Domestic Hot Water Control: Advanced - Daikin Altherma ERLQ004-006-008CA Reference Manual

Low temperature split
Hide thumbs Also See for Altherma ERLQ004-006-008CA:
Table of Contents

Advertisement

8 Configuration
Shut-off valve
The following is only applicable in case of 2 leaving water
temperature zones. In case of 1 leaving water temperature zone,
connect the shut-off valve to the heating output.
The shut-off valve, which is in the main leaving water temperature
zone, output is configurable.
INFORMATION
During defrost operation, the shut-off valve is ALWAYS
opened.
Thermo On/OFF: the valve closes, depending on [F‑0B] when there
is no heating demand from the main zone.
#
Code
[A.3.1.1.6.1] [F-0B]
The shut-off valve:
▪ 0 (No)(default): is NOT influenced by
heating demand.
▪ 1 (Yes): closes when there is NO
heating demand.
INFORMATION
The setting [F‑0B] is only valid when there is a thermostat
or external room thermostat request setting (NOT in case
of leaving water temperature setting).
Operation range
Depending on the average outdoor temperature, the operation of the
unit in space heating is prohibited.
Space heating OFF temp: When the averaged outdoor temperature
raises above this value, space heating is turned OFF to avoid
overheating.
#
Code
[A.3.3.1]
[4-02]
▪ EHVZ04+08:
25°C)
▪ EHVZ16: 14°C~35°C (default: 35°C)
8.3.2

Domestic hot water control: advanced

Preset tank temperatures
Only applicable when domestic hot water preparation is scheduled
or scheduled + reheat.
You can define preset tank temperatures:
▪ storage economic
▪ storage comfort
▪ reheat
Preset values make it easy to use the same value in the schedule. If
you later want to change the value, you only have to do it in 1 place
(see also operation manual and/or user reference guide).
Storage comfort
When programming the schedule, you can make use of the tank
temperatures set as preset values. The tank will then heat up until
these setpoint temperatures have been reached. Additionally, a
storage stop can be programmed. This feature puts a stop to tank
heating even if the setpoint has NOT been reached. Only program a
storage stop when tank heating is absolutely undesirable.
#
Code
[7.4.3.1]
[6-0A]
30°C~[6‑0E]°C (default: 60°C)
Storage eco
The storage economic temperature denotes the lower desired tank
temperature. It is the desired temperature when a storage economic
action is scheduled (preferably during day).
Installer reference guide
50
Description
Description
14°C~35°C
(default:
Description
#
Code
[7.4.3.2]
[6-0B]
30°C~min(50, [6‑0E])°C (default: 45°C)
Reheat
The desired reheat tank temperature is used:
▪ in reheat mode or scheduled + reheat mode: The guaranteed
minimum tank temperature is set by T
[6‑0C] or the weather dependent setpoint, minus the reheat
hysteresis. If the tank temperature drops below this value, the tank
is heated up.
▪ during storage comfort, to prioritize the domestic hot water
preparation. When the tank temperature raises above this value,
domestic hot water preparation and space heating is executed
sequentially.
#
Code
[7.4.3.3]
[6-0C]
30°C~min(50, [6‑0E])°C (default: 45°C)
Weather dependent
The weather dependent installer settings define the parameters for
the weather dependent operation of the unit. When weather
dependent operation is active the desired tank temperature is
determined automatically depending on the averaged outdoor
temperature: low outdoor temperatures will result in higher desired
tank temperatures as the cold water tap is colder and vice versa. In
case of scheduled or scheduled+reheat domestic hot water
preparation, the storage comfort temperature is weather dependent
(according to the weather dependent curve), the storage economic
and reheat temperature are NOT weather dependent. In case of
reheat only domestic hot water preparation, the desired tank
temperature is weather dependent (according to the weather
dependent curve). During weather dependent operation, the end-
user cannot adjust the desired tank temperature on the user
interface.
#
Code
[A.4.6]
N/A
Weather dependent desired tank
temperature is:
▪ Fixed (default): disabled. All desired
tank temperature are NOT weather
dependent.
▪ Weather dep.: enabled. In scheduled
or
storage
weather dependent. Storage economic
and reheat temperatures are NOT
weather dependent. In reheat mode,
the
weather dependent.
Note:
temperature is weather dependent, it
cannot be adjusted on the user
interface.
Description
–[6‑08], which is either
HP OFF
Description
Description
scheduled+reheat
mode,
the
comfort
temperature
desired
tank
temperature
When
the
displayed
tank
ERLQ004~008CA + EHVZ04+08S18CB
Daikin Altherma – Low temperature split
4P401676-1 – 2015.02