Lock (P069)
P069 Unlocked value
Stores the value to enter in Lock (P000) to unlock programming. If P000 is locked, P069
will not display the Unlocked value.
Values
Notes:
• Default setting for P000 is unlocked.
• After a new value has been stored at P069, that value will be recalled after a master
reset (P999).
• Consult your Siemens representative, if you have forgotten the unlocked value.
Failsafe (P070 to P073)
Factory settings are indicated by an asterisk (*) in the parameter tables, unless
Note:
explicitly described.
P070 Failsafe Timer
The last valid reading is maintained until the Failsafe timer expires. After the
Note:
timer expires, the reading is set based on P071.
Sets the time to elapse in minutes since the last valid reading, before Failsafe State
activates.
Values
7ML19985HR02
Range
Factory setting
----
Range
Default
SITRANS Probe LR – INSTRUCTION MANUAL
1 to 9999
1954
Display when P000 is locked
0.00 to 720 min.
100.0 (based on P003)
Page 47