Using Proportional Control

If parameter Pn000.1 is set to 0 or 1 as shown below, input signal /P-CON serves as
a PI/P control changeover switch.
PI control: Proportional/integral control.
P control: Proportional control.
Parameter
Pn000.1
Control Method Selection
Pn000.1
Setting
Speed
0
Control
Position
1
Control
Methods for Using Proportional Control
Proportional control can be used in the following two ways.
When operation is performed by sending speed references from the host control-
ler to the servo amplifier, the host controller can selectively use P control mode
for particular conditions only. This method can suppress overshooting and
shorten setting time. Refer to 6.2.5 Using Mode Switch for particular conditions.
If PI control mode is used when the speed reference has a reference offset, the
motor may rotate at a very slow speed and fail to stop even if 0 is specified as a
speed reference. In this case, use P control mode to stop the motor.
Signal
Default Setting: 0
Usual speed control or position
control is selected.
Input signal /P-CON (CN1-41) is used
to select PI control or P control.
CN1-41
PI control
is open.
CN1-41
P control
is 0V
Setting
(%)
Control Mode
P or PI
control
selection
6 - 13
Chapter 6: Servo Adjustment
Application
Speed Control,
Position Control
Servo amplifier
/P-CON
CN1-41