8 Configuration
#
Code
N/A
[9‑0E]
Pump speed limitation main zone
▪ 0: No limitation.
▪ 1~4: General limitation. There is
limitation
required delta T control and comfort
are NOT guaranteed.
▪ 5~8 (default: 6): Limitation when no
actuators. When there is no heating
output, the pump speed limitation is
applicable. When there is heating
output, the pump speed is only
determined by delta T in relation to the
required capacity. With this limitation
range, delta T is possible and the
comfort is guaranteed.
N/A
[9‑0D]
Pump speed limitation additional zone
▪ 0: No limitation.
▪ 1~4: General limitation. There is
limitation
required delta T control and comfort
are NOT guaranteed.
▪ 5~8 (default: 6): Limitation when no
actuators. When there is no heating
output, the pump speed limitation is
applicable. When there is heating
output, the pump speed is only
determined by delta T in relation to the
required capacity. With this limitation
range, delta T is possible and the
comfort is guaranteed.
Installer reference guide
56
Description
in
all
conditions.
The
in
all
conditions.
The
ERLQ004~008CA + EHVZ04+08S18CB
Daikin Altherma – Low temperature split
4P401676-1 – 2015.02