Advertisement

P007 Span (process full level)
Sets the range to be measured (referenced from Empty) in units selected at P005.
Range
Values
Default
Enter the distance between Empty (process empty level) and Span (process full level), in
units set in P005. Span can be set at any distance above Empty level.
Notes:
• Setting P006 will reset Span, if it has not previously been set to a different value.
• The default setting for Span is based on Operation (P001) and Empty (P006). Span is
set to Empty minus 110% of Blanking
(P001 = 3). In this case, Span is set to Empty distance.
• Always prevent the monitored surface from approaching within 0.3 m (1 ft) of the
reference point, as this is the minimum distance detectable.
P010 Language
Selects the language used for the auxiliary reading on the display.
Values
If a language is selected, parameter titles for the parameters P000 to P010 are displayed.
(See the table on page 25 for the titles displayed.)
1.
Near Blanking
See
7ML19985HR02
0.0000 to 20.00 (m)
19.56 (see note below)
0
*
Numeric / None
1
English
2
German
3
French
4
Spanish
on page 93 for details.
SITRANS Probe LR – INSTRUCTION MANUAL
1
distance, unless Operation is set to Distance
1
Page 41