Hobart 5359D Operation And Maintenance Manual page 60

Engine-driven generator set
Table of Contents

Advertisement

OM 2012
power supply
is turned ON
and OFF by a toggle
switch
(21,
Fig.
11) mounted
on
the engine
control
panel.
The toggle
switch
is equipped
with
o hinged
guard which
insures that the power supply
is OFF when the guard
is closed,
covering
the switch.
The guard may be safety-wired
In the closed
position
to prevent
inadvertent
operation
of the switch.
Refer to Figure
16.
When the toggle
switch
(7) is in the UP position,
24 volts DC
is present on terminal
E of the generator's
output
terminal
panel
(14,
Fig.
3) through
the following
circuitry.
Refer to diagrans
in Chapter
6 as required.
115 volts
AC
power into'the
power supply
is topped off the generator
output
line,
on the input
side of the load contactor.
The per
supply
is protected
by the fuse (6) in the
input line.
This 115 volts
input
is reduced
by the transformer
(3),
rectified
by the
diode
bridge
(2),
and filtered
by the capacitor
(4) and resistor
(5),
so that an un-
regulated
24 volts DC is provided
to terminal
E on the output
terminal
panel.
In
addition,
the plug interlock
relay (1, Fig.
10) is energized
to penit
power delivery
to the aircraft.
l-l
Page 36
Aug 25, '85