Daikin Altherma ERLQ004CAV3 Installer's Reference Manual

Hide thumbs Also See for Altherma ERLQ004CAV3:
Table of Contents

Advertisement

Installer reference guide
Daikin Altherma low temperature split
+
ERLQ004-006-008CA
EHVH04S18CA3VF
Installer reference guide
English
EHVH08S18CA3VF
Daikin Altherma low temperature split

Advertisement

Table of Contents
loading

Summary of Contents for Daikin Altherma ERLQ004CAV3

  • Page 1 Installer reference guide Daikin Altherma low temperature split ERLQ004-006-008CA EHVH04S18CA3VF Installer reference guide English EHVH08S18CA3VF Daikin Altherma low temperature split...
  • Page 2: Table Of Contents

    To finish the outdoor unit installation ......41 6.1.3 Installation site requirements of the indoor unit ..21 7.7.2 To close the outdoor unit ..........41 Preparing refrigerant piping ............21 Finishing the indoor unit installation .......... 41 6.2.1 Refrigerant piping requirements........21 7.8.1 To fix the user interface cover to the indoor unit..41 6.2.2 Refrigerant piping insulation ........21 7.8.2 To close the indoor unit..........41 Preparing water piping............... 21 6.3.1 Water circuit requirements .......... 21 Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 3 12.2 Solving problems based on symptoms........66 12.2.1 Symptom: The unit is NOT heating as expected ..66 12.2.2 Symptom: The compressor does NOT start (space heating or domestic water heating)......66 12.2.3 Symptom: The pump is making noise (cavitation) ..67 12.2.4 Symptom: The pressure relief valve opens....67 12.2.5 Symptom: The water pressure relief valve leaks ..67 12.2.6 Symptom: The space is NOT sufficiently heated at low outdoor temperatures ........... 67 12.2.7 Symptom: The pressure at the tapping point is temporarily unusual high..........68 12.2.8 Symptom: Decoration panels are pushed away due to a swollen tank ............68 ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 4: About The Documentation

    Only  use Installer Preparation of the Digital files on http:// accessories,  optional  equipment  and  spare  parts  made  or reference installation, technical www.daikineurope.com/ approved by Daikin. guide specifications, good support­and­manuals/ practices, reference data, product­information/. WARNING … Make  sure  installation,  testing  and  applied  materials Addendum Additional info about how...
  • Page 5: Installation Site

    ▪ Toxic  gas  may  be  produced  if  refrigerant  gas  comes components box is connected securely. into contact with fire. ▪ Make sure all covers are closed before starting up the WARNING unit. Always  recover  the  refrigerants.  Do  NOT  release  them directly  into  the  environment.  Use  a  vacuum  pump  to evacuate the installation. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 6: About The Box

    ▪ At  delivery,  the  unit  must  be  checked  for  damage.  Any  damage 1 Lift the outdoor unit. must be reported immediately to the carrier’s claims agent. CAUTION ▪ Bring  the  packed  unit  as  close  as  possible  to  its  final  installation position to prevent damage during transport. Only handle the outdoor unit as follows: Outdoor unit 3.1.1 To unpack the outdoor unit 57kg 2 Remove the accessories at the bottom of the package. Outdoor unit installation manual Fluorinated greenhouse gases label Multilingual fluorinated greenhouse gases label Unit mounting plate Indoor unit 3.2.1 To unpack the indoor unit Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 7: To Remove The Accessories From The Indoor Unit

    3 Remove the accessories. Code Explanation 1× 1× 1× 1× European split outdoor pair heat pump Low water temperature – ambient zone: −10~ −20°C Refrigerant R410A Capacity class: 1× 2× 1× ▪ 004=4.5 kW ▪ 006=6 kW ▪ 008=7.5 kW Series General safety precautions Addendum book for optional equipment 1~, 230 V, 50 Hz Indoor unit installation manual Operation manual 4.1.2 User interface kit: user interface, 4 fixing screws, 2 plugs Identification label: Indoor unit Shut­off valve User interface cover Location 4 Reinstall the top panel. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 8: Possible Combinations Of Units And Options

    It  is  recommended  to  install  this  option  in  colder  regions  with temperature sensor. possible low ambient temperatures or heavy snowfall. As an option the remote indoor sensor can be installed to measure For  installation  instructions,  see  the  installation  manual  of  the the room temperature on another location. outdoor unit. For installation instructions, see the installation manual of the remote indoor sensor and addendum book for optional equipment. INFORMATION ▪ The remote indoor sensor can only be used in case the user  interface  is  configured  with  room  thermostat functionality. ▪ You can only connect either the remote indoor sensor or the remote outdoor sensor. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 9: Possible Combinations Of Indoor Unit And Outdoor

    PC.  It  gives  the  possibility  to  upload  different language  files  to  the  user  interface  and  indoor  parameters  to  the indoor  unit.  For  the  available  language  files,  contact  your  local dealer. The software and corresponding operating instructions are available on Daikin Extranet. For  installation  instructions,  see  the  installation  manual  of  the  PC cable. 4.2.3 Possible combinations of indoor unit and outdoor unit Indoor unit...
  • Page 10: Application Guidelines

    ▪ Stable  room  temperature  matching  the  desired  temperature system (higher comfort) ▪ Less  ON/OFF  cycles  (more  quiet,  higher  comfort  and  higher The  Daikin  heat  pump  system  supplies  leaving  water  to  heat efficiency) emitters in one or more rooms. ▪ Lowest possible leaving water temperature (higher efficiency) Because  the  system  offers  a  wide  flexibility  to  control  the ▪...
  • Page 11 ▪ #: [A.2.2.4] convector  can  only  send  a ▪ Space heating is provided by: ▪ Code: [C­05] thermo ON/OFF condition. ▪ The under floor heating Benefits ▪ The heat pump convectors ▪ Wireless.  The  Daikin  external  room  thermostat  is  available  in  a Setup wireless version. ▪ Efficiency. Although the external room thermostat only sends ON/ OFF signals, it is specifically designed for the heat pump system. Heat pump convectors Setup Main leaving water temperature zone One single room Remote controller of the heat pump convectors...
  • Page 12: Multiple Rooms - One Lwt Zone

    Setting Value Unit temperature control: 2 (RT control): Unit operation is decided based on the ambient ▪ #: [A.2.1.7] temperature of the user interface. ▪ Code: [C­07] Number of water temperature 0 (1 LWT zone): Main zones: ▪ #: [A.2.1.8] ▪ Code: [7­02] Benefits ▪ Cost effective. Main leaving water temperature zone Room 1 ▪ Easy.  Same  installation  as  for  one  room,  but  with  thermostatic Room 2 valves. Remote controller of the heat pump convectors Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 13: Multiple Rooms - Two Lwt Zones

    ▪ The user interface connected to the indoor unit decides the space convectors must be set to match the indoor unit. operation mode. INFORMATION ▪ The  heating  demand  signals  of  each  heat  pump  convector  are connected in parallel to the digital input on the indoor unit (X2M/1 To increase comfort and performance, Daikin recommends and  X2M/4).  The  indoor  unit  will  only  supply  leaving  water to install the valve kit option EKVKHPC on each heat pump temperature when there is an actual demand. convector. INFORMATION Configuration To increase comfort and performance, Daikin recommends...
  • Page 14: Setting Up An Auxiliary Heat Source For Space Heating

    ▪ Other  rooms  =  external  room thermostat functionality Number of water temperature 1 (2 LWT zones): Main + zones: additional ▪ #: [A.2.1.8] ▪ Code: [7­02] In case of heat pump convectors: 1 (Thermo ON/OFF): When the used external room thermostat or External room thermostat for the heat pump convector can only additional zone: send a thermo ON/OFF ▪ #: [A.2.2.5] condition. ▪ Code: [C­06] Shut­off valve output Set to follow the thermo demand of the main zone. At the mixing valve station Set the desired main leaving water temperature. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 15 Heat exchanger coil 1 2 3 4 FHL1...3 Under floor heating NOTICE ▪ Make sure the auxiliary boiler and its integration in the system complies with applicable legislation. Boiler thermostat input ▪ Daikin  is  NOT  responsible  for  incorrect  or  unsafe Auxiliary contact (normal closed) Heating demand room thermostat (optional) situations in the auxiliary boiler system. Auxiliary relay for activation of indoor unit (field supply) Auxiliary relay for activation of boiler (field supply) ▪ Make  sure  the  return  water  to  the  heat  pump  does  NOT  exceed Indoor Indoor unit...
  • Page 16: Setting Up The Domestic Hot Water Tank

    55°C  (50°C  if  outdoor  temperature  is  low).  The  electrical resistance  integrated  in  the  heat  pump  can  higher  this ▪ To heat up the DHW tank to the desired DHW tank temperature, temperature.  However,  this  consumes  more  energy.  Daikin you can use the following energy sources: recommends  to  set  the  desired  DHW  tank  temperature  below ▪ Thermodynamic cycle of the heat pump 55°C to avoid using the electrical resistance.
  • Page 17: Dhw Pump For Instant Hot Water

    *3V ▪ You can read out the energy data: connected  to  a  single­phase ▪ Per month grid) ▪ Per year INFORMATION The  calculated  produced  heat  and  consumed  energy  are an estimation, the accuracy cannot be guaranteed. 5.5.1 Produced heat ▪ The produced heat is calculated internally based on: ▪ The leaving and entering water temperature ▪ The flow rate ▪ Setup and configuration: No additional equipment needed. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 18: Preferential Kwh Rate Power Supply

    Power  limitation  is  also  useful  in  combination  with  an  energy power consumption. You only need to set the number of pulses management system. of each power meter. The  power  or  current  of  the  entire  Daikin  system  is  limited ▪ See  "5.5.4  Preferential  kWh  rate  power  supply"  on  page  18  for dynamically  by  digital  inputs  (maximum  four  steps).  Each  power an example with two power meters.
  • Page 19: Power Limitation Process

    ▪ That  is  NOT  affected  by  outside  air  or  air  draught  because  of, Actual power input for example, door opening/closing Setup ▪ If  this  is  NOT  possible,  Daikin  recommends  to  connect  a  remote ▪ Demand PCB (option EKRP1AHTA) needed. indoor sensor (option KRCS01­1). ▪ Maximum  four  digital  inputs  are  used  to  activate  the ▪...
  • Page 20: Preparation

    ▪ In heavy snowfall areas it is very important to select an installation site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is possible, make sure that the heat exchanger coil is NOT affected by  the  snow.  If  necessary,  install  a  snow  cover  or  shed  and  a pedestal. Baffle plate Prevailing wind direction Air outlet Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 21: Installation Site Requirements Of The Indoor Unit

    ▪ Use  piping  with  annealed  temper  grade,  in  function  of  the  pipe diameter. ▪ The  minimal  pipe  thickness  should  comply  with  applicable legislation. The minimal pipe thickness for R410A piping must be in accordance with the following table. FHL1 Pipe for… Outer diameter Pipe thickness (Ø) FHL2 FHL3 Ø Liquid 6.4 mm (1/4") ≥0.8 mm Outdoor unit Indoor unit 15.9 mm (5/8") ≥1.0 mm Heat exchanger Backup heater Pump Stop valve Motorised 3­way valve Motorised 2­way valve (field supply) Collector ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 22: Formula To Calculate The Expansion Vessel Pre-Pressure

    ▪ Only use clean pipes In  critical  processes,  or  in  rooms  with  a  high  heat  load, ▪ Hold the pipe end downwards when removing burrs. extra water might be required. ▪ Cover the pipe end when inserting it through a wall, to prevent NOTICE dust and/or particles entering the pipe. When  circulation  in  each  space  heating  loop  is  controlled ▪ Use a decent thread sealant to seal connections. by remote­controlled valves, it is important that a minimum ▪ For safety reasons, it is NOT allowed to add any kind of glycol to water flow of 15 l/min is guaranteed, even if all the valves the water circuit. are closed. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 23: Changing The Pre­pressure Of The Expansion Vessel

    >7 m Do the following: The expansion vessel of the indoor unit is too ▪ Increase  the  pre­ small for the installation. pressure. In this case, it is ▪ Check  if  the  water recommended to install volume  does  an extra vessel outside exceed  the  maximum the unit. allowed water volume. This is the height difference (m) between the highest point of the water circuit and the indoor unit. If the indoor unit is at the highest point of the installation, the installation height is 0 m. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 24: Preparing Electrical Wiring

    58 0 1 5 0 1 5 0 1 5 0 1 5 0 During preferential kWh rate power supply During preferential kWh rate power supply activation, power supply is NOT interrupted. activation, power supply is interrupted The outdoor unit is turned off by the control. immediately or after some time by the electricity company. In this case, the indoor Remark: The electricity company must always unit must be powered by a separate normal allow the power consumption of the indoor power supply. unit. Normal power supply Preferential kWh rate power supply Power supply for outdoor unit Power supply and interconnection cable to indoor unit Power supply for backup heater Preferential kWh rate power supply (voltage free contact) Normal kWh rate power supply (to power the indoor unit PCB in the event of power supply interruption of the preferential kWh rate power supply) 6.4.4 The following illustration shows the required field wiring. Overview of electrical connections for external and internal actuators Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 25: Installation

    User interface Optional equipment Room thermostat 3 or 4 100 mA Outdoor ambient temperature sensor Indoor ambient temperature sensor Heat pump convector 100 mA Field supplied components 100 mA(b) Shut­off valve Electricity meter 2 (per meter) Domestic hot water pump Alarm output Changeover to external heat source control Space cool/heat operation control Power consumption 2 (per input digital inputs signal) Refer to name plate on outdoor unit. Minimum cable section 0.75 mm². Cable section 2.5 mm². Cable section 0.75 mm² till 1.25 mm²; maximum length: 50 m. Voltage­free contact shall ensure the minimum applicable load of 15 V DC, 10 mA. Cable section 0.75 mm² till 1.25 mm²; maximum length: 500 m. Applicable for both single user interface and dual use interface connection. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 26: To Open The Indoor Unit

    If  the  unit  is  installed  directly  on  the  floor,  prepare  4  sets  of  M8  or M10 anchor bolts, nuts and washers (field supply) as follows: INFORMATION The  maximum  height  of  the  upper  protruding  part  of  the bolts is 15 mm. (mm) 7.1.3 To open the switch box cover of the indoor unit In order to guarantee good operation of the unit in areas with risk of snowfall, a minimum of 10 cm needs to be assured below the bottom plate of the unit. It is recommended to construct a pedestal with the same height as the maximum snowfall height. On this pedestal it is then recommended to install the EKFT008CA option kit to guarantee the minimum space of 10 cm below the bottom plate of the unit. (mm) Maximum snowfall height EKFT008CA option kit Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 27: To Prepare Drain Work

    ▪ If  you  install  the  unit  on  a  frame,  install  a  waterproof  plate  within 150  mm  of  the  underside  of  the  unit  in  order  to  prevent  the invasion of water in the unit and to avoid the drain water dripping (see the following illustration). NOTICE If  the  drain  holes  of  the  outdoor  unit  are  blocked  up, provide space of at least 300 mm below the outdoor unit. An additional drain pan kit (EKDP008CA) can be used to gather the drain water. The drain pan kit consists of: (mm) Maximum snowfall height EKFT008CA option kit Drain pan U­beams ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 28: To Install The Outdoor Unit

    3 Adjust  the  height  of  the  leveling  feet  to  compensate  for  floor over irregularities. The maximum allowed deviation is 1°. ≤1° In case the unit is installed  in places where strong wind can tilt the unit, take following measure: 1 Prepare  2  cables  as  indicated  in  the  following  illustration  (field supply). 2 Place the 2 cables over the outdoor unit. 3 Insert  a  rubber  sheet  between  the  cables  and  the  outdoor  unit to prevent the cable from scratching the paint (field supply). 4 Attach the cable’s ends. Tighten those ends. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 29: Connecting The Refrigerant Piping

    Tighten  3  or  4  turns  by  hand,  before R410A (clutch (Ridgid-type) (Imperial-type) tightening firmly. type) 0~0.5 mm 1.0~1.5 mm 1.5~2.0 mm 5 Check that the flaring is properly made. ▪ Always use two wrenches together when loosening a flare nut. ▪ Always  use  a  spanner  and  torque  wrench  together  to  tighten  the flare nut when connecting the piping. This to prevent nut cracking and leaks. Flare’s inner surface must be flawless. The pipe end must be evenly flared in a perfect circle. Make sure the flare nut is lifted. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 30: To Braze The Pipe End

    For  the  tightening  torque,  refer  to  the  table  in  chapter "7.4.6 To handle the stem cap" on page 30. ▪ Check for refrigerant leaks after tightening the service port cap. 7.4.8 To connect the refrigerant piping to the outdoor unit 1 Connect the liquid refrigerant connection from the indoor unit to the liquid stop valve of the outdoor unit. Spanner Torque wrench ▪ When  it  is  expected  that  the  operating  pressure  will  be  low  (e.g. when cooling  will be performed while the outside air temperature is low), sufficiently seal the flare nut in the stop valve on the gas line with silicon sealant to prevent freezing. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 31: To Connect The Refrigerant Piping To The Indoor Unit

    Liquid stop valve absolute). 1 Vacuum the system until the pressure on the manifold indicates NOTICE −0.1 MPa (−1 bar). 2 Leave as is for 4­5 minutes and check the pressure: Use  this  vacuum  pump  for  R410A  exclusively.  Using  the same  pump  for  other  refrigerants  may  damage  the  pump Then… If the pressure… and the unit. Does not change There is no moisture in the system. This procedure is finished. Increases There is moisture in the system. Go to the next step. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 32: To Determine The Additional Refrigerant Amount

    ▪ When  charging  refrigerant,  always  use  protective gloves and safety glasses. CAUTION Do  NOT  charge  the  refrigerant  more  than  the  specified amount, to avoid compressor breakdown. Other guidelines: ▪ Only  use  tools  exclusively  for  R410A  to  ensure  pressure resistance and to prevent foreign materials from entering into the system. ▪ Charge the liquid refrigerant as follows: Then A siphon tube is present Charge with the cylinder upright. (i.e., the cylinder is marked with "Liquid filling siphon attached") Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 33: Connecting The Water Piping

    To  avoid  damage  to  the  surroundings  in  case  of  water leakage,  it  is  recommended  to  close  the  cold  water  inlet stop valves during periods of absence. 2 Screw the indoor unit nuts on the shut­off valves. 3 Connect  the  domestic  hot  water  in  and  out  pipes  to  the  indoor unit. Pressure relief blow­out The blow out should be connected to an appropriate drain according to the applicable legislation. It is recommended to use a tundish. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 34: To Fill The Water Circuit

    If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher than  RH  80%,  the  thickness  of  the  sealing  materials  should  be  at least 20 mm to prevent condensation on the surface of the sealing. 7.5.6 To connect the recirculation piping 1 Loosen and remove the screws at the bottom of the unit. 2 Slide the front panel of the unit downwards and remove it. 3 Loosen and remove the 4 screws that fix the top panel. 4 Remove the top panel from the unit. 10 Re­attach the insulation, expansion vessel and casing. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 35: Connecting The Electrical Wiring

    7.6.2 To connect the electrical wiring on the outdoor unit 1 Remove the 2 switch box cover screws. 2 Remove the switch box cover. Stranded conductor wire Round crimp­style terminal ▪ Use the following methods for installing wires: Wire type Installation method Single core wire AA´ A´ a Curled single core wire 3 Strip insulation (20 mm) from the wires. b Screw c Flat washer Stranded conductor wire with round Strip wire end to this point crimp­style terminal Excessive strip length may cause electrical shock or leakage. 4 Open the wire clamp. a Terminal 5 Connect the interconnection cable and power supply as follows: b Screw c Flat washer ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 36: To Connect The Electrical Wiring On The Indoor Unit

    4 Fix  the  cable  with  cable  ties  to  the  cable  tie  mountings  to ensure strain relief and to make sure that it does NOT come in contact with the piping and sharp edges. Routing Possible cables (depending on unit type and installed options) ▪ User interface Low voltage ▪ Power consumption digital inputs (field supply) ▪ Outdoor ambient temperature sensor (option) ▪ Indoor ambient temperature sensor (option) ▪ Electrical meters (field supply) ▪ Interconnection cable High voltage power supply ▪ Normal kWh rate power supply ▪ Preferential kWh rate power supply ▪ Power supply for backup heater Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 37: To Connect The Main Power Supply

    1 Connect  the  backup  heater  power  supply.  Use  a  single  pole 1 2 3 fuse for F1B. Legend: see illustration below. Backup heater Connections to Connections to type terminals backup heater power supply In case of preferential kWh rate power supply 3 kW 1~ 230 V — X19A (*3V) X6YB 30 31 X6YA Special remark for fuses: 1 2 3 2 Fix the cable with cable ties to the cable tie mountings. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 38: To Connect The User Interface

    K2M/1 ∞ Example measure resistance between K1M/1 and K5M/13: 1 3 5 13 1 3 5 13 2 4 6 14 2 4 6 14 NOTICE Ω Ω Be careful NOT to distort the shape of the backside of the user interface by overtightening the mounting screws. 3 Cut off a 2 wire conductor. 1 3 5 13 4 Connect the wires to the user interface as shown below. 2 4 6 14 Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 39: To Connect The Shut­off Valve

    NOTICE etc. Secure the wiring to the front part of the casing using the The PCB is mounted in the faceplate of the user interface. wiring retainer and clamp. Be careful NOT to damage it. 4 Reinstall the faceplate onto the wallplate. 2 Fix the wallplate of the user interface to the wall. NOTICE 3 Connect the wires to the user interface as shown below Be  careful  NOT  to  pinch  the  wiring  when  attaching  the From the rear frontplate to the unit. 7.6.7 To connect the shut­off valve 1 Connect the valve control cable to the appropriate terminals as shown in the illustration below. NOTICE Wiring is different for a NC (normal closed) valve and a NO (normal open) valve. From the left 2 Fix the cable with cable ties to the cable tie mountings. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 40: To Connect The Electrical Meters

    X1 X2 X3 X4 Installation of EKRP1HB is required. 2 Fix the cable with cable ties to the cable tie mountings. 2 Fix the cable with cable ties to the cable tie mountings. 7.6.10 To connect the alarm output 7.6.13 To connect the power consumption digital 1 Connect the alarm output cable to the appropriate terminals as inputs shown in the illustration below. 1 Connect  the  power  consumption  digital  inputs  cable  to  the appropriate terminals as shown in the illustration below. Installation of EKRP1HB is required. 2 Fix the cable with cable ties to the cable tie mountings. Installation of EKRP1AHTA is required. 2 Fix the cable with cable ties to the cable tie mountings. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 41: Finishing The Outdoor Unit Installation

    Then  in  the  table  explained below, the bread crumb is set as N/A (not applicable). 8.1.1 To connect the PC cable to the switch box Prerequisite: The EKPCCAB kit is required. 1 Connect the cable with USB connection to your PC. 2 Connect the plug of the cable to X10A on A1P of the switch box of the indoor unit. X10A 3 Mount the front panel to the indoor unit. 7.8.2 To close the indoor unit 3 Pay special attention to the position of the plug! 1 Close the switch box cover. 2 Reinstall the top plate. 3 Reinstall the front panel. NOTICE When  closing  the  indoor  unit  cover,  make  sure  that  the tightening torque does NOT exceed 4.1 N•m. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 42: To Access The Most Used Commands

    This  user  interface  is  now  the INFORMATION main user interface. An additional 0­digit is added to the first part of the setting INFORMATION when you access the codes in the overview settings. During the quick wizard, the second user interface displays Example:  [1­01]: "1" will result in "01". Busy and will NOT be possible to operate. 3 The quick wizard will guide you. Overview settings 4 For  proper  operation  of  the  system,  the  local  data  on  the  two user interfaces must be the same. If this is NOT the case, both user interfaces will display: Confirm Adjust Scroll 3 Go to the corresponding second part of the setting by using the  and   button. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 43: To Copy The Language Set From The First To The Second User Interface

    ▪ 1  (Ext  RT  control):  Unit  operation  is decided  by  the  external  thermostat  or Language equivalent (e.g. heat pump convector). Select the desired language ▪ 2  (RT  control):  Unit  operation  is decided  based  on  the  ambient temperature of the user interface. Confirm Adjust ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 44 ▪ 0  (Continuous):  Continuous  pump temperature zone. operation, regardless of thermo ON or OFF  condition.  Remark:  continuous pump  operation  requires  more  energy than  sample  or  request  pump operation. ▪ a:  Space  heating  control  (user ▪ a: Main LWT zone interface) continued >> ▪ b: OFF ▪ c: On ▪ d: Pump operation continued >> Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 45: Quick Wizard: Options

    No  further water temperature control. settings are needed. See also illustrations below. Domestic hot water pump installed for… Disinfection Instant hot water ▪ a:  Space  heating  control  (user interface) ▪ b: OFF ▪ c: On Indoor unit Tank ▪ d:  Heating  demand  (by  ext  RT  or Domestic hot water pump Heater element Non­return valve ▪ e: Pump operation Shower Cold water ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 46 Remark:  For  some functionality,  the  temperature  sensor in the outdoor unit is still used. ▪ 2  (Room  sensor):  Installed.  The temperature  sensor  in  the  user interface  is  NOT  used  anymore. Remark: This value has only meaning in room thermostat control. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 47: Quick Wizard: Capacities (Energy Metering)

    [1­02] by a maximum of 10°C. [1-02] [1­03] See  the  user  reference  guide  and/or  operation  manual  for  more [1-03] details about this function. [1-00] [1-01] ▪ T :  Target  leaving  water  temperature (main) ▪ T : Outdoor temperature continued >> ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 48 :  Target  leaving  water  temperature leaving water temperature is: (main) ▪ NOT weather­dependent (i.e. does ▪ T : Outdoor temperature NOT  depend  on  the  outdoor continued >> ambient temperature) ▪ fixed in time (i.e., NOT scheduled) ▪ Weather  dep.  The  desired  leaving water temperature is: ▪ weather­dependent  (i.e.  depends on  the  outdoor  ambient temperature) ▪ fixed in time (i.e., NOT scheduled) continued >> Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 49: Domestic Hot Water Control

    Moreover,  with  the  modulation  turned  on,  the desired leaving water temperature is lowered or raised in function of the desired room temperature and the difference between the actual and the desired room temperature. This results in: ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 50: Contact/Helpdesk Number

    Preset values make it easy to use the same value in the schedule or temperature for 4 persons compared to 3 to  adjust  the  desired  leaving  water  temperature  according  to  the persons. 0~20°C (default: 17°C) room temperature (see modulation). If you later want to change the [A.4.3.2.5] 5 persons value, you only have to do it in one place. Depending on whether the The increment of the desired tank desired leaving water temperature is weather dependent or not, the temperature for 5 persons compared to 4 absolute  desired  leaving  water  temperature  should  be  specified  or persons. 0~20°C (default: 1°C) the desired shift values. [A.4.3.2.6] 6 persons The increment of the desired tank temperature for 6 persons compared to 5 persons. 0~20°C (default: 1°C) Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 51 R=4°C (−2°C<T <2°C) (depending on the heat emitter), such situations can be avoided. ▪ 3 (enabled) L=2°C, R=8°C (−4°C<T <4°C) Example:  Set  the  minimum  leaving  water  temperature  to  28°C  to avoid  NOT  to  be  able  to  heat  up  the  room:  leaving  water ▪ 4 (enabled) L=4°C, temperatures must be sufficiently higher than the room temperatures R=8°C (−4°C<T <4°C) (in heating). ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 52 0.5°C. The actual room temperature is Thermo On/OFF: the valve closes, depending on [F­0B] when there displayed with an accuracy of 0.1°C. is no heating demand from the main zone. Enable this setting to: Room temperature hysteresis ▪ avoid  leaving  water  supply  to  the  heat  emitters  in  the  main  LWT zone (through the mixing valve station) when there is request from ONLY applicable in case of room thermostat control. The hysteresis the additional LWT zone. band  around  the  desired  room  temperature  is  settable.  Daikin advises NOT to change the room temperature hysteresis as it is set ▪ activate the On/OFF pump of the mixing valve station ONLY when for an optimal use of the system. there is demand. See "5 Application guidelines" on page 10. Code Description [A.3.1.1.6.1] [F­0B] The shut­off valve: [ 9-0C ] ▪...
  • Page 53: Domestic Hot Water Control: Advanced

    (according  to  the  weather dependent  curve).  During  weather  dependent  operation,  the  end­ user  cannot  adjust  the  desired  tank  temperature  on  the  user interface. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 54 This  maximum [5-03] [4-02] [F-01] allowable  hot  water  temperature  shall  be  selected according to the applicable legislation. Ambient (outdoor) temperature Time CAUTION Anti­recycle time Maximum running current Be  sure  that  the  disinfection  function  start  time  [A.4.4.3] with  defined  duration  [A.4.4.5]  is  NOT  interrupted  by possible domestic hot water demand. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 55: Heat Source Settings

    Make  sure  to  observe  all  rules  mentioned  in  application operation.  This  setting  is  only  overruled  when  backup  heating  is guideline 5 when bivalent operation function is enabled. required  during  defrost  operation  or  malfunctioning  of  the  outdoor Daikin  shall  NOT  be  held  liable  for  any  damage  resulting unit (when [A.5.1.2] [4­06] is enabled). from failure to observe this rule. Code...
  • Page 56: System Settings

    When  power  returns  after  a  power  supply  failure,  the  auto  restart 30­31 X2M) and the backup heater is function  reapplies  the  remote  controller  settings  at  the  time  of  the NOT connected to the preferential kWh power  failure.  Therefore,  Daikin  recommends  to  always  enable  the rate power supply. function. If  the  preferential  kWh  rate  power  supply  is  of  the  type  that  power Do NOT use 1 or 3.
  • Page 57 6  minutes  after  forced  defrost  operation  was [A.6.3.3] [5­05] Value: Only applicable in case of full enabled, the outdoor unit ignored the forced defrost request. time power limitation mode. Code Description 0~50 A, step 1 A (default: 50 A) [A.6.6] Do you want to start a defrost operation? [A.6.3.4] [5­09] Value: Only applicable in case of full ▪ OK time power limitation mode. ▪ Cancel 0~20 kW, step 0.5 kW (default: 20 kW) Amp. limits for DI: Only applicable in case of power limitation mode based on digital inputs and based on current values. [A.6.3.5.1] [5­05] Limit DI1 0~50 A, step 1 A (default: 50 A) [A.6.3.5.2] [5­06] Limit DI2 0~50 A, step 1 A (default: 50 A) ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 58 Pump  operation  during  flow  abnormality  [F­09]  defines  whether  the pump stops at flow abnormality or allow to continue operation when flow  abnormality  occurs.  This  functionality  is  only  valid  in  specific conditions  where  it  is  preferable  to  keep  the  pump  active  when  T <4°C (pump will be activated for 10 minutes and deactivated after 10 minutes).  Daikin  shall  NOT  be  held  liable  for  any  damage  resulting this functionality. Code Description [F­09] Pump continue operation when flow...
  • Page 59: Menu Structure: Overview

    Backlit LCD time Allowed operation mode User profile Unit of measurement Available home pages [7.3] Set schedules Room temp. LWT main LWT additional Tank temp. Quiet mode DHW pump [7.4] Preset values Room temperature LWT main Tank temperature Quiet level ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 60: Menu Structure: Overview Installer Settings

    Amp. value [A.7] Commissioning kW value Test run Amp. limits for DI UFH screed dryout kW limits for DI Air purge Priority Actuator test run INFORMATION Solar  kit  and  bottom  plate  heater  settings  are  shown  but NOT applicable for this unit. Settings shall NOT be used or changed. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 61: Commissioning

    >  Start  air  purge  and  press    to  start  the  air  purge function. insulated. The  correct  pipe  size  is  installed  and  the  pipes  are Result:  The  manual  air  purge  starts  and  the  following  screen appears. properly insulated. There is NO water leak inside the indoor unit. The shut­off valves are properly installed and fully open. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 62: To Perform An Automatic Air Purge

    1 Go  to  [A.7.1]:    >  Installer  settings  >  Commissioning  >  Test run. 2 Select a test and press  . Example: Heating. 3 Select OK and press  Result:  The  test  run  starts.  It  stops  automatically  when  done (±30 min). To stop it manually, press  , select OK and press  Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 63: Underfloor Heating Screed Dryout

    4 To delete a step, set the duration to "–" by pressing    last executed step. 5 Press   to save the schedule. 6 Modify and restart the execution of the program. INFORMATION It  is  important  that  there  is  no  empty  step  in  the  program. Hand­over to the user The  schedule  will  stop  when  a  blank  step  is  programmed OR when 20 consecutive steps have been executed. Once the test run is finished and the unit operates properly, please make sure the following is clear for the user: ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 64: Maintenance And Service

    ▪ Dirty water coming out of the relief valve: Check the following at least once a year: ▪ open the valve until the discharged water does not contain dirt anymore ▪ Water pressure ▪ flush and clean the complete tank, including the piping between ▪ Water filter the relief valve and cold water inlet. ▪ Water pressure relief valve To make sure this water originates from the tank, check after a tank ▪ Relief valve hose heat up cycle. ▪ Pressure relief valve of the domestic hot water tank It is recommended to do this maintenance more frequently. ▪ Switch box ▪ Descaling ▪ Chemical disinfection ▪ Anode Water pressure Check whether the water pressure is above 1 bar. If it is lower, add water. Water filter Clean the water filter. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 65: To Drain The Domestic Hot Water Tank

    The  heat  exchanger  of  the  outdoor  unit  can  get  blocked  up  due  to dust,  dirt,  leaves,  etc.  It  is  recommended  to  clean  the  heat exchanger  yearly.  A  blocked  heat  exchanger  can  lead  to  too  low pressure or too high pressure leading to worse performance. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 66: Troubleshooting

    Possible causes Corrective action The unit must start up out of its If the water temperature is too operation range (the water low, the unit uses the backup temperature is too low) heater to reach the minimum water temperature first (15°C). Check and make sure that: ▪ The  power  supply  to  the backup  heater  is  correctly wired. ▪ The  backup  heater  thermal protector is NOT activated. ▪ The  backup  heater  contactors are NOT broken. If the problem persists after you have conducted all of the above checks, contact your dealer. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 67: Symptom: The Pump Is Making Noise (Cavitation)

    The backup heater equilibrium Increase the “equilibrium page 23). temperature has not been temperature” to activate the The water circuit head is too high The water circuit head is the configured correctly backup heater operation at a difference in height between the higher outdoor temperature. Go indoor unit and the highest point of the water circuit. If the indoor ▪ [A.5.1.4]  >  Installer  settings  > unit is located at the highest Heat sources > Backup heater point of the installation, the > Equilibrium temp. OR installation height is considered 0 m. The maximum water circuit ▪ [A.8]  >  Installer  settings  > head is 10 m. Overview settings [5­00] Check the installation requirements. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 68: Symptom: The Pressure At The Tapping Point Is Temporarily Unusual High

    Large domestic hot water tapping When the Domestic hot water > Please contact your dealer. happened recently before the Setpoint mode > Reheat or programmed start­up of the Reheat + sched. is selected, it is disinfection function recommended to program the OU: Malfunction of outdoor start­up the disinfection function unit fan motor. Please contact at least 4 hours later than the last your dealer. expected large hot water tapping. This start­up can be set by OU: Power input overvoltage. installer settings (disinfection Please contact your dealer. function). When the Domestic hot water > OU: Cool/heat switchover Setpoint mode > Scheduled only is selected, it is recommended to problem. program a Storage eco 3 hours Please contact your dealer. before the scheduled start­up of the disinfection function to OU: Voltage/current sensor preheat the tank. problem. Please contact your dealer. OU: Malfunction of high pressure switch (HPS) Please contact your dealer. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 69 OU: Malfunction of inverter Please contact your dealer. radiating fin temperature rise. Heat exchanger temperature Please contact your dealer. sensor problem. OU: Inverter instantaneous Please contact your dealer. overcurrent (DC). Returning water temperature Please contact your dealer. sensor problem. OU: Malfunction of radiating Please contact your dealer. fin temperature sensor. User interface Please contact your dealer. communication problem. OU: Shortage of refrigerant. Please contact your dealer. Indoor/outdoor unit communication problem. OU: Defect of power supply voltage. Abnormal increase tank Please contact your dealer. temperature. OU: Transmission malfunction between main CPU­ INV CPU. Tank temperature sensor Please contact your dealer. problem. OU: Indoor/outdoor combination Please contact your dealer. problem. Power reset required. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 70: Disposal

    This  start­up  can  be  set  by installer settings (disinfection function). ▪ When  the  Domestic  hot  water  >  Setpoint  mode  > Scheduled  only  is  selected,  it  is  recommended  to program  a  Storage  eco  3  hours  before  the  scheduled start­up of the disinfection function to preheat the tank. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 71: Glossary

    Equipment  made  or  approved  by  Daikin  that  can  be combined  with  the  product  according  to  the  instructions  in the accompanying documentation. Field supply Equipment  not  made  by  Daikin  that  can  be  combined  with the  product  according  to  the  instructions  in  the accompanying documentation. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide...
  • Page 72: Technical Data

    IN CASE OF REMOVING STOP VALVE COVER NAME PLATE TERMINAL STRIP OUTDOOR AIR TEMPERATURE BRAND NAME LABEL WIRING INLET WITH EARTH TERMINAL THERMISTOR LIQUID STOP VALVE (Ø6.4 CuT) SERVICE PORT GAS STOP VALVE (Ø15.9 CuT) 3TW60814-1B Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 73: Dimensions And Service Space: Indoor Unit

    15 Technical data 15.1.2 Dimensions and service space: Indoor unit 3D087616-1 Gas pipe connection Ø15.9 mm Liquid pipe connection Ø6.35 mm Pressure gauge Safety valve Drain valve water circuit Air purge Stop valve with fill valve (included accessory) Water filter Water IN connection 1­1/4" female British standard pipe thread Water OUT connection 1­1/4" female British standard pipe thread Tank IN connection 1" female British standard pipe thread Tank OUT connection 1" female British standard pipe thread Control wiring intake (Ø24 mm) Power supply wiring intake (Ø24 mm) Levelling feet User interface (included accessory) Drain valve tank circuit Recirculation connection G 1/2" female ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 74 15 Technical data Hole for recirculation piping or option wiring (Ø62 mm) Drain outlet (unit+safety valve) Flow­through vessel (12 l) Note 1: Typical field installation is according to local and national regulations. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 75 15 Technical data MIN. 500 3D078541 ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 76: Components

    15 Technical data 15.2 Components 15.2.1 Components: Outdoor unit Switch box main PCB (inverter and control PCB) Terminal communication and power supply Service PCB 4­way valve Electronic expansion valve (main) Accumulator Compressor Liquid stop valve Gas stop valve Service port Fan motor Heat exchanger 15.2.2 Components: Switch box (outdoor unit) Service PCB Terminal communication cable Terminal power supply cable Earth connection Wire clamp Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 77: Components: Indoor Unit

    Remaining  air  in  the  water  circuit  will  be  automatically or blockage of the heat exchanger. removed via the air purge valve. Heat exchanger 3­way valve Water pump Controls whether the water is used for space heating, or the Circulates the water in the water circuit. domestic hot water tank. Thermistors User interface (accessory) Determines the water and refrigerant temperature at various Flow­through vessel points in the circuit. Drain flexible pressure relief valve Drain caps Air valve Tank thermistors Domestic hot water tank drain valve Empties the full tank. Switch box Contains  the  main  electronic  and  electrical  parts  of  the indoor unit. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 78: Components: Switch Box (Indoor Unit)

    The  components  in  the  switch  box are accessible by removing the switch box cover. 15.2.4 Components: Switch box (indoor unit) X6YB X6YA Pump PCB A7P (Inverter PCB) Backup heater thermal protector Q1L Transformer TR1 Backup heater contactors K1M, K2M and K5M Connectors X6YA/X6YB/X6Y Backup heater circuit breaker F1B Terminal block X2M (high voltage) Terminal block X1M (to outdoor unit) Cable tie mountings Digital I/O PCB A4P (only for installations with solar kit or digital I/O PCB kit) Demand PCB for power limitation Terminal block X5M (low voltage) Main PCB A1P PCB fuse FU1 Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 79: Piping Diagram

    12.7CuT 12.7CuT HIGH PRESSURE P > SWITCH FIELD PIPING 12.7CuT (6.4 CuT) 6.4CuT LIQUID STOP VALVE MUFFLER MUFFLER 12.7CuT FIELD PIPING 7.9CuT (15.9 CuT) GAS STOP VALVE DISCHARGE PIPE WITH SERVICE PORT THERMISTOR ACCUMULATOR COMPRESSOR 3TW60815-1 ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 80: Piping Diagram: Indoor Unit

    SCREW CONNECTION Inlet water thermistor Refrigerant liquid side thermistor Outlet water backup heater thermistor FLARE CONNECTION QUICK COUPLING Outlet water heat exchanger thermistor THERMISTOR DESCRIPTION FLANGE CONNECTION SPINNED PIPE BRAZED CONNECTION PINCHED PIPE 3D077572-1A page 2 Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 81: Wiring Diagram

    PRESSURE SWITCH (HIGH) INTERIGENT POWER MODULE PRINTED CIRCUIT BOARD (SERVICE) TERMINAL STRIP FIXED PLATE NOTES: REFER TO PURCHASING SPECIFICATION AS303002, UNLESS OTHERWISE SPECIFIED THIS DRAWING WAS DRAWN ON CAD SYSTEM 3TW60816-1A SIZE: LENGTH 140 x WIDTH 230. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 82 LED A, LED B Pilot lamp X11A, X12A Connector Compressor motor X1M, X2M Terminal strip Compressor fan Electronic expansion valve MR30, MRM306, Magnetic relay Reversing solenoid valve coil MRM307, MR4 Z1C~Z4C Ferrite core MRM10, MRM20 Magnetic relay Field wiring MR30_A~MR30_B Connector Terminal strip Neutral Connector PCB1 Printed circuit board (main) Terminal PCB2 Printed circuit board (inverter) Protective earth PCB3 Printed circuit board (service) Black Q1DI Earth leakage circuit breaker Blue Overload protector Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 83 15 Technical data Brown Green Orange Purple White Yellow ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 84: Wiring Diagram: Indoor Unit

    Ext. thermistor Heat pump convector Add LWT: * : optional On/OFF thermostat (wired) (*) : standard for *HV*, optional for *HB* On/OFF thermostat (wireless) # : field supply Ext. thermistor Heat pump convector 4D077028 page 1 Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 85 Min. load 20 mA - 5 V DC Only for demand PCB option only for EKBPHT* only if no EKBPHT* Options: bottom plate heater OR On/OFF output Only for digital I/O PCB option 4D077028 page 3 ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 86 Backup heater element (2 kW) Inlet water thermistor Backup heater element (3 kW) (*) Domestic hot water thermistor Booster heater (3 kW) External indoor or outdoor ambient thermistor Overcurrent fuse backup heater R1H (A3P) Humidity sensor Overcurrent fuse booster heater Preferential kWh rate power supply contact Thermal fuse backup heater Electrical meter pulse input 1 F1U, F2U Fuse 5 A 250 V for digital I/O PCB Electrical meter pulse input 2 Fuse T 6.3 A 250 V for PCB S6S~S9S Digital power limitation inputs PHC1 Optocoupler input circuit SS1 (A4P) Selector switch K1M, K2M Contactor backup heater T1R (A7P) Rectifier bridge (not applicable) Contactor booster heater Power supply transformer Safety contactor backup heater (only for *9W) Terminal strip Relay on PCB Connector Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 87 (only for *9W) User installed options User installed options Bottom plate heater Bottom plate heater Domestic hot water tank Domestic hot water tank Domestic hot water tank with Domestic hot water tank with solar connection solar connection Remote user interface Remote user interface Ext. indoor thermistor Extended indoor thermistor Ext outdoor thermistor Extended outdoor thermistor Digital I/O PCB Digital I/O PCB Demand PCB Demand PCB Solar pump and control station Solar pump and control station Main LWT Main leaving water temperature On/OFF thermostat (wired) On/OFF thermostat (wired) On/OFF thermostat (wireless) On/OFF thermostat (wireless) Ext. thermistor Extended thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 88 15 Technical data Electrical connection diagram Daikin Altherma For more details please check unit wiring Power supply Standard parts Only for normal power supply installation Notes: 5 or 3 core unit power supply: 400 V or 230 V + earth - In case of signal cable: keep minimum distance to power cables >5 cm...
  • Page 89 3 / 6 6 / 9 3 / 6 6 / 9 configuration Regular kWh rate power supply Electrical 3~ balanced meter type 3~ unbalanced Benefit kWh rate power supply Electrical 3~ balanced meter type 3~ unbalanced 4D078288 ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 90: Technical Specifications

    59 kg Packing Material EPS, carton Weight 3 kg Heat exchanger Specifications Length 845 mm Nr. of rows Fin pitch 1.8 mm Nr. of passes — Face area — Nr. of stages Tube type Hi­Xa(8) Type WF fin Treatment Anti­corrosion treatment (PE) Type Propeller Quantity Air flow rate (nominal at Heating — 230 V) Discharge direction Horizontal Motor Quantity Output Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 91 Flare connection Diameter (OD) Ø15.9 mm Drain Quantity Type hole Diameter (OD) 1× Ø15 mm + 1× Ø20 mm Piping length Minimum 3 m Maximum 30 m Equivalent — Chargeless — Additional refrigerant charge 0.02 kg/m IF >10 m Maximum height difference between outdoor unit and 20 m indoor unit Defrost method Reverse cycle Defrost control Sensor for outdoor heat exchanger temperature Capacity control method Inverter controlled Standard accessories Item Installation manual Quality See operation range drawing. (*) Range increase by support backup heater. The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to the sound spectrum drawing for more information. ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 92 Wiring connections For power supply Quantity Remark — For connection with indoor Quantity Remark Earth wire European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low­voltage systems with input current >16 A and ≤75 A per phase. See figure A. Figure A: Starting current Daikin  inverter  controlled  compressor  starting  current  always  less then or equal to maximal running current. Running current Time Maximum Example 1 Example 2 Standard  on/off  compressor  starting  current  to  maximum  running current Running current Time Maximum Example 1 Example 2...
  • Page 93: Technical Specifications: Indoor Unit

    Volume 10 l Maximum water pressure 3 bar Pre­pressure 1 bar Water filter Diameter perforations Material Copper + brass + stainless steel Main components tank Tank Water volume 180 l Material Stainless steel (EN1.4521) Maximum temperature 65°C Maximum pressure 10 bar Insulation material Corrosion protection Anode Heatloss 1.4 kWh/24 h Heat exchanger Quantity Material Stainless steel (EN1.4521) Surface 1.9 m Internal coil volume 8.9 l 3­way valve Flow factor space heating/tank heating 13/8 m ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 94 Nominal flow (heating) 42 dBa Sound pressure Nominal flow (heating) 28 dBa Operation range Ambient Space heating –25~25°C Domestic hot water –25~35°C Water side Space heating 15~55°C (10) Domestic hot water 25~60°C Heatloss according to EN12897. Ambient temperature 35°C – leaving water evaporator 7°C (DT=5°C). DB/WB 7°C/6°C – leaving water condenser 35°C (DT=5°C). The sound pressure level is measured via a microphone at 1 m from the unit. It is a relative value, depending on the distance and acoustic environment. The sound pressure level mentioned is valid for pump medium speed – 0 external static pressure/medium speed – nominal flow/ high speed – nominal flow. 15°C~25°C: backup heater only, no heat pump operation during commissioning.. Including piping, plate heat exchanger, and backup heater/excluding expansion vessel. Value mentioned is connection after ball valves. It is the same as the connection at the unit (G 1­1/4" female). Ambient temperature 35°C – leaving water evaporator 18°C (DT=5°C). For details, see operation range drawing. (10) For outdoor units: >55°C backup heater only, no heat pump operation. (11) Minimum flow is mentioned for heat pump operation. To allow backup heater to operate safely, a higher minimum flow is required: 12 l/min. (12) Refer to operation range for details. (13) DB/WB 7°C/6°C – leaving water condenser 45°C (DT=5°C). Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 95 Type of wires Minimum 0.75 mm For connection with A3P Quantity of wires Note (3)    Type of wires Note Note For connection with M2S Quantity of wires (3)    Type of wires Note Note For connection with optional FWXV (demand input Quantity of wires and output) Type of wires 100 mA, minimum 0.75 mm Above mentioned power supply of the hydrobox is for the backup heater only. The switch box and pump of the hydrobox are supplied via the outdoor unit. Select diameter and type according to national and local regulations. For more details of the voltage range and current refer to the installation manual. Voltage: 230 V / maximum current: 100 mA / minimum 0.75 mm Depends on thermostat type, refer to the installation manual. Note 10: Backup heater (*3V), minimum time delay between stages. 1 min 10 min Capacity Stage 1 Time ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 96: Operation Range

    Operation range 15.6.1 Operation range: Heating A (°C DB) –15 –20 –25 B (°C) 15 18 25 30 45 50 55 3TW60813-1B_page 2 Outdoor temperature Leaving condenser water temperature Outdoor unit operation is possible if setpoint ≥  2 5°C. Only backup heater operation (no outdoor unit operation) Operation of outdoor unit, but no guarantee of capacity. (If outdoor temperature <  –   2 0°C or <  –   2 5°C outdoor unit will stop)(Indoor unit and backup heater operation will continue) Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 97: Operation Range: Domestic Hot Water

    A (°C DB) –15 –20 –25 45 50 B (°C) 3TW60813-2C_page 2 Only for ERLQ006CAV3+ERLQ008CAV3 A (°C DB) –15 –20 –25 B (°C) 3TW60813-2C_page 2 Outdoor temperature Domestic hot water temperature Only backup heater operation. Operation of outdoor unit, but no guarantee of capacity. (If outdoor temperature <  –   2 0°C or <  –   2 5°C outdoor unit will stop)(Indoor unit and backup heater operation will continue) ERLQ004~008CA + EHVH04+08S18CA3VF Installer reference guide Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 98: Esp Curve

    A (kPa) B (l/min) Only for EHVH08S18CA3VF A (kPa) B (l/min) External static pressure available at space heating/cooling circuit Water flow rate: water flow through space heating/cooling circuit Note  1:  Selecting  a  flow  outside  the  area  of  operation  can  cause damage or malfunction of the unit. See also minimum and maximum allow water flow range in the technical specifications. Note  2:  Water  quality  MUST  be  according  to  EN  directive EC98/83EC. Installer reference guide ERLQ004~008CA + EHVH04+08S18CA3VF Daikin Altherma low temperature split 4P366226­1 – 2014.01...
  • Page 99: Field Settings Table

    Field settings table Applicable indoor units EHVH04S18CA3VF EHVH08S18CA3VF Notes 4P366223-1 - 2014.02...
  • Page 101 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value User settings └─ Preset values └─ Room temperature 7.4.1.1 Comfort (heating) [3-07]~[3-06], step: A.3.2.4 21°C 7.4.1.2 Eco (heating) [3-07]~[3-06], step: A.3.2.4 19°C └─...
  • Page 102 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value A.3.1.1.3 [1-02] Set weather-dependent heating Leaving water value for low ambient temp. for 25~55°C, step: 1°C LWT main zone heating WD curve. 35°C A.3.1.1.3 [1-03]...
  • Page 103 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value └─ Auto restart A.6.1 [3-00] 0: No 1: Yes └─ Preferential kWh rate A.6.2.1 [D-00] Allowed heaters 0: None 2: BUH only A.6.2.2 [D-05]...
  • Page 104 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value A.8.31 [2-09] Adjust the offset on the measured room temperature -5~5°C, step: 0,5°C 0°C A.8.32 [2-0A] Adjust the offset on the measured room temperature -5~5°C, step: 0,5°C 0°C A.8.33...
  • Page 105 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value A.8.95 [8-07] A.8.96 [8-08] A.8.97 [8-09] What is the desired comfort main LWT in heating? [9-01]~[9-00], step: 1°C 35°C A.8.98 [8-0A] What is the desired eco main LWT in heating?
  • Page 106 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value A.8.152 [F-01] A.8.153 [F-02] A.8.154 [F-03] A.8.155 [F-04] A.8.156 [F-05] A.8.157 [F-06] A.8.158 [F-09] Pump operation during flow abnormality. 0: Disabled 1: Enabled A.8.159...
  • Page 108 4P366226­1  2014.01...

Table of Contents