Understanding The Effects Of A Hard Drive Failure; Identifying A Compromised Fault Tolerance; Recovering From Compromised Fault Tolerance; Factors To Consider Before Replacing Hard Drives - HPE D6020 Maintenance And Service Manual

Disk enclosure
Hide thumbs Also See for D6020:
Table of Contents

Advertisement

Understanding the effects of a hard drive failure

If a hard drive fails, all logical drives that are in the same array are affected. Each logical drive
in an array may be using a different fault tolerance method, so each logical drive can be affected
differently.
RAID 0 configurations cannot tolerate a drive failure. If any physical drive in the array fails,
all non-fault-tolerant (RAID 0) logical drives in the same array will also fail.
RAID 1+0 configurations can tolerate multiple drive failures as long as no failed drives are
mirrored to one another (with no spares assigned).
RAID 5 configurations can tolerate one drive failure (with no spares assigned).
RAID 6 with ADG configurations can tolerate simultaneous failure of two drives (with no
spares assigned).

Identifying a compromised fault tolerance

CAUTION:
to recover the data. For more information, see
(page
46).
If more drives fail than the fault-tolerance method can manage, fault tolerance is compromised,
and the logical drive fails. If this failure occurs, the operating system rejects all requests and
indicates unrecoverable errors.
For example, fault tolerance might occur when a drive in an array fails while another drive in the
array is being rebuilt.
Compromised fault tolerance can also be caused by problems unrelated to drives. In such cases,
replacing the physical drives is not required.

Recovering from compromised fault tolerance

If fault tolerance is compromised, inserting replacement drives does not improve the condition
of the logical volume. Perform the following procedure to recover data:
1.
Check for loose, dirty, broken, or bent cabling and connectors on all devices.
2.
Power down the D6020 (see
3.
Power up the D6020 (see
In some cases, a marginal drive is operational long enough to allow backup of important
files.
4.
Make copies of important data, if possible.
5.
Replace any failed drives.

Factors to consider before replacing hard drives

You can replace hard drives without powering down the system. However, before replacing a
degraded drive:
Open HPE SIM and inspect the Error Counter window for each physical drive in the same
array to confirm that no other drives have any errors. (For details, refer to the HPE SIM
documentation on the Management CD.)
Be sure that the array has a current, valid backup.
Use replacement drives that have a capacity at least as great as that of the smallest drive
in the array. The controller immediately fails drives that have insufficient capacity.
46
Troubleshooting the system
If fault tolerance is compromised, data loss can occur. However, it may be possible
"Powering down" (page
"Powering up" (page
"Recovering from compromised fault tolerance"
18)).
18)).