VIPA System 300S
Order no.
Rated value
Input voltage for signal "0"
Input voltage for signal "1"
Input voltage hysteresis
Frequency range
Input resistance
Input current for signal "1"
Connection of Two-Wire-BEROs possible
Max. permissible BERO quiescent current
Input delay of "0" to "1"
Input delay of "1" to "0"
Number of simultaneously utilizable inputs horizontal con-
figuration
Number of simultaneously utilizable inputs vertical configu-
ration
Input characteristic curve
Initial data size
Status information, alarms, diagnostics
Status display
Interrupts
Process alarm
Diagnostic interrupt
Diagnostic functions
Diagnostics information read-out
Supply voltage display
Group error display
Channel error display
Isolation
Between channels
Between channels of groups to
Between channels and backplane bus
Insulation tested with
Datasizes
Input bytes
Output bytes
Parameter bytes
Diagnostic bytes
HB140 | SM-DIO | | en | Rev. 16-43
Digital Modules FAST - SPEED-Bus
321-1BH70 - DI 16xDC 24V > Technical data
321-1BH70
DC 24 V
DC 0...5 V
DC 15...28.8 V
-
-
-
7 mA
ü
1.5 mA
parameterizable 2.56µs - 40ms
parameterizable 2.56µs - 40ms
16
16
IEC 61131-2, type 1
2 Byte
green LED per channel
yes
yes, parameterizable
yes, parameterizable
yes
possible
green LED
none
none
-
16
ü
DC 500 V
2 / 48
0
0 / 66
16
101