6.4.1 Technical data

Order no.
Type
SPEED-Bus
Current consumption/power loss
Current consumption from backplane bus
Power loss
Technical data digital outputs
Number of outputs
Cable length, shielded
Cable length, unshielded
Rated load voltage
Current consumption from load voltage L+ (without load)
Total current per group, horizontal configuration, 40°C
Total current per group, horizontal configuration, 60°C
Total current per group, vertical configuration
Output current at signal "1", rated value
Output delay of "0" to "1"
Output delay of "1" to "0"
Minimum load current
Lamp load
Parallel switching of outputs for redundant control of a load not possible
Parallel switching of outputs for increased power
Actuation of digital input
Switching frequency with resistive load
Switching frequency with inductive load
Switching frequency on lamp load
Internal limitation of inductive shut-off voltage
Short-circuit protection of output
Trigger level
Number of operating cycle of relay outputs
Switching capacity of contacts
Output data size
Status information, alarms, diagnostics
Status display
Interrupts
Process alarm
HB140 | SM-DIO | | en | Rev. 16-43
Digital Modules FAST - SPEED-Bus
322-1BH70 - DO 16xDC 24V 0.5A > Technical data
322-1BH70
SM 322S - SPEED-Bus
ü
390 mA
5 W
16
1000 m
600 m
DC 24 V
30 mA
4 A
4 A
4 A
0.5 A
6.12 µs
6.12 µs
-
5 W
not possible
ü
max. 100 kHz
max. 0.5 Hz
max. 10 Hz
L+ (-52 V)
yes, electronic
1 A
-
-
2 Byte
green LED per channel
no
no
105