General Data - YASKAWA VIPA 300S Manual

Hide thumbs Also See for VIPA 300S:
Table of Contents

Advertisement

Manual VIPA System 300S SPEED7

General data

Conformity and approval
Conformity
CE
Approval
UL
others
RoHS
Protection of persons and device protection
Type of protection
Electrical isolation
to the field bus
to the process level
Insulation resistance
Insulation voltage to reference earth
Inputs / outputs
Protective measures
Environmental conditions to EN 61131-2
Climatic
Storage / transport
Operation
Horizontal installation
Vertical installation
Air humidity
Pollution
Mechanical
Oscillation
Shock
Mounting conditions
Mounting place
Mounting position
EMC
Standard
Emitted
EN 61000-6-4
interference
Noise immunity
EN 61000-6-2
zone B
)
*
Due to the high-energetic single pulses with Surge an appropriate external protective circuit with
lightning protection elements like conductors for lightning and overvoltage is necessary.
HB140E - PS - RE_307-1FB70 - Rev. 13/43
All manuals and user guides at all-guides.com
Chapter 1 Assembly and installation guidelines
2006/95/EC
2004/108/EC
UL 508
2011/65/EU
-
-
-
EN 61131-2
-
-
EN 60068-2-14
EN 61131-2
EN 61131-2
EN 60068-2-30
EN 61131-2
EN 60068-2-6
EN 60068-2-27
-
-
EN 61000-4-2
EN 61000-4-3
EN 61000-4-6
EN 61000-4-4
EN 61000-4-5
Low-voltage directive
EMC directive
Approval for USA and Canada
Product is lead-free; Restriction of the use of
certain hazardous substances in electrical and
electronic equipment
IP20
electrically isolated
electrically isolated
-
AC / DC 50V, test voltage AC 500V
against short circuit
-25...+70°C
0...+60°C
0...+60°C
RH1 (without condensation, rel. humidity 10...95%)
Degree of pollution 2
1g, 9Hz ... 150Hz
15g, 11ms
In the control cabinet
Horizontal and vertical
Comment
Class A (Industrial area)
Industrial area
ESD
8kV at air discharge (degree of severity 3),
4kV at contact discharge (degree of severity 2)
HF irradiation (casing)
80MHz ... 1000MHz, 10V/m, 80% AM (1kHz)
1.4GHz ... 2.0GHz, 3V/m, 80% AM (1kHz)
2GHz ... 2.7GHz, 1V/m, 80% AM (1kHz)
HF conducted
150kHz ... 80MHz, 10V, 80% AM (1kHz)
Burst, degree of severity 3
Surge, installation class 3 *
)
1-11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vipa 307-1fb70Vipa ps 307s

Table of Contents