Opening and closing the units ............................61 7.2.1 About opening the units..........................61 7.2.2 To open the outdoor unit..........................61 7.2.3 To close the outdoor unit..........................61 Installer reference guide ERLA03D + EHFH03S18D Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 3
To connect the electrical wiring to the outdoor unit ..................97 Connections to the indoor unit ............................98 9.3.1 To connect the main power supply........................ 101 ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 4
Symptom: The system is making gurgling noises after commissioning ............183 14.3.4 Symptom: The pump is blocked........................184 14.3.5 Symptom: The pump is making noise (cavitation)..................184 14.3.6 Symptom: The pressure relief valve opens....................185 Installer reference guide ERLA03D + EHFH03S18D Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 5
Piping diagram: Indoor unit ............................199 16.3 Wiring diagram: Outdoor unit ............................200 16.4 Wiring diagram: Indoor unit ............................202 17 Glossary 18 Field settings table ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
The original documentation is written in English. All other languages are translations. Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required).
Indicates a situation that could result in death or serious injury. WARNING: FLAMMABLE MATERIAL CAUTION Indicates a situation that could result in minor or moderate injury. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Piping installation What to do and know to install the piping of the system, including information on how to prepare for an installation ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 9
Note: There is also an installer settings table in the user reference guide. This table has to be filled in by the installer and handed over to the user. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. ONLY use accessories, optional equipment and spare parts made or approved by Daikin. WARNING Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
▪ Use a separate recovery system so that the unit's compressor does NOT have to operate. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 12
ONLY use tools exclusively for the refrigerant type used in the system, this to ensure pressure resistance and prevent foreign materials from entering into the system. ▪ Charge the liquid refrigerant as follows: ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, MUST be installed in the fixed wiring. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 14
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will damage the head and make proper tightening impossible. ▪ Over-tightening the terminal screws may break them. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 15
ON and OFF while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
The appliance shall be stored so as to prevent mechanical damage and in a well- ventilated room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater). ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 17
Specific installer safety instructions WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons. Opening and closing the units (see "7.2 Opening and closing the units" [ 61]) DANGER: RISK OF ELECTROCUTION Do NOT leave the unit unattended when the service cover is removed.
Page 18
WARNING ALWAYS use multicore cable for power supply cables. CAUTION Do NOT push or place redundant cable length into the unit. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 19
[A.4.4.5] is NOT interrupted by possible domestic hot water demand. Commissioning (see "11 Commissioning" [ 165]) WARNING Commissioning method MUST be in accordance with the instructions from this manual. See "11 Commissioning" [ 165]. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 20
NEVER shunt safety devices or change their values to a value other than the factory default setting. If you are unable to find the cause of the problem, call your dealer. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 21
▪ Use a separate recovery system so that the unit's compressor does NOT have to operate. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
4.1.1 To unpack the outdoor unit 4.1.2 To handle the outdoor unit CAUTION To avoid injury, do NOT touch the air inlet or aluminium fins of the unit. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Drain plug (located on the bottom of the packing case) d Energy label e Fluorinated greenhouse gases label 4.2 Indoor unit 4.2.1 To unpack the indoor unit 8× ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Handles at the back of the unit b Handles at the bottom of the unit. Carefully tilt the unit to the back so that the handles become visible. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
European split outdoor pair heat pump Low water temperature – ambient zone (see operation range) Refrigerant R32 Capacity class Model series Power supply 5.1.2 Identification label: Indoor unit Location ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Control close to the indoor unit (by the main user interface) ▪ Room thermostat functionality in the principal space to be heated (by the optional user interface) EKRUDAL1 contains following languages: English, French, Dutch, Italian. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 27
The remote indoor sensor can only be used in case the user interface is configured with room thermostat functionality. ▪ You can only connect either the remote indoor sensor or the remote outdoor sensor. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 28
LAN adapter for smartphone control (BRP069A62) You can install this LAN adapter to control the system via a smartphone app. For installation instructions, see the installation manual of the LAN adapter. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Setting up the domestic hot water tank ▪ Setting up the energy metering ▪ Setting up the power consumption control ▪ Setting up an external temperature sensor ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
[A.6.C] to 1. NOTICE A differential pressure bypass valve can be integrated in the system. Keep in mind that this valve might not be shown on the illustrations. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
For your daily needs, you can use preset values and schedules. To deviate from your daily needs, you can temporarily overrule the preset values and schedules, or use the holiday mode. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 32
OFF condition. ▪ Code: [C-05] Benefits ▪ Wireless. The Daikin external room thermostat is available in a wireless version. ▪ Efficiency. Although the external room thermostat only sends ON/OFF signals, it is specifically designed for the heat pump system. ▪ Comfort. In case of underfloor heating, the wireless external room thermostat prevents condensation on the floor during cooling operation by measuring the room humidity.
Page 33
▪ Cooling. The heat pump convector offers, besides heating capacity, also excellent cooling capacity. ▪ Efficiency. Optimal energy efficiency because of the interlink function. ▪ Stylish. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 34
The shut-off valve Configuration Setting Value Unit temperature control: 1 (Ext RT control): Unit operation is decided by the external thermostat. ▪ #: [A.2.1.7] ▪ Code: [C-07] ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
"9.2 Connections to the outdoor unit" [ 97] "9.3 Connections to the indoor unit" [ 98] ▪ The underfloor heating of the main room is directly connected to the indoor unit. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 36
The user interface connected to the indoor unit decides the space operation mode. Mind that the operation mode on each room thermostat must be set to match the indoor unit. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 37
(X2M/35 and X2M/30). The indoor unit will only supply leaving water temperature when there is an actual demand. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 38
A shut-off valve to prevent hot water supply when the room has no heating demand A shut-off valve to prevent condensation on the floor during cooling operation of the rooms with heat pump convectors. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
In cooling: 12°C In cooling mode, you can allow the underfloor heating (main zone) to provide refreshment (no real cooling), or NOT allow it. See setup below. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 40
▪ For more information about connecting the electrical wiring to the unit, see: "9.2 Connections to the outdoor unit" [ 97] "9.3 Connections to the indoor unit" [ 98] ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 41
▪ Other rooms external room thermostat functionality Number of water temperature zones: 1 (2 LWT zones): Main + additional ▪ #: [A.2.1.8] ▪ Code: [7-02] ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Bivalent operation is only possible for space heating, NOT for domestic hot water production. Domestic hot water is always produced by the DHW tank connected to the indoor unit. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 43
Make sure the auxiliary boiler and its integration in the system complies with applicable legislation. ▪ Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler system. ▪ Make sure the return water to the heat pump does NOT exceed 60°C. To do so: Set the desired water temperature via the auxiliary boiler controller to maximum 60°C.
Page 44
K1A Auxiliary relay for activation of indoor unit (field supply) K2A Auxiliary relay for activation of boiler (field supply) Indoor Indoor unit Auto Automatic Boiler Boiler ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Example: If the DHW consumption for 2 persons per day is as follows: ▪ 1 showers ▪ 1 bath ▪ 2 sink volumes Then the DHW consumption = (1×100 l)+(1×150 l)+(2×10 l)=270 l ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Thermodynamic cycle of the heat pump Electrical backup heater ▪ For more information about optimizing the energy consumption for producing domestic hot water, see "10 Configuration" [ 116]. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
The DHW pump is field-supplied and its installation is the responsibility of the installer. For the electrical wiring, see "9.3.6 To connect the domestic hot water pump" [ 108]. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
▪ Setup and configuration: No additional equipment needed. 6.5.2 Consumed energy You can use the following methods to determine the consumed energy: ▪ Calculating ▪ Measuring ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Single-phase outdoor unit Single-phase ▪ Backup heater supplied from a single- phase grid (i.e. the backup heater model is *3V connected to a single- phase grid) ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Power meter 2: Measures the rest (i.e. indoor unit and backup heater). Setup ▪ Connect power meter 1 to X5M/5 and X5M/6. ▪ Connect power meter 2 to X5M/3 and X5M/4. "9.3.5 To connect the electricity meters" [ 107]. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Power input t Time DI Digital input (power limitation level) a Power limitation active b Actual power input Setup and configuration ▪ No additional equipment needed. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
6.6.2 Power limitation activated by digital inputs Power limitation is also useful in combination with an energy management system. The power or current of the entire Daikin system is limited dynamically by digital inputs (maximum four steps). Each power limitation level is set via the user interface by limiting one of the following: ▪...
Produced heat Consumed energy A Outdoor unit B Backup heater a Limited outdoor unit operation b Full outdoor unit operation c Backup heater step 1 turned ON ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
To protect the outdoor unit, the internal sensor of the outdoor unit is always used. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
(example: open flames, an operating gas appliance or an operating electric heater). WARNING DO NOT reuse refrigerant piping that has been used with any other refrigerant. Replace the refrigerant pipes or clean thoroughly. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
It is recommended to install a baffle plate when the air outlet is exposed to wind. It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 57
If the outdoor unit is exposed to direct sea winds, install a windbreaker. ▪ Height of windbreaker≥1.5×height of outdoor unit ▪ Mind the service space requirements when installing the windbreaker. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
([8-0E]) field setting. This setting can also be changed via the menu structure. See the installation manual of the indoor unit for how to change the setting. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Maximum height difference between indoor unit and outdoor 20 m unit Refrigerant piping length is the one-way length of liquid piping. ▪ Mind the following spacing installation guidelines: ≥500 ≥600 (mm) ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 60
(example: open flames, an operating gas appliance or an operating electric heater). WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons. NOTICE ▪...
DANGER: RISK OF BURNING/SCALDING 1× 7.2.3 To close the outdoor unit NOTICE When closing the outdoor unit cover, make sure that the tightening torque does NOT exceed 1.3 N•m. 1× ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
1 Remove the top panel. 5× 2 Remove the upper front panel. Open the hinges at the top and slide the top panel upwards. 3 Remove the switch box cover. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 63
▪ When you need access to the high voltage switch box 2× 5 If you need access to the high voltage components, remove the high voltage switch box cover. 4× ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
5 Reinstall the front panel. 6 Reinstall the upper front panel. NOTICE When closing the indoor unit cover, make sure that the tightening torque does NOT exceed 4.1 N•m. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Fix the unit securely by means of foundation bolts in accordance with the foundation drawing. Prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field supply). ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
If you install the unit on a frame, install a waterproof plate within 150 mm of the bottom side of the unit in order to prevent water from getting into the unit and to avoid drain water dripping (see the following figure). ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cables from scratching the paint (field supply). 4 Attach the ends of the cables. 5 Tighten the cables. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
4 Adjust the height of the leveling feet to compensate for floor irregularities. The maximum allowed deviation is 1°. ≤1° NOTICE Do NOT tilt the unit forwards: 1° 1° 0° ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
It is recommended to use a tundish to collect the water. Option 1: Through the left side panel 3× Option 2: Through the right side panel 3× ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Gas pipe insulation c Interconnection cable d Field wiring (if applicable) e Liquid pipe f Liquid pipe insulation g Finishing tape 2 Install the service cover. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Connecting the refrigerant piping involves: ▪ Connecting the refrigerant piping to the outdoor unit ▪ Connecting the refrigerant piping to the indoor unit ▪ Insulating the refrigerant piping ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Use caution when passing copper tubes through walls (see figure below). Unit Installation period Protection method Outdoor unit >1 month Pinch the pipe <1 month Pinch or tape the pipe Indoor unit Regardless of the period ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
1 Cut the pipe end with a pipe cutter. 2 Remove burrs with the cut surface facing down so that the chips do NOT enter the pipe. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
1 Remove the stop valve cover. 2 Insert a hexagon wrench (liquid side: 4 mm, gas side: 4 mm) into the valve stem and turn the valve stem: Counterclockwise to open ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
8.3.2 Precautions when checking the refrigerant piping INFORMATION Also read the precautions and requirements in the following chapters: ▪ "2 General safety precautions" [ 10] ▪ "8.1 Preparing refrigerant piping" [ 71] ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
200 kPa (2 bar). It is recommended to pressurize to 3000 kPa (30 bar) in order to detect small leaks. 2 Check for leaks by applying the bubble test solution to all connections. 3 Discharge all nitrogen gas. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
NOT increase. This might be caused by e.g. the closed state of the expansion valve in the outdoor unit circuit, but does NOT present any problem for correct operation of the unit. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
8.4.3 To determine the complete recharge amount INFORMATION If a complete recharge is necessary, the total refrigerant charge is equal to the factory refrigerant charge (see unit name plate). ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Deformation of the piping can cause malfunctioning of the unit. ▪ Connecting piping – Tools. Only use appropriate tooling to handle brass, which is a soft material. If NOT, pipes will get damaged. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 83
Water temperature. All installed piping and piping accessories (valve, connections,…) MUST withstand the following temperatures: INFORMATION The following figure is an example and may NOT completely match your system layout ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 84
▪ Hygienic measures. The installation must be in compliance with the applicable legislation and may require additional hygienic installation measures. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Differential pressure bypass valve (field supply; recommended) c Shut-off valve Maximum water volume Use the following graph to determine the maximum water volume for the calculated pre-pressure. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 86
This minimum flow rate is required during defrost operation. For this purpose, it is recommended to use a differential pressure bypass valve (field supply). Minimum required flow rate 12 l/min ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Because the total water volume (250 l) is more than the default water volume (200 l), the pre-pressure must be decreased. ▪ The required pre-pressure is: Pg = (0.3+(H/10)) bar = (0.3+(0/10)) bar = 0.3 bar ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
1 Connect the space heating water in and out pipes to the indoor unit. 2 Connect the domestic hot water in and out pipes to the indoor unit. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 89
A pressure relief valve (field supply) with an opening pressure of maximum 10 bar (=1 MPa) must be installed on the domestic cold water inlet connection in accordance with the applicable legislation. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
3 Route the recirculation piping through the grommet and connect it to the recirculation connector. 4 Reattach the top panel. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Typical workflow Connecting the electrical wiring typically consists of the following stages: ▪ "9.2 Connections to the outdoor unit" [ 97] ▪ "9.3 Connections to the indoor unit" [ 98] ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
We recommend using solid (single-core) wires. If stranded wires are used, slighly twist the strands to consolidate the end of the conductor for either direct use in the terminal clamp or insertion in a round crimp-style terminal. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 94
Installation method Single-core wire AA´ A´ Stranded conductor wire twisted to "solid-like" connection a Curled wire (single-core or twisted stranded conductor wire) b Screw c Flat washer ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
When the equipment is connected to such preferential kWh rate power supply, the electricity company is allowed to: ▪ interrupt power supply to the equipment for certain periods of time; ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
5 Normal kWh rate power supply (to power the indoor unit PCB in the event of power supply interruption of the preferential kWh rate power supply) ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
An excessive strip length may cause electrical shock or leakage 3 Open the wire clamp. 4 Connect the interconnection cable and power supply as follows: ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Changeover to external "9.3.9 To connect the changeover to external heat source control heat source" [ 111]. Power consumption digital "9.3.10 To connect the power consumption inputs digital inputs" [ 112]. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 99
Installation manual of the remote outdoor sensor ▪ Addendum book for optional equipment Wires: 2×0.75 mm² [A.2.2.B]=1 (External sensor=Outdoor sensor) [A.6.5] Ext amb. sensor offset [A.6.4] Averaging time ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 100
(field supply, see addendum book for optional equipment) LAN adapter – System requirements The requirements posed on the Daikin Altherma system depend on the LAN adapter application/system layout (app control): ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C –...
In case of normal kWh rate power supply Interconnection cable Wires: (3+GND)×1.5 mm² (= main power supply) — 1 2 3 1 2 3 X11YB X11YA X11Y a Interconnection cable (=main power supply) ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 102
Interconnection cable (=main power supply) b Normal kWh rate power supply c Preferential power supply contact 3 Fix the cables with cable ties to the cable tie mountings. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Z less than or equal to Z Connect the power supply of the backup heater as follows: ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Maximum length: 200 m [A.2.1.7] Unit control method [A.2.1.B] User interface location [A.3.2.2] Room temp. offset 1 Open the following (see "7.2.4 To open the indoor unit" [ 62]): ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 105
4 Fix the wallplate of the user interface to the wall. 5 Connect as shown in A, B, C or D: A From the rear B From the left 1× 1× ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
2 Connect the valve control cable to the appropriate terminals as shown in the illustration below. NOTICE Wiring is different for a NC (normally closed) valve and a NO (normally open) valve. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
1 Top panel 2 Upper front panel 3 Upper switch box cover 2 Connect the electricity meters cable to the appropriate terminals as shown in the illustration below. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
2 Upper front panel 3 Upper switch box cover 2 Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below. Wires connected to the alarm output Wire between X2M and A4P Installation of EKRP1HBAA is required. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
2 Connect the space cooling/heating ON/OFF output cable to the appropriate terminals as shown in the illustration below. Wires connected to the space cooling/heating ON/OFF output Wire between X2M and A4P Installation of EKRP1HBAA is required. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
2 Upper front panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
2 Upper front panel 3 Upper switch box cover 2 Connect the power consumption digital inputs cable to the appropriate terminals as shown in the illustration below. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
2 Upper front panel 3 Upper switch box cover 2 Connect the safety thermostat (normally closed) cable to the appropriate terminals as shown in the illustration below. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
9.4 After connecting the electrical wiring to the indoor unit To prevent water ingress to the switch box, seal the low voltage wiring intake using the sealing tape (delivered as accessory). ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 115
Electrical installation Without low voltage cables With low voltage cables ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Configuring via the PC You can prepare the configuration off-site on PC and configurator afterwards upload the configuration to the system with the PC configurator. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
The Installer permission level switches automatically back to End user in the following cases: ▪ If you press again for more than 4 seconds, or ▪ If you do NOT press any button for more than 1 hour ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
5 Repeat previous steps if you have to modify other settings. 6 Push to confirm the modification of the parameter. 7 At installer settings menu, press to confirm the settings. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Copy the data of the other user interface to this user interface. 5 Confirm to proceed. Start copy Are you sure you want to start the copy operation? Cancel Confirm Adjust ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
3 Set the system layout settings: Standard, Options, Capacities. For more details, see "10.2 Basic configuration" [ 121]. System layout Standard Options Capacities Confirm layout Select Scroll 4 After configuration, select Confirm layout and press ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
3 Pay special attention to the position of the plug! 10.2 Basic configuration 10.2.1 Quick wizard: Language / time and date Code Description [A.1] Language Time and date ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
In room, ▪ acts as room thermostat if RT control is selected. In room: This user interface acts as room thermostat if RT control is selected. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 123
Additional LWT zone b Main LWT zone c Mixing station ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 124
Example: Using a room thermostat creates a thermo ON/OFF condition. When there is no demand, the pump is OFF. Remark: Request is NOT available in leaving water temperature control. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
The backup heater will also be used for domestic hot water heating. Remark: The domestic hot water tank type is read only and CANNOT be changed. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 126
(X2M/1 and 2). Select this value in case of connection with the wired (EKRTWA) wireless (EKRTR1 EKRTRB) room thermostat. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 127
During the bivalent operation, the heat pump is turned OFF. Set this value in case an auxililary boiler is used. See "6 Application guidelines" [ 29]. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
▪ 2 (Scheduled only): The domestic hot water tank can ONLY be heated according to a schedule. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Thus, the unit does not have to wait for feedback by the thermostat to increase or decrease the ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
To use the weather-dependent curve, you need to define the correct setpoint mode: Go to setpoint mode … Set the setpoint mode to … Main zone – Heating/Cooling ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
The purpose of this setting is to prevent selecting a wrong (i.e. too hot or too cold) leaving water temperature. Therefore the available desired heating temperature range and desired cooling temperature range can be configured. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 137
(= the leaving water temperature zone with the highest leaving water temperature in heating operation and the lowest leaving water temperature in cooling operation) [A.3.1.2.2.2] [9-06] Maximum temp (heating) 37°C~60°C ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 139
Room temp. range [A.3.2.1.2] [3-06] Maximum temp (heating) 18°C~30°C [A.3.2.1.1] [3-07] Minimum temp (heating) 12°C~30°C [A.3.2.1.4] [3-08] Maximum temp (cooling) 25°C~35°C [A.3.2.1.3] [3-09] Minimum temp (cooling) 15°C~25°C ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 140
Room frost protection prevents the room from getting too cold. This setting behaves differently depending on the set unit control method ([C‑07]). Perform actions according to the table below: ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 141
If Emergency is set to Manual ([A.6.C]=0), and the unit is triggered to start emergency operation, the user interface will ask confirmation before starting. Room frost protection is active even if the user does NOT confirm emergency operation. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 142
When the leaving water temperature home page is ON and the operation mode is "cooling", then there is no protection. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 143
The shut-off valve: ▪ 0 (No): is NOT influenced by changing the space operation mode to cooling. ▪ 1 (Yes)(default): closes when the space operation mode is cooling. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 144
(thus 21°C) and the desired cooling temperature subtracted by the offset value (thus 20°C). ▪ Guard timer to prevent too frequent changing from heating to cooling and vice versa. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Preset values make it easy to use the same value in the schedule. If you later want to change the value, you only have to do it in 1 place (see also operation manual and/or user reference guide). Storage comfort ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 146
(according to the weather-dependent curve). During weather dependent operation, the end-user cannot adjust the desired tank temperature on the user interface. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 147
The temperature difference determining the heat pump ON temperature. 2°C~40°C [6-01] The temperature difference determining the heat pump OFF temperature. 0°C~10°C Example: setpoint (T )>maximum heat pump temperature–[6‑01] ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 148
Timers for simultaneous request space and domestic hot water operation Code Description [8-00] Minimum running timer for domestic hot water operation. Do not change. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 149
The disinfection function settings MUST be configured by the installer according to the applicable legislation. Code Description [A.4.4.1] [2‑01] Disinfection ▪ 0: No ▪ 1: Yes ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 150
[A.4.4.5] is NOT interrupted by possible domestic hot water demand. NOTICE Disinfection mode. Even if you turn OFF domestic hot water operation via the DHW tank temperature home page (Tank), disinfection mode will remain active. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
▪ When auto emergency is set to Automatic and a heat pump failure occurs, the boiler will automatically take over the heat load. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 152
If bivalent is enabled: When the outdoor temperature drops below the bivalent ON, the space heating by the indoor unit stops automatically and the permission signal for the auxiliary boiler is active. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 153
OFF temperature. 2°C~10°C Permission signal X1–X2 [C-04] [C-03] Outdoor temperature [C-03] Bivalent ON temperature (fixed) a Auxiliary boiler active b Auxiliary boiler inactive ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
[5‑03] Space heating priority temperature. Defines the outdoor temperature which below the backup heater will assist during domestic hot water heating. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 155
The preferential kWh rate power supply contact is connected to the same terminals (X5M/9+10) as the safety thermostat. Thus, the system can have EITHER preferential kWh rate power supply OR a safety thermostat. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 156
[D-00] back to 0, as the system does not have a booster heater. Only set [D-00] to the values in the table below: [D‑00] Backup heater Compressor Forced OFF Forced OFF Allowed ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 157
[A.6.3.2] [4-09] Type: ▪ 0 (Current): The limitation values are set in ▪ 1 (Power)(default): The limitation values are set in kW. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 158
The outdoor temperature is averaged over the selected time period. Code Description [A.6.4] [1-0A] Outdoor average timer: ▪ 0: No averaging ▪ 1: 12 hours ▪ 2: 24 hours ▪ 3: 48 hours ▪ 4: 72 hours ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 159
[4‑02] or if the outdoor temperature drops below the value set by [F‑01]. When the pump operation is enabled, the pump operation is possible at all outdoor temperatures. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 160
The maximum values depend on the unit type: [9-0D]=0 [9-0D]=1/5 a (kPa) a (kPa) b (l/min) b (l/min) [9-0D]=2/6 [9-0D]=3/7 a (kPa) a (kPa) b (l/min) b (l/min) ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 161
Configuration [9-0D]=4/8 a (kPa) b (l/min) a External static pressure b Water flow rate ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Tank temperature Quiet level [7.7] Set weather dependent Main [7.7.1] Main Additional Set weather-dependent heating Set weather-dependent cooling [7.7.2] Additional Set weather-dependent heating Set weather-dependent cooling ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Disable protections Amp. value kW value [A.7] Commissioning Amp. limits for DI Test run kW limits for DI UFH screed dryout Priority Air purge Actuator test run ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 164
Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/ invisible. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Performing a test run for the system. If necessary, performing a test run for one or more actuators. If necessary, performing an underfloor heating screed dryout. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
There are NO refrigerant leaks. The refrigerant pipes (gas and liquid) are thermally insulated. The correct pipe size is installed and the pipes are properly insulated. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
> Information > Sensor information > Flow rate to check the flow rate. During pump test run operation, the unit can operate below this minimum required flow rate. Minimum required flow rate 12 l/min ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
> Commissioning > Air purge > Start air purge and press to start the air purge function. Result: The manual air purge starts and the following screen appears. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
"To set the user permission level Installer" [ 117]. 2 Go to [A.7.4]: > Installer settings > Commissioning > Actuator test run. 3 Select an actuator and press . Example: Pump. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
For the underfloor heating screed dryout to be able to start, make sure the following settings are met: ▪ [4‑00]=1 ▪ [C‑02]=0 ▪ [D‑01]=0 ▪ [4‑08]=0 ▪ [4‑01]≠1 ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 171
Result: The underfloor heating screed dryout starts and following screen will be shown. It stops automatically when done. To stop it manually, press , select OK and press ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 172
> Commissioning > UFH screed dryout > Dryout status > Stopped at and followed by the last executed step. 6 Modify and restart the execution of the program. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Please note that some sections of the electric component box are hot. ▪ Make sure you do NOT touch a conductive section. ▪ Do NOT rinse the unit. This may cause electric shocks or fire. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
(bottle, sink...). 4 Open the drain valve for a couple of seconds (c). Result: Water and dirt will come out. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 176
▪ Check if nothing blocks the water in the valve or in between piping. The water flow coming from the relief valve must be high enough. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Prerequisite: Open all the hot water tapping points to allow air to enter the system. 1 Remove the top panel, the upper front panel and the lower front panel. 2 Lower the switch box. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Collect the drained water in a bottle, sink,… using the installed drain hose. 7 Remove the 2 clips that fix the water filter. a Clip ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
4 Install the cleaned rolled‑up filter and strainer in the water filter housing. INFORMATION Correctly install the strainer in the magnetic filter/dirt separator housing using the protrusions. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Make sure to open the valve (if equipped) towards the expansion vessel, otherwise the overpressure will be generated. 5 Open the stop valves and add water to the water circuit if needed. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring. 14.2 Precautions when troubleshooting DANGER: RISK OF ELECTROCUTION DANGER: RISK OF BURNING/SCALDING ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Make sure that the water volume in the too low installation is above the minimum required value (see "8.5.3 To check the water volume and flow rate" [ 85]). ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Various malfunctions. Check if is displayed on the home pages of the user interface. You can press to display more information about the malfunction. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Purge air manually (see "To perform a manual air purge" [ 168]) or use the automatic air purge function (see "To perform an automatic air purge" [ 169]). ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
▪ If the water keeps running out of the unit, close both the water inlet and outlet shut-off valves first and then contact your dealer. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
This chapter gives you an overview of all possible error codes and their descriptions as they appear on the user interface. For detailed troubleshooting of each error, see the service manual. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
OU: Cool/heat switchover problem. Please contact your dealer. OU: Voltage/current sensor problem. Please contact your dealer. OU: Malfunction of high pressure switch (HPS) Please contact your dealer. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 189
Please contact your dealer. OU: Electrical box temperature rise problem. Please contact your dealer. OU: Malfunction of inverter radiating fin temperature rise. Please contact your dealer. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 190
Water flow problem during cooling/ defrost. Manual reset. Check the plate heat exchanger. Water flow problem. Pump deblocking active Returning water temperature sensor problem. Please contact your dealer. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 191
Backup heater overheated. Power reset required. Please contact your dealer. Tank disinfection function completed correctly. Too long DHW heat-up time required. Flow sensor/switch malfunction. Please contact your dealer. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 192
Please contact your dealer. Water pressure sensor abnormality. Refrigerant pressure sensor abnormality. Under floor heating screed dryout function not completed correctly. Indoor/outdoor unit communication problem. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 193
7H‑01. After some time, this error will reset automatically and the unit will resume operation. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 194
Error AJ-03 is reset automatically from the moment there is a normal tank heat-up. INFORMATION The user interface will display how to reset an error code. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Pump down operation will extract all refrigerant from the system into the outdoor unit (compressor module). 1 Remove the valve cap from the liquid stop valve and the gas stop valve. ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 196
5 After ±5 minutes, close the gas stop valve, and stop the pump down operation by pressing on the user interface. a Liquid stop valve b Closing direction c Hexagonal wrench d Valve cap e Gas stop valve ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
This unit is a heating only model. Therefore, all references to cooling in this document are NOT applicable. A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required).
R5T, R8T Tank j Air purge k Drain valve Connections: l Pump Screw connection m Flow sensor Flare connection n Backup heater Quick coupling Brazed connection ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
(3) Legend Live Neutral Protective earth Earth Field wiring Circuit breaker Connection Terminal strip Connector Terminal Black White Brown Green Yellow Orange Blue Grey Printed circuit board ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 203
* External indoor or outdoor ambient thermistor # Preferential kWh rate power supply contact # Electrical meter pulse input 1 # Electrical meter pulse input 2 ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 204
230 V AC supplied by PCB 230 V AC supplied by PCB Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 205
Only for heat pump convector Only for heat pump convector Only for wired On/OFF thermostat Only for wired ON/OFF thermostat Only for wireless On/OFF thermostat Only for wireless ON/OFF thermostat ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Page 206
2 core 2×0.75 A13P: P1-P2 LAN adapter communication Only for EKRUDAL1 (delivered with the unit as accessory) 2 core 2×0.75 A10P: P1-P2 Main user interface communication 4D125237A ERLA03D + EHFH03S18D Installer reference guide Daikin Altherma 3 R F 4P596806-1C – 2022.09...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Field settings table Applicable units EHFH03S18D▲3V▼ Notes (*1) Only applicable for models where cooling is possible (*2) EHFH03S18D▲3V▼ ▲ = A, B, C, …, Z ▼ = , , 1, 2, 3, …, 9 4P596814-1B - 2022.09...
Page 209
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value User settings └─ Preset values └─ Room temperature 7.4.1.1 Comfort (heating) [3-07]~[3-06], step: A.3.2.4 22°C 7.4.1.2 Eco (heating) [3-07]~[3-06], step: A.3.2.4 18°C 7.4.1.3 Comfort (cooling)
Page 210
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value └─ Space operation └─ LWT settings └────────────────── Main A.3.1.1.1 LWT setpoint mode 0: Fixed 1: Weather dep. 2: Fixed / scheduled 3: WD / scheduled A.3.1.1.2.1 [9-01]...
Page 211
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value └─ Pwr consumpt. Control A.6.3.1 [4-08] Mode 0: No limitation 1: Continuous 2: Digital inputs A.6.3.2 [4-09] Type 0: Current 1: Power A.6.3.3 [5-05]...
Page 212
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [2-09] Adjust the offset on the measured room temperature -5~5°C, step: 0,5°C 0°C [2-0A] Adjust the offset on the measured room temperature -5~5°C, step: 0,5°C 0°C [2-0B]...
Page 213
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [6-0E] What is the maximum temperature setpoint? 40~60°C, step: 1°C 60°C [7-00] [7-01] [7-02] How many leaving water temperature zones are there? 0: 1 LWT zone 1: 2 LWT zones [7-03]...
Page 214
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [D-02] Which type of DHW pump is installed? 0: No 1: Secondary rtrn 2: Disinf. Shunt [D-03] Leaving water temperature compensation around 0°C. 0: No 1: increase 2°C, span 4°C 2: increase 4°C, span 4°C...
Page 216
4P596806-1C 2022.09 Verantwortung für Energie und Umwelt...
Need help?
Do you have a question about the Altherma EHFH03S18D 3V Series and is the answer not in the manual?
Questions and answers