Code
[A.4.7]
[0-0E]
Weather-dependent curve
T
[0-0D]
[0-0C]
[0-0C]
[0-0B]
[0-0B]
▪ T
DHW
▪ T
: The (averaged) outdoor ambient
a
temperature
▪ [0-0E]:
temperature: –40°C~5°C (default: –
10°C)
▪ [0-0D]:
temperature:
15°C)
▪ [0-0C]: desired tank temperature when
the outdoor temperature equals or
drops
temperature: 45°C~[6‑0E]°C (default:
60°C)
▪ [0-0B]: desired tank temperature when
the outdoor temperature equals or
rises
temperature: 35°C~[6‑0E]°C (default:
55°C)
Limits on heat pump operation
In domestic hot water operation, following hysteresis values can be
set for the heat pump operation:
#
Code
N/A
[6-00]
The temperature difference determining
the heat pump ON temperature.
Range: 2°C~20°C (default: 2°C)
N/A
[6-01]
The temperature difference determining
the heat pump OFF temperature.
Range: 0°C~10°C (default: 2°C)
Example:
T
DHW
T
= T
60
U
BUH OFF
T
50
HP MAX
[6-01]
T
48
[6-00]
HP OFF
T
46
HP ON
40
30
20
HP
10
5
BUH
Backup heater
HP
Heat pump. If heating up time by the heat pump takes too
long, auxiliary heating by the backup heater can take place
T
Backup heater OFF temperature (T
BUH OFF
T
Maximum heat pump temperature at sensor in domestic
HP MAX
hot water tank
T
Heat pump OFF temperature (T
HP OFF
T
Heat pump ON temperature (T
HP ON
T
Domestic hot water temperature
DHW
ERLQ004~008CA + EHVZ04+08S18CB
Daikin Altherma – Low temperature split
4P401676-1 – 2015.02
Description
DHW
T
a
[0-0E]
[0-0D]
: The desired tank temperature.
low
outdoor
ambient
high
outdoor
ambient
10°C~25°C
(default:
below
the
low
ambient
above
the
high
ambient
Description
T
= 60°C
U
T
= 50°C
BUH
HP MAX
HP
[6-01] =
2°C
[6-00] =
2°C
)
U
−[6-01])
HP MAX
−[6-00])
HP OFF
T
User set point temperature (as set on the user interface)
U
t
Time
Timers for simultaneous request space and domestic hot water
operation
#
Code
N/A
[8-00]
N/A
[8-01]
N/A
[8-02]
N/A
[8-04]
[8-02]: Anti-recycling time
1
0
1
0
[8-00]
[8-01]
1
Heat pump domestic water heating mode (1=active, 0=not
active)
2
Hot water request for heat pump (1=request, 0=no request)
t
Time
[8-04]: Additional running time at [4-02]/[F-01]
t
[8-01]+
[8-04]
t
[8-02]
[8-01]
0
[5-03]
[4-02]
T
Ambient (outdoor) temperature
A
t
Time
Anti-recycle time
8 Configuration
Description
Do not change. (default: 1)
Maximum running time for domestic hot
water operation. Domestic hot water
heating stops even when the target
domestic hot water temperature is NOT
reached. The actual maximum running
time also depends on setting [8‑04].
▪ When
system
layout
thermostat control: This preset value is
only taken into account if there is a
request for space heating. If there is
NO request for space heating, the tank
is heated until the setpoint has been
reached.
▪ When
system
layout
thermostat control: This preset value is
always taken into account.
Range: 5~95 minutes (default: 30)
Anti-recycling time.
Minimum time between two cycles for
domestic hot water. The actual anti-
recycling time also depends on setting
[8‑04].
Range: 0~10 hours (default: 0.5) (step:
0.5 hour).
Remark: The minimum time is 1/2 hour
even when the selected value is 0.
Additional running time for the maximum
running time depending on the outdoor
temperature [4‑02].
Range: 0~95 minutes (default: 95).
t
[8-02]
T
A
Installer reference guide
=
Room
Room
51