6.3.4 Overview of electrical connections for external and internal screed dryout ..............55 actuators................21 9.6.4 To interrupt an underfloor heating screed dryout ....55 10 Hand-over to the user Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
12.3.7 Symptom: The pressure at the tapping point is temporarily Latest revisions of the supplied documentation may be available on unusual high ...............59 the regional Daikin website or via your dealer. 12.3.8 Symptom: Decoration panels are pushed away due to a swollen tank................59 12.4 Solving problems based on error codes.........59...
Name and address of fire department, police and hospital Name, address and day and night telephone numbers for obtaining service In Europe, EN378 provides the necessary guidance for this logbook. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
After finishing the electrical work, confirm that each electrical component and terminal inside the electrical components box is connected securely. Make sure all covers are closed before starting up the unit. Remove the accessories. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Only for EHVH/X16 models: Control signal for bottom plate heater kit EKBPHTH16A For installation instructions, see the installation manual of the digital I/O PCB and addendum book for optional equipment. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
ERLQ014CAW1 ERLQ016CAW1 Application guidelines Setting up the space heating/cooling system The Daikin heat pump system supplies leaving water to heat emitters in one or more rooms. Because the system offers a wide flexibility to control the temperature Overview: Application guidelines...
(modulation). This results in: Benefits Stable room temperature matching the desired temperature Wireless. The Daikin external room thermostat is available in a (higher comfort) wireless version. Less ON/OFF cycles (more quiet, higher comfort and Efficiency. Although the external room thermostat only sends...
The under floor heating is shut off by the shut-off valve. Example: If the heat pump system is used to heat up one floor where all the rooms have the same heat emitters. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 10
B Room 1 B Room 2 a Remote controller of the heat pump convectors The desired room temperature is set via the remote controller of the heat pump convectors. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
The user interface connected to the indoor unit decides the NOTICE space operation mode. To increase comfort and performance, Daikin recommends The heating or cooling demand signals of each heat pump to install the valve kit option EKVKHPC on each heat pump convector are connected in parallel to the digital input on the convector.
The combination of the two heat emitter systems provides the excellent heating comfort of the under floor heating, and the excellent cooling comfort of the heat pump convectors. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Make sure the auxiliary boiler and its integration in the Boiler Boiler system complies with applicable legislation. NOTICE Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler system. Make sure the auxiliary contact has enough differential or time delay to prevent frequent changeover between Make sure the return water to the heat pump does NOT exceed indoor unit and auxiliary boiler.
5 Application guidelines 5.4.2 System layout – Standalone DHW tank If energy prices are the same during the day and the night, Daikin recommends to heat up the DHW tank during the day. If energy prices are lower during the night, Daikin recommends to heat up the DHW tank during the night.
For more information, see the configuration chapter. You can program a schedule to control the DHW pump via the user interface. For more information, see the user reference guide. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Power meter 2: In case of a single-phase backup heater configuration, use a single-phase power meter. In other cases, use a three-phase power meter. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
(sum of outdoor unit, indoor unit, backup heater and management system. optional booster heater). The power or current of the entire Daikin system is limited Configuration: Set the power limitation level and how it has dynamically by digital inputs (maximum four steps). Each power to be achieved via the user interface.
Therefore, the electrical heaters are limited and turned OFF first. The of, for example, door opening/closing system limits power consumption in the following order: If this is NOT possible, Daikin recommends to connect a remote Limits certain electrical heaters. indoor sensor (option KRCS01-1).
Check that the air purge is NOT tightened too much, so that automatic release of air in the water circuit is possible. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
FHL1...3 Floor heating loop (field supply) point and the recirculation connection of the domestic hot water T1...3 Individual room thermostat (optional) tank. M1...3 Individual motorised valve to control loop FHL1...3 (field supply) Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Make electrical connections to the fixed wiring. All components procured on the site and all electrical construction must comply with applicable legislation. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
The following illustration shows the required field wiring. INFORMATION The following illustration is an example and may NOT match your system layout. a Indoor unit Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Required number of type Power supply conductors 1x 230 V 2+GND 1x 230 V 2+GND + 2 bridges 3x 230 V 3+GND + 1 bridge 3x 400 V 4+GND EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Domestic cold water in (cold water supply) NOTICE It is recommended to install shut-off valves to domestic cold water in and domestic hot water out connections. Shut-off valves are field supplied. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the sealing materials should be at least 20 mm to prevent condensation on the surface of the sealing. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
NOT come in contact with the piping and sharp edges. CAUTION Do NOT push or place redundant cable length in the unit. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
X6M and X7M need to be changed to configure a backup heater. type supply terminals Refer to the illustration below as a caution about handling the 3 kW 1~ 230 V — terminals. (*3V) EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
2 4 6 14 user interface by overtightening the mounting screws. Cut off a 2 wire conductor. Connect the wires to the user interface as shown below. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Wiring is different for a NC (normal closed) valve and a NO (normal open) valve. From the left Fix the cable with cable ties to the cable tie mountings. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Fix the cable with cable ties to the cable tie mountings. a Installation of EKRP1AHTA is required. Fix the cable with cable ties to the cable tie mountings. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
To access the overview settings necessary, you can also make changes to the configuration Set the user permission level to Installer. afterwards. Go to [A.8]: > Installer settings > Overview settings. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
The user interface requests confirmation if you are sure to proceed. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
(e.g. heat pump convector). 2 (RT control): Unit operation is decided based on the ambient temperature of the user interface. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 34
Example: Using a room thermostat creates thermo ON/OFF condition. When there is no such demand, the pump is OFF. Remark: Request is NOT available in leaving water temperature control. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Tank Remark: This value only c Domestic hot water pump meaning in room thermostat control. d Heater element e Non-return valve f Shower g Cold water EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Only applicable for EHBH/X04+08 and EHVH/X04+08. Indicates if the optional demand PCB is installed. 0 (No)(default): NOT installed. (Yes): Installed. Power consumption control by digital inputs is selectable in [A.6.2.1]. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
The scheduled actions consists of desired leaving water temperatures either preset or custom Remark: This value can only leaving water temperature control. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 38
(default: Remark: This value can only 18°C). leaving water Note: This value should be lower temperature control. than [1-08] as for high outdoor temperatures colder water required. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 39
Range: 3~10°C (in steps of 1°C; default value: 5°C). [A.3.1.3.2] [9-0A] Cooling: required temperature difference between entering and leaving water. Range: 3~10°C (in steps of 1°C; default value: 5°C). EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
[A.4.4.2]: Operation day. [A.4.3.2.1] 1 person The increment of the desired tank temperature for 2 persons compared to 1 person. 0~20°C (default: 4°C) Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
18~20°C to prevent condensation on the floor. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 42
The compressor will startup again when the leaving water temperature drops below the desired leaving water temperature. This function is only applicable in heating mode. Code Description [9-04] 1~4°C (default: 1°C) Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 43
Only applicable in case of room thermostat control. The hysteresis 0 (No): is NOT influenced by heating or band around the desired room temperature is settable. Daikin cooling demand. advises NOT to change the room temperature hysteresis as it is set 1 (Yes)(default): closes when there is for an optimal use of the system.
Changeover settings related to the indoor temperature. Only applicable when Automatic is selected and the system is configured in room thermostat control with 1 leaving water temperature zone and quick heat emitters. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 45
When setting [4-03]=1/2/3, the booster heater operation can still be restricted by the booster heater allowance schedule. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
The purpose of this function is to 8.3.3 Heat source settings determine — based on the outdoor temperature — which heating source can/will provide the space heating, either the Daikin indoor Backup heater unit or an auxiliary boiler.
Page 48
Outdoor temperature CAUTION Make sure to observe all rules mentioned in application guideline 5 when bivalent operation function is enabled. Daikin shall not be held liable for any damage resulting from failure to observe this rule. Outdoor temperature INFORMATION CAUTION The combination of setting [4-03]=0/2 with bivalent The bottom plate heater is controlled via EKRP1HB.
When power returns after a power supply failure, the auto restart Defines the outdoor temperature which function reapplies the remote controller settings at the time of the below the domestic hot water will be power failure. Therefore, Daikin recommends to always enable the heated by booster heater only. function. [5-04]...
Page 50
(in A or kW) to which system power consumption will be limited when the corresponding digital input asks. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 51
2 (BUH): The backup heater is <4°C (pump will be activated for 10 minutes and disactivated after prioritized. power 10 minutes). Daikin shall NOT be held liable for any damage resulting consumption control is enabled, this functionality. the booster heater will be limited...
The stop valves (gas and liquid) on the outdoor unit are function. fully open. Result: Air purging is started and following screen will be shown. The air purge valve is open (at least 2 turns). Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Make sure the room temperature control, the leaving water temperature control and the domestic hot water control are turned OFF via the user interface. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
INFORMATION There is limited access to the menu structure. Only the following menu’s can be accessed: Information. Installer settings > Commissioning > UFH screed dryout Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
For this reason, descaling of the heat exchanger may be required at certain intervals. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
The air purge operation Press the reset button in the switch box. See "14.2 Components" on page 63 for the location of the reset button. EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Water circuit pressure is Please contact your dealer. too low. Backup heater overheated. Power reset required. Water pressure sensor problem. Please contact your dealer. Please contact your dealer. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply: Equipment not made by Daikin that can be combined with the product according to the instructions in the accompanying documentation. EHVH/X16...
Typical field installation is according to local and national regulations. For examples, refer t to installer reference guide. ONLY FOR EHVX MODELS 260L TANK 180L TANK 3D078519 Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 63
14 Technical data MIN. 500 3D078541 EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Tank thermistors (180 l/260 l) Domestic hot water tank drain valve Empties the full tank. Switch box Contains the main electronic and electrical parts of the indoor unit. Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Digital I/O PCB A4P (only for installations with solar kit or digital I/O PCB kit) Demand PCB for power limitation Terminal block X5M (low voltage) Main PCB A1P PCB fuse FU1 EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
* : optional On/OFF thermostat (wired) (*) : standard for *HV*, optional for *HB* On/OFF thermostat (wireless) # : field supply Ext. thermistor Heat pump convector 4D077028 page 1 Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 69
Only for demand PCB option only for EKBPHT* only if no EKBPHT* Options: bottom plate heater OR On/OFF output Only for digital I/O PCB option 4D077028 page 3 EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 70
Add LWT zone DHW pump NC valve 3 wire type (SPST) only for domestic Shut-off valve hot water option only for *04* and *08* 4D077028 page 4 Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 71
In case user interface is relocated 2x0.75 X5M: 1-2 A2P: P1-P2 user interface communication OPTIONAL PART Only for *KRCAL* 2 core 2x0.75 communication A2P: P1-P2 user interface 4D078494 EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 73
Digital I/O PCB Demand PCB Demand PCB Solar pump and control station Solar pump and control station Main LWT Main leaving water temperature On/OFF thermostat (wired) On/OFF thermostat (wired) EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
For *9W models: 15 l/min (12) Refer to operation range detail for diferences between *RHQ* and *RLQ* models 3D077571_A page 1 (13) DB/WB 7°C/6°C - LWC 45°C (DT = 5°C) Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 75
(**) : European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase. (***) : System impedance EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
In case such conditions ara expected, the *RLQ must be installed instead. These models contain countermeasures (insulation, heater sheet, ...) to prevent freeze up. 3TW60813-1A Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 77
–15 –20 –20 domestic hot water domestic hot water –25 –25 tank temperature (°C) tank temperature (°C) 40 45 55 60 40 45 INDOOR UNITS: CA-SERIES 3TW60813-2B EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
Page 78
Dry bulb temperature [°C] 1. Refer to psychometric chart for more information. 2. If condensation is expected, installation of EKHBDPCA2 - drainpan kit must be considered. 4D078990 Installer reference guide EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...
1) Selecting a flow outside the area of operation can cause damage or malfunctioning of the unit. See also minimum and maximum allowed waterflow range in the technical specifications. 2) Water quality must be according to EN directive EC 98/83 EC. 4D078833 EHVH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05...