Symptom: The Water Pressure Relief Valve Leaks; Symptom: The Space Is Not Sufficiently Heated At Low Outdoor Temperatures; Symptom: The Pressure At The Tapping Point Is Temporarily Unusual High; Symptom: Decoration Panels Are Pushed Away Due To A Swollen Tank - Daikin Altherma ERLQ004-006-008CA Reference Manual

Low temperature split
Hide thumbs Also See for Altherma ERLQ004-006-008CA:
Table of Contents

Advertisement

12 Troubleshooting
Possible causes
The water volume in the
installation is too high
The water circuit head is too high The water circuit head is the
12.3.5
Symptom: The water pressure relief valve
leaks
Possible causes
Dirt is blocking the water
pressure relief valve outlet
12.3.6
Symptom: The space is NOT sufficiently
heated at low outdoor temperatures
Possible causes
The backup heater operation is
not activated
Installer reference guide
66
Corrective action
Make sure that the water volume
in the installation is below the
maximum allowed value (see
"6.4.3 To check the water
volume" on page 19
and
"6.4.4 Changing the pre-pressure
of the expansion vessel" on
page 20).
difference in height between the
indoor unit and the highest point
of the water circuit. If the indoor
unit is located at the highest
point of the installation, the
installation height is considered
0 m. The maximum water circuit
head is 10 m.
Check the installation
requirements.
Corrective action
Check whether the pressure
relief valve works correctly by
turning the red knob on the valve
counterclockwise:
▪ If you do NOT hear a clacking
sound, contact your dealer.
▪ If the water keeps running out
of the unit, close both the
water inlet and outlet shut-off
valves first and then contact
your dealer.
Corrective action
Check and make sure that:
▪ The backup heater operation
mode is enabled. Go to:
▪ [A.5.1.1] > Installer settings
> Heat sources > Backup
heater > Operation mode
[4‑00]
▪ The thermal protector of the
backup heater has not been
activated. If it has, check:
▪ The water pressure
▪ Whether there is air in the
system
▪ The air purge operation
Press the reset button in the
switch box. See
"14.4 Components" on page 74
for the location of the reset
button.
Possible causes
The backup heater equilibrium
temperature has not been
configured correctly
Too much heat pump capacity is
used for heating domestic hot
water
12.3.7
Symptom: The pressure at the tapping
point is temporarily unusual high
Possible causes
Failing or blocked pressure relief
valve.
12.3.8
Symptom: Decoration panels are pushed
away due to a swollen tank
Possible causes
Failing or blocked pressure relief
valve.
12.3.9
Symptom: Tank disinfection function is
NOT completed correctly (AH-error)
Possible causes
The disinfection function was
interrupted by domestic hot water
tapping
Corrective action
Increase the "equilibrium
temperature" to activate the
backup heater operation at a
higher outdoor temperature. Go
to:
▪ [A.5.1.4] > Installer settings >
Heat sources > Backup heater
> Equilibrium temp. OR
▪ [A.8] > Installer settings >
Overview settings [5‑01]
Check and make sure that the
"space heating priority" settings
have been configured
appropriately:
▪ Make sure that the "space
heating priority status" has
been enabled. Go to [A.8] >
Installer settings > Overview
settings [5‑02]
▪ Increase the "space heating
priority
temperature"
activate
backup
heater
operation at a higher outdoor
temperature. Go to [A.8] >
Installer settings > Overview
settings [5‑03]
Corrective action
▪ Flush and clean the complete
tank
including
the
piping
between pressure relief valve
and the cold water inlet.
▪ Replace the pressure relief
valve.
Corrective action
Contact your local dealer.
Corrective action
Program the start-up of the
disinfection function when the
coming 4 hours NO domestic hot
water tapping is expected.
ERLQ004~008CA + EHVZ04+08S18CB
Daikin Altherma – Low temperature split
4P401676-1 – 2015.02
to