Digital Modules FAST - SPEED-Bus
323-1BH70 - DIO 16xDC 24V 0.5A > Technical data
Order no.
Rated value
Input voltage for signal "0"
Input voltage for signal "1"
Input voltage hysteresis
Frequency range
Input resistance
Input current for signal "1"
Connection of Two-Wire-BEROs possible
Max. permissible BERO quiescent current
Input delay of "0" to "1"
Input delay of "1" to "0"
Number of simultaneously utilizable inputs horizontal con-
figuration
Number of simultaneously utilizable inputs vertical configu-
ration
Input characteristic curve
Initial data size
Technical data digital outputs
Number of outputs
Cable length, shielded
Cable length, unshielded
Rated load voltage
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)
Output current at signal "1", rated value
Output delay of "0" to "1"
Output delay of "1" to "0"
Minimum load current
Lamp load
Parallel switching of outputs for redundant control of a load not possible
Parallel switching of outputs for increased power
Actuation of digital input
Switching frequency with resistive load
Switching frequency with inductive load
Switching frequency on lamp load
Internal limitation of inductive shut-off voltage
Short-circuit protection of output
118
323-1BH70
DC 20.4...28.8 V
DC 0...5 V
DC 15...28.8 V
-
-
-
7 mA
ü
1.5 mA
parameterizable 2.56µs - 40ms
parameterizable 2.56µs - 40ms
16
16
IEC 61131-2, type 1
2 Byte
16
1000 m
600 m
DC 24 V
ü
50 mA
0.5 A
6.12 µs
6.12 µs
-
5 W
not possible
ü
max. 100 kHz
max. 0.5 Hz
max. 10 Hz
L+ (-52 V)
yes, electronic
VIPA System 300S