P007: Span - Siemens SITRANS L Series Operating Instructions Manual

Radar transmitters, probe with ma/hart
Hide thumbs Also See for SITRANS L Series:
Table of Contents

Advertisement

Note
P006 and P007 are interlinked: see notes attached to P007.
6.2.11.6

P007: Span

Set the range to be measured (P007: Span)
Value
Enter the distance between Empty (process empty level) and Span (process full level), in the
units set in P005. Span can be set at any distance above Empty level.
Note
• Setting P006 resets Span, if it has not previously been set to a different value.
• The default setting for Span is based on Operation (P001) and Empty (P006). Span is set
to Empty minus 110% of Blanking distance, unless Operation is set to distance (P001=3).
In this case, Span is set to Empty distance. Blanking distance is 0.3 m (1 ft), plus the
shield length (if any).
• Always prevent the monitored surface from approaching within 0.3 m (1 ft) of the
reference point, as this is the minimum distance detectable.
SITRANS Probe LR with mA/HART
Operating Instructions, 05/2019, A5E32337711-AC
Reference point
Span
Level setup
Level
Empty
Range
Default
0.0000 to 20.00
19.56 (see note below)
Commissioning
6.2 Local commissioning
37