14.9

ESP curve

14.9.1

ESP curve: Indoor unit

Note: A flow error will occur when the minimum water flow rate is not
reached.
EHVZ04S18CB
A
70
60
50
40
30
20
10
0
0
5
10
EHVZ08S18CB
A
70
60
50
40
30
20
10
0
0
5
10
15
A
External static pressure (kPa)
B
Water flow rate (l/min)
C
Operation range
Additional/direct zone
Main/mixed zone
Operation area is extended to lower flow rates only in case the unit
operates with heat pump only. (Not in startup, no backup heater
operation, no defrost operation).
ESP=External static pressure [kPa] in the space heating circuit.
Flow=Water flow through the unit in the space heating circuit.
Notes:
▪ Selecting a flow outside the area of operation can cause damage
or malfunction of the unit. See also the minimum and maximum
allowed water flow range in the technical specifications.
▪ Water quality MUST be according to EN directive EC98/83EC.
ERLQ004~008CA + EHVZ04+08S18CB
Daikin Altherma – Low temperature split
4P401676-1 – 2015.02
C
15
20
25
30
4D097420-1
C
20
25
30
35
4D097420-1
B
B
14 Technical data
Installer reference guide
95