Security

The Lock parameter, P000, secures SITRANS Probe LR against changes via the handheld
programmer. To enable programming, set P000 to the Unlocked Value stored in P069.
To disable programming, enter a different value.
Note:
• A remote master can still change configuration, if P799 is set to allow this.

Handheld programmer

For detailed instructions on using the handheld programmer, see the next page.
Note:
For direct access to SITRANS Probe LR, point the handheld programmer at the display
from a maximum distance of 600 mm (2 ft), and press the keys.
Function
Keys
7ML19985HR02
Numeric and
Auxiliary keys
SITRANS Probe LR – INSTRUCTION MANUAL
handheld programmer
display
max. 600 mm
(2 ft)
Page 21