display indicates "- - - -" and the main display gives only an assess-
ment of the peak value of the measured voltage.
Measurement Category: 1000V CAT III or 2500V CAT I (transients ≤2.5kV)
3.3 Insulation Resistance
Method: Voltage-current method according to EN 61557-2 (ed. 02/97)
Nominal Output Voltage: 500, 1000, 2500, 5000 V
Adjustments Available in Variable Mode: 10V from 40V to 1000V
Open-circuit Voltage: ≤1.1 x Vn ±2V (Vn ±2% in variable mode)
Max. Overload of Voltage Vn: (1.05 + dISt) Vn + 50V
NOTE: Vn = Test Voltage
Megohmmeter Model 5070
CHAPTER 3
SPECIFICATIONS
Influence Quantity
1.0 to 99.9V
DC and 15Hz to 500Hz
0.1V
1% of Reading ± 5cts
750kΩ at 3MΩ depending on measure voltage
with dlSt = 3%, 10% or 20%
Reference Values
23°C ±3°K
45 to 55%
9 to 12V
DC and 15.3 to 65Hz
0µF
nil
<40A/m
100 to 999V
1000 to 2500V
1V
1% of Reading ± 3ct
(or selectable from 40V to 5100V)
DC
100V from 1000V to 5100V
2502 to 4000V
DC Only
2V
2V
11