6 Preparation

▪ During suspend (see
"8  Configuration"  on page 
unit is turned down to reduce the standby energy losses. As a
result, the outdoor ambient temperature is NOT read out.
▪ If the desired leaving water temperature is weather dependent, the
full time outdoor temperature measurement is important. This is
another reason to install the optional outdoor ambient temperature
sensor.
INFORMATION
The external outdoor ambient sensor data (either averaged
or instantaneous) is used in the weather-dependent control
curves. To protect the outdoor unit, the internal sensor of
the outdoor unit is always used.
6
Preparation
6.1

Overview: Preparation

This chapter describes what you have to do and know before going
on-site.
It contains information about:
▪ Preparing the installation site
▪ Preparing the refrigerant piping
▪ Preparing the water piping
▪ Preparing the electrical wiring
6.2

Preparing installation site

Do NOT install the unit in places often used as work place. In case
of construction works (e.g. grinding works) where a lot of dust is
created, the unit must be covered.
Choose the installation location with sufficient place for carrying the
unit in and out of the site.
NOTICE
This unit is designed for operation on 2 temperature zones:
▪ underfloor
heating
temperature 35°C), this is the zone with the lowest
water temperature,
▪ radiators in the additional zone (water temperature
45°C), this is the zone with the highest water
temperature.
6.2.1
Installation site requirements of the
outdoor unit
INFORMATION
Also read the following requirements:
▪ General
installation
"General safety precautions" chapter.
▪ Refrigerant
piping
difference). See further in this "Preparation" chapter.
Mind the following spacing guidelines:
>250
>350
b
a
(mm)
Installer reference guide
16
38), the outdoor
in
the
main
zone
(water
site
requirements.
See
the
requirements
(length,
height
b
>250
a
>250
(mm)
a
Air outlet
b
Air inlet
See
"14.2  Dimensions and service space"  on page  71
detailed information about spacing guidelines.
NOTICE
▪ Do NOT stack the units on each other.
▪ Do NOT hang the unit on a ceiling.
Strong winds (≥18 km/h) blowing against the outdoor unit's air outlet
causes short circuit (suction of discharge air). This may result in:
▪ deterioration of the operational capacity;
▪ frequent frost acceleration in heating operation;
▪ disruption of operation due to decrease of low pressure or
increase of high pressure;
▪ a broken fan (if a strong wind blows continuously on the fan, it
may start rotating very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is
exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing
the wall and NOT directly exposed to the wind.
b
a
Baffle plate
b
Prevailing wind direction
c
Air outlet
Do NOT install the unit in the following places:
▪ Sound sensitive areas (e.g. near a bedroom and the like), so that
the operation noise will cause no trouble.
Note: If the sound is measured under actual installation
conditions, the measured value might be higher than the sound
pressure level mentioned in Sound spectrum in the data book due
to environmental noise and sound reflections.
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall
off or cause water leakage.
It is NOT recommended to install the unit in the following places
because it may shorten the life of the unit:
▪ in coastal areas or other places where the air contains high levels
of salt. Corrosion may occur,
▪ where the voltage fluctuates a lot,
▪ in vehicles or vessels,
▪ where acidic or alkaline vapour is present.
The outdoor unit is designed for outdoor installation only, and for
ambient temperatures ranging 10~43°C in cooling mode and –
25~25°C in heating mode.
for more
b
a
ERLQ004~008CA + EHVZ04+08S18CB
Daikin Altherma – Low temperature split