14.8
Operation range
14.8.1
Operation range: Heating and cooling
Space heating and cooling mode (for current models in this manual)
Remark: Cooling mode is NOT applicable for EHVZ04, EHVZ08,
and EHVZ16.
Cooling mode
4~8 kW
A (°C DB)
43
18
10
5
13
22
50
B (°C)
3TW60813-1D
A
Outdoor temperature
B
Leaving water evaporator temperature
C
Leaving water condensor temperature
Backup heater only operation. No outdoor operation.
Outdoor unit operation is possible if setpoint ≥ 2 5°C.
Operation of outdoor unit is possible, but with possible capacity reduction. If the outdoor temperature < – 2 5°C, the outdoor unit will stop. Indoor
unit and backup heater operation will continue.
Pull-down area.
Remark: In restricted power supply mode, the outdoor unit, booster heater, and backup heater can only operate separately.
(*)
ERLQ units include special equipment (insulation, heater sheet,...) to ensure proper operation in areas with low ambient temperatures and high
humidity conditions. In such conditions, the ERHQ models may experience problems with severe ice buildup on the air-cooled coil. If such
conditions are expected, the ERLQ must be installed instead. These models contain countermeasures (insulation, heater sheet,...) to prevent
freeze-up.
ERLQ004~008CA + EHVZ04+08S18CB
Daikin Altherma – Low temperature split
4P401676-1 – 2015.02
Heating mode
4~8 kW
A (°C DB)
25
10
0
–15
–20
–25
15 18 25
50
55
30
45
C (°C)
3TW60813-1D
Cooling mode
11~16 kW
A (°C DB)
46
10
5
22
B (°C)
3TW60813-1D
14 Technical data
Heating mode
11~16 kW
A (°C DB)
35
0
*
–20
–25
15 18 25
55
C (°C)
3TW60813-1D
Installer reference guide
93