Technical Data - YASKAWA VIPA System 300S Manual

Hide thumbs Also See for VIPA System 300S:
Table of Contents

Advertisement

VIPA System 300S

3.3.1 Technical data

Order no.
Type
SPEED-Bus
Current consumption/power loss
Current consumption from backplane bus
Power loss
Technical data digital inputs
Number of inputs
Cable length, shielded
Cable length, unshielded
Rated load voltage
Current consumption from load voltage L+ (without load)
Rated value
Input voltage for signal "0"
Input voltage for signal "1"
Input voltage hysteresis
Frequency range
Input resistance
Input current for signal "1"
Connection of Two-Wire-BEROs possible
Max. permissible BERO quiescent current
Input delay of "0" to "1"
Input delay of "1" to "0"
Number of simultaneously utilizable inputs horizontal con-
figuration
Number of simultaneously utilizable inputs vertical configu-
ration
Input characteristic curve
Initial data size
Status information, alarms, diagnostics
Status display
Interrupts
Process alarm
Diagnostic interrupt
Diagnostic functions
Diagnostics information read-out
Supply voltage display
HB140 | SM-DIO | | en | Rev. 16-43
321-1FH00 - DI 16xAC120/230V > Technical data
321-1FH00
SM 321
-
35 mA
5 W
16
1000 m
600 m
AC 120/230 V
-
AC 120/230 V
AC 0...40 V
AC 79...264 V
-
47...63 Hz
-
7 mA
ü
1.5 mA
25 ms
25 ms
16
16
-
2 Byte
green LED per channel
no
no
no
no
none
none
Digital Input Modules
33

Advertisement

Table of Contents
loading