Technical Data - YASKAWA VIPA System 300S Manual

Hide thumbs Also See for VIPA System 300S:
Table of Contents

Advertisement

Chapter 2 Hardware description

Technical data

2-6
Order no.
Type
SPEED-Bus
Technical data power supply
Power supply (rated value)
Power supply (permitted range)
Reverse polarity protection
Current consumption (no-load operation)
Current consumption (rated value)
Inrush current
I²t
Max. current drain at backplane bus
Max. current drain load supply
Power loss
Status information, alarms, diagnostics
Status display
Interrupts
Process alarm
Diagnostic interrupt
Diagnostic functions
Diagnostics information read-out
Supply voltage display
Service Indicator
Group error display
Channel error display
Hardware configuration
Racks, max.
Modules per rack, max.
Number of digital modules, max.
Number of analog modules, max.
Communication
Fieldbus
Type of interface
Connector
Topology
Electrically isolated
Number of participants, max.
Node addresses
Transmission speed, min.
Transmission speed, max.
Address range inputs, max.
Address range outputs, max.
Number of TxPDOs, max.
Number of RxPDOs, max.
Housing
Material
Mounting
Mechanical data
Dimensions (WxHxD)
Weight
Environmental conditions
Operating temperature
Storage temperature
Certifications
UL certification
KC certification
Manual VIPA System 300S
353-1DP01
IM 353DP
-
DC 24 V
DC 20.4...28.8 V
70 mA
1 A
60 A
0.45 A²s
3.5 A
-
2.5 W
yes
yes, parameterizable
yes, parameterizable
yes, parameterizable
yes, parameterizable
possible
green LED
-
red LED
none
1
29
29
16
PROFIBUS-DP to EN 50170
RS485
Sub-D, 9-pin, female
Linear bus with bus termination
at both ends
125
1 - 99
9.6 kbit/s
12 Mbit/s
244 Byte
244 Byte
-
-
PPE
Rail System 300
40 x 125 x 120 mm
170 g
0 °C to 60 °C
-25 °C to 70 °C
Yes
Yes
HB140E - IM - RE_353-1DP01 - Rev. 14/47

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vipa im 353-1dp01

Table of Contents