Digital Output Modules
322-5FF00 - DO 8xAC 120/230V 2A > Parameterization

4.7.1 Parameterization

Overview
Parameterization by hard-
ware configuration
Parameters
Parameterization during
run time by means of
SFCs
Parameter Record set 1
62
CAUTION!
The outputs must be protected by a fast-acting 3.15A, AC 250V fuse.
When mounted in a hazardous area, the fuse may only be removed by a
tool.
There are the following possibilities for parameterization:
n
Parameterization by WinPLC7 from VIPA or by hardware configuration of Siemens
SIMATIC manager.
Parameterization during run time by means of SFCs
n
To be compatible to the Siemens SIMATIC manager the following steps are to be accom-
plished:
1.
Start the hardware configurator from Siemens.
2.
Create a new project.
3.
Configure your CPU.
4.
Link-up your System 300V modules in the plugged-in sequence starting with slot 4.
Here the digital output modules of VIPA are to be projected as digital output
modules of Siemens in accordance with the following rules:
VIPA 322-5FF00 to be configured as 6ES7 322-5FF00-0AB0
The digital output modules can be found at the hardware catalog at Simatic 300 >
SM-300.
5.
If needed parameterize the CPU respectively the modules. The parameter window
appears as soon as you double click on the according module. At this window the
according parameter can be changed.
6.
Save your project, switch the CPU to STOP and transfer your project to the CPU.
As soon as the CPU is switched to RUN the parameters are transferred to the con-
nected modules.
The following parameters can be adjusted at the digital output modules:
n
Reaction at CPU-STOP
n
Switch substitute value "1"
More description of the parameters may be found at the following pages.
If the module gets parameters, which are not supported by the module, for example a
current module is to be configured as a voltage module, these parameters are interpreted
as wrong parameters and an error is initialized. At the parameterization, a 4byte long
parameter area is set in the record set 1. Deploying the SFCs 56, 57 and the SFB 53, you
may alter parameters during run time and transfer them to the module.
Record set 1 (Byte 0 to 3):
VIPA System 300S
HB140 | SM-DIO | | en | Rev. 16-43