Technical Data - YASKAWA VIPA System 300S Manual

Hide thumbs Also See for VIPA System 300S:
Table of Contents

Advertisement

Digital Output Modules
322-1HH00 - DO 16xRelay > Technical data

4.8.1 Technical data

Order no.
Type
SPEED-Bus
Current consumption/power loss
Current consumption from backplane bus
Power loss
Technical data digital outputs
Number of outputs
Cable length, shielded
Cable length, unshielded
Rated load voltage
Current consumption from load voltage L+ (without load)
Total current per group, horizontal configuration, 40°C
Total current per group, horizontal configuration, 60°C
Total current per group, vertical configuration
Output current at signal "1", rated value
Output delay of "0" to "1"
Output delay of "1" to "0"
Minimum load current
Lamp load
Parallel switching of outputs for redundant control of a load not possible
Parallel switching of outputs for increased power
Actuation of digital input
Switching frequency with resistive load
Switching frequency with inductive load
68
Maximum toggle capacity
Life Time
322-1HH00
SM 322
-
80 mA
4 W
16
1000 m
600 m
DC 30 V/ AC 230 V
-
8 A
8 A
8 A
5 A
10 ms
5 ms
-
6 W
not possible
ü
max. 0.33 Hz
max. 0.33 Hz
VIPA System 300S
HB140 | SM-DIO | | en | Rev. 16-43