Daikin Altherma ERLQ004-006-008CA Reference Manual page 103

Low temperature split
Hide thumbs Also See for Altherma ERLQ004-006-008CA:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
A.8
[6-08]
What is the hysteresis to be used in reheat mode?
A.8
[6-09]
--
A.8
[6-0A]
What is the desired comfort storage temperature?
A.8
[6-0B]
What is the desired eco storage temperature?
A.8
[6-0C]
What is the desired reheat temperature?
A.8
[6-0D]
What is the desired DHW production type?
A.8
[6-0E]
What is the maximum temperature setpoint?
A.8
[7-00]
--
A.8
[7-01]
--
A.8
[7-02]
How many leaving water temperature zones are there?
A.8
[7-03]
--
A.8
[7-04]
--
A.8
[7-05]
Boiler efficiency
A.8
[8-00]
--
A.8
[8-01]
Maximum running time for domestic hot water operation.
A.8
[8-02]
Anti-recycling time.
A.8
[8-03]
--
A.8
[8-04]
Additional running time for the maximum running time.
A.8
[8-05]
Allow modulation of the LWT to control the room temp?
A.8
[8-06]
Leaving water temperature maximum modulation.
A.8
[8-07]
--
A.8
[8-08]
--
A.8
[8-09]
What is the desired comfort main LWT in heating?
A.8
[8-0A]
What is the desired eco main LWT in heating?
A.8
[8-0B]
--
A.8
[8-0C]
--
A.8
[8-0D]
--
A.8
[9-00]
What is the maximum desired LWT for main zone in heating?
A.8
[9-01]
What is the mimimum desired LWT for main zone in heating?
A.8
[9-02]
--
A.8
[9-03]
--
A.8
[9-04]
Leaving water temperature overshoot temperature.
A.8
[9-05]
What is the mimimum desired LWT for add. zone in heating?
A.8
[9-06]
What is the maximum desired LWT for add. zone in heating?
A.8
[9-07]
--
A.8
[9-08]
--
A.8
[9-09]
What is the desired delta T in heating?
A.8
[9-0A]
--
A.8
[9-0B]
What emitter type is connected to the main LWT zone?
A.8
[9-0C]
Room temperature hysteresis.
A.8
[9-0D]
Pump speed limitation
A.8
[9-0E]
--
A.8
[A-00]
--
A.8
[A-01]
--
A.8
[A-02]
--
A.8
[A-03]
--
A.8
[A-04]
--
A.8
[B-00]
--
A.8
[B-01]
--
A.8
[B-02]
--
A.8
[B-03]
--
A.8
[B-04]
--
A.8
[C-00]
Domestic heating water priority.
A.8
[C-01]
--
A.8
[C-02]
Is an external backup heat source connected?
A.8
[C-03]
Bivalent activation temperature.
A.8
[C-04]
Bivalent hysteresis temperature.
A.8
[C-05]
What is the thermo request contact type for the main zone?
A.8
[C-06]
What is the thermo request contact type for the add. zone?
A.8
[C-07]
What is the unit control method in space operation?
(*5) *04/08*
(*6) *16*
Range, step
Default value
R/W
2~20°C, step: 1°C
10°C
0
R/W
30~[6-0E]°C, step: 1°C
60°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
0: Reheat only
1: Reheat + sched.
2: Scheduled only
R/W
40~60°C, step: 1°C
60°C
R/W
0
R/W
2
R/W
0: 1 LWT zone
1: 2 LWT zones
2,5
0
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
1 min
R/W
5~95 min, step: 5 min
30 min
R/W
0~10 hour, step: 0,5 hour
0,5 hour
R/W
50
R/W
0~95 min, step: 5 min
95 min
R/W
0: No
1: Yes
R/W
0~10°C, step: 1°C
3°C
R/W
18
R/W
20
R/W
[9-01]~[9-00], step: 1°C
35°C
R/W
[9-01]~[9-00], step: 1°C
33°C
13
10
16
R/W
37~55, step: 1°C
55°C
R/W
15~37°C, step: 1°C
25°C
R/W
22
R/W
5
R/W
1~4°C, step: 1°C
1°C
R/W
15~37°C, step: 1°C
25°C
R/W
37~55, step: 1°C
55°C
R/W
5
R/W
22
R/W
3~10°C, step: 1°C
5°C
R/W
5
R/W
0: Quick
1: Slow
R/W
1~6°C, step: 0,5°C
1 °C
R/W
0~8, step:1
0 : 100%
1~4 : 80~50%
5~8 : 80~50%
6
6
0
0 (*5)
3 (*6)
0 (*5)
1 (*6)
0
0
0
0
0
0
0
R/O
0~1
1: Heat pump priority
0
R/W
0~3
0: No
1: Bivalent
R/W
-25~25°C, step: 1°C
0°C
R/W
2~10°C, step: 1°C
3°C
R/W
1: Thermo ON/OFF
2: C/H request
R/W
0: -
1: Thermo ON/OFF
2: C/H request
R/W
0: LWT control
1: Ext RT control
2: RT control
7/8
Installer setting at variance with
default value
Date
Value
4P401673-1 - 2015.04

Advertisement

Table of Contents
loading

This manual is also suitable for:

Altherma ehvz08s18cbAltherma ehvz04s18cb

Table of Contents