Measurement

P911 mA Output Value (HART/mA only)
Access this parameter to display the current value of the mA output.
Values (HART)
1. Set P201 to 0 (manual).
2. Enter a test value.
P201 must be set to 0 to enable the test value to be entered at P911: be sure to
Note:
restore P201 to the previous setting after the test!
P920 Reading Measurement
P920 corresponds to the final reading after all programming is applied. It is a copy of one
of P921 to P924, depending on the setting for Operation (P001).
P920 Values
(read only)
P921 Material Measurement
Displays the distance between Empty/process empty level (P006) and the monitored
surface, in Units (P005) or percent of Span (P007).
Values (view only)
7ML19985HR02
Range
3.6 to 22.6 (mA)
4 mA in HART fixed current mode
*
Operation P001
Off
0
Level
1
Space
2
Distance
3
–99999 to 99999 (dimensional units, if volume has not been
Range:
selected)
Range
SITRANS Probe LR – INSTRUCTION MANUAL
Source Parameter for P920
– – – –
P921 if P050 = 0, otherwise P924
P922
P923
–99999 to 99999
Page 67