Connecting the water piping............38 7.8.1 About connecting the water piping....... 38 6 Preparation 7.8.2 Precautions when connecting the water piping.... 38 Overview: Preparation............... 23 Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 3
To perform a test run ..........75 9.4.4 To perform an actuator test run ........76 9.4.5 Underfloor heating screed dryout........ 76 10 Hand-over to the user 11 Maintenance and service ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
(on top of the waves. Electromagnetic waves may disturb the control system, instructions described in the Daikin documentation). and cause malfunction of the equipment. ▪ In places where there is a risk of fire due to the leakage of...
▪ Charge the liquid refrigerant as follows: Then A siphon tube is present Charge with the cylinder upright. (i.e., the cylinder is marked with "Liquid filling siphon attached") ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Latest revisions of the supplied documentation may be available on to a utility pipe, surge absorber, or telephone earth. the regional Daikin website or via your dealer. Incomplete earth may cause electrical shock. The original documentation is written in English. All other languages ▪...
Outdoor unit 3.3.1 To unpack the indoor unit 3.2.1 To unpack the outdoor unit 3.2.2 To handle the outdoor unit Carry the unit slowly as shown: ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models. 3 Remove the accessories. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Demand PCB (KRP58M51) (only for ERLQ) ▪ EKRUCBL7 contains following languages: English, German, ▪ Limits the maximum current. However, this also decreases the Russian, Danish. heating/cooling capacity of the system. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
— 4.3.4 Possible combinations of indoor unit and domestic hot water tank Indoor unit Domestic hot water tank EKHWS EKHWSU EKHWE EKHWET EHBH16CB3V EHBX16CB3V EHBH16CB9W Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
▪ #: [A.2.1.7] questions first: temperature of the user interface. ▪ Code: [C-07] ▪ How many rooms are heated (or cooled) by the Daikin heat pump Number of water temperature 0 (1 LWT zone): Main system? zones: ▪...
Page 12
Combination: Under floor heating + Heat pump convectors Benefits ▪ Wireless. The Daikin external room thermostat is available in a ▪ Space heating is provided by: wireless version. ▪ The under floor heating ▪ Efficiency. Although the external room thermostat only sends ON/ ▪...
Bypass valve ▪ For each room, a shut-off valve (field supplied) is installed to avoid leaving water supply when there is no heating or cooling demand. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 14
INFORMATION convectors must be set to match the indoor unit. To increase comfort and performance, Daikin recommends INFORMATION to install the valve kit option EKVKHPC on each heat pump To increase comfort and performance, Daikin recommends convector.
Room 1 Room 2 water temperature for heating Main leaving water temperature zone and/or cooling. Room 3 Remote controller of the heat pump convectors User interface ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Under floor heating NOTICE ▪ Make sure the auxiliary boiler and its integration in the system complies with applicable legislation. ▪ Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler system. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma –...
▪ If energy prices are the same during the day and the night, Daikin recommends to heat up the DHW tank during the day. ▪ If energy prices are lower during the night, Daikin recommends to heat up the DHW tank during the night.
▪ for separate DHW tank, see installation manual of DHW tank. ▪ The power consumption of the booster heater (if applicable) in Configuration the domestic hot water tank ▪ For more information, see "8 Configuration" on page 48. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
"5.5.4 Preferential kWh rate power supply" on page 20 an example with two power meters. 5.5.4 Preferential kWh rate power supply General rule ▪ Power meter 1: Measures the outdoor unit. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
▪ Allows you to limit the power consumption of the entire system (sum of outdoor unit, indoor unit, backup heater and optional The power or current of the entire Daikin system is limited booster heater). dynamically by digital inputs (maximum four steps). Each power limitation level is set via the user interface by limiting one of the ▪...
The system limits power consumption in the following order: for example, door opening/closing Limits certain electrical heaters. ▪ If this is NOT possible, Daikin recommends to connect a remote indoor sensor (option KRCS01-1). ▪ Setup: For installation instructions, see the installation manual of the remote indoor sensor.
▪ That is NOT exposed to direct sunlight conditions, the measured value might be higher than the sound ▪ If this is NOT possible, Daikin recommends to connect a remote pressure level mentioned in Sound spectrum in the data book due outdoor sensor (option EKRSCA1).
▪ Use polyethylene foam as insulation material: ▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and 0.045 kcal/mh°C) ▪ with a heat resistance of at least 120°C Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
20 litre, the internal water volume of the indoor unit NOT included. INFORMATION In critical processes, or in rooms with a high heat load, extra water might be required. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
The backup heater should have a dedicated power supply. Schräder valve WARNING 6.4.5 To check the water volume: Examples ALWAYS use multicore cable for power supply cables. Example 1 ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Normal kWh rate power supply (to power the indoor unit Outdoor ambient PCB in the event of power supply interruption of the temperature sensor preferential kWh rate power supply) Indoor ambient temperature sensor Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Finishing the indoor installation. INFORMATION Depending on the units and/or the installation conditions, it might be necessary to connect electrical wiring before you can charge refrigerant. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
▪ Avoid drain water flowing over the footpath, so that it does not become slippery in case of ambient freezing temperatures. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
In case the unit is installed in places where strong wind can tilt the unit, take following measure: Connect cables (field supply) as shown. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Tighten 3 or 4 turns by hand, before 0~0.5 mm 1.0~1.5 mm 1.5~2.0 mm tightening firmly. 5 Check that the flaring is properly made. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
For the tightening torque, refer to the table in chapter leak. "To handle the stem cap" on page 34. ▪ Check for refrigerant leaks after tightening the service port cap. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Make sure to open the stop valves after installing the refrigerant piping and performing vacuum drying. Running the system with the stop valves closed may break the compressor. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
"PS High" on the unit name plate). Before checking the refrigerant piping Make sure the refrigerant piping is connected between the outdoor unit and the indoor unit. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
0.1 kg) Completely recharging refrigerant Example: INFORMATION ▪ When relocating the system. Piping length is the one way length of liquid piping. ▪ After a leak. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
4 In case of connection with the optional domestic hot water tank, see the installation manual of the domestic hot water tank. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
1 bar to avoid air entering the circuit. necessary, that the equipment is connected only to a supply with a system impedance Z less than or equal to Z ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Interconnection cable Minimum cable section of 2.5 mm² ▪ Use the following methods for installing wires: and applicable for 230 V Recommended field fuse 32 A 40 A 20 A Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Routing through Choose one of the 3 possibilities: the frame a Power supply, earth wiring, and bottom plate heater wire (if applicable) b Interconnection cable ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
When installing field supply or option cables, foresee sufficient cable length. This will make it possible to remove/ reposition the switch box and gain acces to other components during service. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
▪ if no power consumption of the indoor unit is allowed at the preferential kWh rate power supply when active. In case of preferential kWh rate power supply ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
2 If required, modify the connections on terminals X6M and X7M. terminals. Backup heater Connections to Connections to type backup heater power terminals supply 3 kW 1~ 230 V — (*3V) Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
▪ If you use 2 user interfaces, you can install 1 user interface at the indoor unit (for control close to the indoor unit) + 1 user interface in the room (used as room thermostat). ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
X5M/7 and X5M/9; the negative polarity to X5M/8 and X5M/10. 1 Connect the electrical meters cable to the appropriate terminals as shown in the illustration below. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
2 Plug the user interface cover into the hinges. Installation of EKRP1AHTA is required. 2 Fix the cable with cable ties to the cable tie mountings. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
To connect the PC cable to the switch box 1 Go to [A.8]: > Installer settings > Overview settings. Prerequisite: The EKPCCAB kit is required. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
1 When power is turned on for the first time, both user interfaces "8.1.3 To copy the system settings from the first to the second display: user interface" on page 49. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
When the installer settings are changed, the system will request to confirm. When confirmation is complete, the screen will shortly turn OFF and "busy" will be displayed for several seconds. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 51
▪ a: Space heating/cooling control ▪ a: Main LWT zone (user interface) continued >> ▪ b: OFF ▪ c: On ▪ d: Pump operation continued >> ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Cold water ▪ EHBH/X: an optional domestic hot water tank is available, ▪ EHVH/X: a domestic hot water tank is standard incorporated into the indoor unit. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 53
Set this value if thermal unit (X2M/1a). solar panels installed. ▪ 2 (H/C request)(default): See Contact "5 Application guidelines" on page 11. type main. Connected on the indoor unit (X2M/1a and 2a). ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
5°C. ▪ 5: Installed (1000 pulse/kWh) See the user reference guide and/or operation manual for more details about this function. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 55
Set weather-dependent heating: [1-01] [1-02] [1-02] [1-03] [1-03] [1-00] [1-01] ▪ T : Target leaving water temperature (main) ▪ T : Outdoor temperature continued >> ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 56
▪ according schedule. scheduled actions are On or OFF. Remark: This value can only be set in leaving water temperature control. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Domestic hot water Type=Reheat only) in case of a ▪ less On/OFF cycles (lower noise level, higher comfort and higher domestic hot water tank without an internal booster heater. efficiency) ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Select preset leaving water temperatures in accordance with the design and selected heat emitters to ensure the balance between desired room and leaving water temperatures. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 60
Enable this setting to avoid cold leaving water through the heat emitter and the forming of condensation (e.g. under floor heating loops or radiators). Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
1 place Changeover from heating to cooling will occur when the room (see also operation manual and/or user reference guide). ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 62
In reheat mode, desired tank temperature weather dependent. Note: When displayed tank temperature is weather dependent, it cannot be adjusted on the user interface. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 63
Range: 5~95 minutes (default: 30) heater is turned OFF. The domestic hot water tank temperature will increase with [7-00] above selected temperature set point. Range: 0°C~4°C (default: 0°C) ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 64
Hot water request for heat pump (1=request, 0=no request) Time ▪ 1: Yes [8-03]: Booster heater delay timer [A.4.4.3] [2‑02] Start time: 00~23:00, step: 1:00. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
In this way it is possible to limit the backup heater capacity. [5-00] Is backup heater operation allowed above equilibrium temperature during space heating operation? ▪ 1: NOT allowed ▪ 0: Allowed ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 66
50°C, Daikin recommends NOT to disable the backup heater ▪ [C‑04] Bivalent hysteresis: defines the temperature difference second step because it will have a big impact on the between bivalent ON temperature and bivalent OFF temperature.
Page 67
Make sure to observe all rules mentioned in application [F-02] Bottom plate heater ON temperature: guideline 5 when bivalent operation function is enabled. 3°C~10°C (default: 3°C) Daikin shall NOT be held liable for any damage resulting [F-03] Hysteresis: 2°C~5°C (default: 5°C) from failure to observe this rule. INFORMATION...
▪ 1 (default): Yes ▪ 1: Always space heating/cooling has priority. For systems with an integrated domestic hot water tank (only for EHVH/X) Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 69
Defines whether the outdoor unit power supply can be interrupted (internally by indoor unit control) during stand-still conditions (no space heating/cooling nor domestic hot water demand). The final ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 70
Priority: Only applicable in case of an optional EKHW. [A.6.4] [1-0A] Outdoor average timer: ▪ 0: No averaging (default) ▪ 1: 12 hours ▪ 2: 24 hours ▪ 3: 48 hours ▪ 4: 72 hours Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 71
This functionality is only valid in specific conditions where it is preferable to keep the pump active when <4°C (pump will be activated for 10 minutes and deactivated after 10 minutes). Daikin shall NOT be held liable for any damage resulting this functionality. Code Description [F‑09]...
Tank temperature Quiet level [7.7] Set weather dependent Main [7.7.1] Main Additional Set weather-dependent heating Set weather-dependent cooling [7.7.2] Additional Set weather-dependent heating Set weather-dependent cooling Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Amp. limits for DI UFH screed dryout kW limits for DI Air purge Priority Actuator test run INFORMATION Depending on the selected installer settings, settings will be visible/invisible. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
▪ Between the gas boiler and the local supply panel (only applicable in case of hybrid system) There are NO missing phases or reversed phases. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
4 Select OK and press Result: The test run starts. It stops automatically when done (±30 min). To stop it manually, press , select OK and press ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
This function is used for drying out the screed of an underfloor heating system very slowly during the construction of a house. It allows the installer to program and execute this program. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
81. To reset the U3 error, your User page 30. permission level needs to be Installer. 1 Go to the underfloor heating screed dryout screen. 2 Press 3 Press to interrupt the program. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
To make sure this water originates from the tank, check after a tank heat up cycle. It is recommended to do this maintenance more frequently. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Symptom: The pressure relief valve opens unit decides to use a low water flow. Possible causes Corrective action The expansion vessel is broken Replace the expansion vessel. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
▪ The air purge operation Press the reset button in the switch box. See "14.4 Components" on page 92 for the location of the reset button. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Disposing of the system typically consists of the following stages: Pumping down the system. Dismantling the system according to the applicable legislation. Treating the refrigerant, oil and other parts according to the applicable legislation. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction side through the bottom of the unit. Maximum two units can be installed. Not allowed ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 88
Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle D Height of the unit Height of obstacles B and D Recommended to prevent exposure to wind and snow. Not allowed Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Pump User interface Safety valve pressure Air purge Expansion vessel Pressure gauge Heat exchanger (refrigerant/water) Stop valve with drain/fill valve (1‑1/4" F BSP) (included accessory) Water filter ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 90
14 Technical data Wire entrance of the power supply/communication wire Service door Switch box terminals Switch box terminals for the domestic hot water tank (option) 3D088485 Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Allows isolation of the indoor unit water circuit side from the residential water circuit side. Water outlet connection Thermistors Determines the water and refrigerant temperature at various points in the circuit. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 99
Wiring dependent on model orange) Colours: K1M, K2M Magnetic contactor Black K1R (A1P) Magnetic relay (Y1S) Blue K1R (A2P) Magnetic relay Brown K2R (A1P) Magnetic relay (Y3S) ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 101
Wiring dependent on model Magnetic relay (Y3S) Colours: Magnetic relay (E1H) Black Magnetic relay (E1HC) Blue K10R Magnetic relay (upload) Brown K11R Magnetic relay (main) ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 103
Wiring dependent on model orange) Colours: K1M, K2M Magnetic contactor (main, upload) Black K1R (A1P) Magnetic relay (Y1S) Blue K1R (A2P) Magnetic relay (upload) Brown ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
2 core STANDARD PART 2x0.75 X5M: 1-2 A2P: P1-P2 user interface communication OPTIONAL PART Only for *KRUCBL* 2 core 2x0.75 communication A2P: P1-P2 user interface 4D090420 ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 110
Regular kWh rate power supply Electrical 3~ balanced meter type 3~ unbalanced Benefit kWh rate power supply Electrical 3~ balanced meter type 3~ unbalanced 4D078288-B Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Heating only type Reversible type Indoor units EHBH11+16/EHVH11+16 EHBX11+16/EHVX11+16 Outdoor units ERHQ011BAV3 ERHQ014BAV3 ERHQ016BAV3 ERHQ011BAV3 ERHQ014BAV3 ERHQ016BAV3 Power supply Name Phase Frequency 50 Hz Voltage 230 V ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 114
European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16 A and ≤75 A per phase. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Tube type Hi-XSS(8) Type WF fin Treatment Anti-corrosion treatment (PE) Type Propeller Quantity Air flow rate (nominal at 230 V) — Discharge direction Horizontal ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 116
Refrigerant oil Type Daphne FVC68D Charged volume 1.0 l Piping connections Liquid Quantity Type Flare connection Diameter (OD) Ø9.52 mm Quantity Type Flare connection Diameter (OD) Ø15.9 mm Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
For power supply See "Connecting electrical wiring" For connection with indoor Power supply intake Outdoor unit only Ambient temperature DB/WB 7°C/6°C – leaving water condenser 35°C (ΔT=5°C). ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Specifications Length 857 mm Nr. of rows Fin pitch 1.4 mm Nr. of passes Face area 1.131 m² Nr. of stages Empty tube plate hole Tube type Hi-XSS(8) Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 119
45 dBA 46 dBA Cooling pressure Refrigerant Type R410A Charge 3.4 kg Control Expansion valve (electronic type) Nr. of circuits Refrigerant oil Type Daphne FVC68D Charged volume 1.5 l ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Current Nominal running current — Starting current — Maximum running current 34.2 A (cooling and heating) 0.22 Ω Minimum S value 525 kVA Recommended fuses 40 A Wiring connections Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 121
S greater than or equal to the minimum S value. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Specifications Length 857 mm Nr. of rows Fin pitch 1.4 mm Nr. of passes Face area 1.131 m² Nr. of stages Empty tube plate hole Tube type Hi-XSS(8) Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 123
45 dBA 46 dBA Cooling pressure Refrigerant Type R410A Charge 3.4 kg Control Expansion valve (electronic type) Nr. of circuits Refrigerant oil Type Daphne FVC68D Charged volume 1.5 l ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
— Starting current — Maximum running current 16.3 A (cooling and heating) — Minimum S value Equipment complying with EN/IEC 61000‑3‑12 Recommended fuses 20 A Wiring connections Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 125
European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16 A and ≤75 A per phase. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Refrigerant circuit Gas side Ø15.9 mm Liquid side Ø9.5 mm Sound power level Nominal 41 dBA 44 dBA 41 dBA 44 dBA Sound pressure level Nominal 27 dBA 30 dBA 27 dBA 30 dBA Operation range Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 127
Type of wires Voltage 230 V/maximum current: 100 mA/minimum 0.75 mm For connection Quantity of with user interface wires Type of wires 0.75 mm ~1.25 mm (maximum length 500 m) ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 128
1 min 6 min* 1 min 0 sec 10 min 1 min 10 min Capacity Capacity Stage 1 Stage 1 Time Stage 2 (1) The equipment complies with EN/IEC 61000-3-12. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Page 129
3 minutes in case of domestic hot water operation. Figure 3: Booster heater (EKHW), minimum time delay between stages 1 min 50 min* Capacity Stage 1 Time Unless manually activated. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
In such conditions, the ERHQ models may experience problems with severe ice buildup on the air-cooled coil. If such conditions are expected, the ERLQ must be installed instead. These models contain countermeasures (insulation, heater sheet,…) to prevent freeze-up. Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
–20 domestic hot water domestic hot water –25 –25 tank temperature (°C) tank temperature (°C) 40 45 55 60 40 45 INDOOR UNITS: CA-SERIES 3TW60813-2B ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Dry bulb temperature [°C] 1. Refer to psychometric chart for more information. 2. If condensation is expected, installation of EKHBDPCA2 - drainpan kit must be considered. 4D078990 Installer reference guide ERHQ+ERLQ011~016 + EHBH/X11+16CB Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
See also the minimum and maximum allowed water flow range in the technical specifications. ▪ Water quality MUST be according to EN directive EC98/83EC. ERHQ+ERLQ011~016 + EHBH/X11+16CB Installer reference guide Daikin Altherma – Low temperature split 4P384974-1 – 2015.01...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment not made by Daikin that can be combined with product according instructions accompanying documentation.
Page 136
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value User settings └─ Preset values └─ Room temperature 7.4.1.1 Comfort (heating) [3-07]~[3-06], step: A.3.2.4 21°C 7.4.1.2 Eco (heating) [3-07]~[3-06], step: A.3.2.4 19°C 7.4.1.3 Comfort (cooling)
Page 137
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value A.2.1.5 [5-0D] BUH type 0: 1P,(1/2) 1: 1P,(1/1+2) 2: 3P,(1/2) 3: 3P,(1/1+2) (*3) 4: 3PN,(1/2) 5: 3PN,(1/1+2) (*4) A.2.1.6 [D-01] Preferential kWh rate 0: No...
Page 138
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value A.3.1.2.2.2 [9-06] Temperature range Maximum temp (heating) 37~depending on outdoor unit, step: 1°C 55°C A.3.1.2.2.3 [9-07] Temperature range Minimum temp (cooling) 5~18°C, step: 1°C 5°C A.3.1.2.2.4...
Page 139
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value A.6.3.2 [4-09] Type 0: Current 1: Power A.6.3.3 [5-05] Amp. value 0~50 A, step: 1 A 50 A A.6.3.4 [5-09] kW value 0~20 kW, step: 0,5 kW...
Page 140
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [2-01] Should the disinfection function be executed? 0: No 1: Yes [2-02] When should the disinfection function start? 0~23 hour, step: 1 hour [2-03] What is the disinfection target temperature? [E-07]≠...
Page 141
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [6-02] What is the capacity of the booster heater? 0~10kW, step: 0,2kW [6-03] What is the capacity of the backup heater step 1? 0~10kW, step: 0,2kW [6-04] What is the capacity of the backup heater step 2?
Page 142
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [A-02] 0 (*5) 1 (*6) [A-03] [A-04] [B-00] [B-01] [B-02] [B-03] [B-04] [C-00] Domestic heating water priority. 0: Solar priority 1: Heat pump priority [C-01] [C-02]...
Page 143
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [E-0B] Is a bi-zone kit installed? 0 (#) [E-0C] [F-00] Pump operation allowed outside range. 0: Disabled 1: Enabled [F-01] Above which outdoor temperature is cooling allowed? 10~35°C, step: 1°C...